1.6 Electrical
Connections
This appliance must be electrically grounded
Supply 120V 60Hz single phase.
Standard heater 0.16HP.
Current rating 1.2 amp max (inductive).
Fuse: external 3 amp.
Important: All electrical work should be done by
a qualified electrician in strict accordance with
the National Electrical Code ANSI/NFPA 70 or
Canadian Codes CSA C22.1.
The electrical supply to the heater is by three
wires: live, neutral and ground connections.
Install in accordance with all state & local codes.
Where alternative manufacturers controls are
used, please refer to their instructions for siting
and installation details.
Table 3 Gas Supply Pressures
Gas Type
Natural Gas
LP/Propane Gas
Required Gas Pressure (in W.C) 60,000 to 150,000 btu
5.0 11.0
Required Gas Pressure (in W.C) 170,000 to 200,000 btu
7.0 11.0
Max Supply Pressure (in W.C)
14.0 14.0
Gas Supply
Connection ½” N.P.T thread
Switch with
Fuse
Fan plugs
into burner
Figure 5.a Typical U-Tube Range Wiring Connections
WARNING:
Before making electrical
connections, switch OFF the main
electrical disconnect. There may be more
than one disconnect switch. Lock out
and tag switch with a suitable warning
label.
Electrical
shock
can
cause
personal injury or death.
9
Figure 5.b Typical Linear Range Wiring Connections
Switch
with Fuse