Ambirad Vision VSX Servicing & Commissioning Manual Download Page 4

 

2. Commissioning 

Instructions. 

Check installation has 

been carried out to these 

instructions. 

NO 

YES 

Ensure gas and electricity 

supplies are isolated. 

Disconnect gas hose from 

burner 

Replace burner on tube 

and secure. 

Open control housing and 

check that all components 

are securely fastened. 

Close control housing 

Reconnect gas hose. 

Open isolating valve. 

Check soundness. 

Check thermostat is set to 

maximum and is calling 

for heat. 

A successful ignition is 
indicated by the amber 

light illuminating and  

remaining illuminated. 

The heater should now 

run through its start up 

sequence and ignite. 

Turn off power and check 

that all components are 

securely fastened. 

Check gas 

pressure. 

Remove burner from tube 

and inspect burner head. 

(See servicing instructions) 

Check operation of 
air pressure switch 

Leave the instructions 

with a responsible 

person. 

Injector pressure 
test point. 

Adjustment screw under 
cap to set injector pressure 

Figure 1. VSX Gas Valve adjustment 

 
These appliances should be commissioned by a qualified engineer.

 

2.1 Tools 

Required. 

 

The following tools and equipment are advisable 

to complete the tasks laid out in this manual.  

 

 Suitable alternative tools may be used.

 

 

 

S m a l l   F l a t 
Head 
Screwdriver 

 
 
 

Manometer 

 

 

Pozidrive 
Screwdriver 

 
 

Leather 
Faced 
Gloves 

 

4mm 
Allen 
Key 

 

12mm 
Spanner 

 

Large Adjustable  
Spanners or 22, 26 & 
27mm Spanners for 
fitting of Gas Flex. 

 

13mm 
Socket 

 
 

Wrench with 
Extension 

Switch on electrical supply. 

The red neon should now 

be illuminated. If restarting 

heater a delay of 15s 

should be allowed. 

 

Has the 

burner lit? 

Check operation on 

flame failure. 

Check gas pressure. 

Gas inlet 
test point 

Summary of Contents for Vision VSX

Page 1: ...ith the relevant provisions of the Gas Safety Installations and Use Regulations 1998 for gas fired products Due account should also be taken of any obligations arising from the Health and Safety at Wo...

Page 2: ...t tube heaters specified in these instructions due care 3 9 Reflector Servicing 3 10 Inspection of Flue 3 11 Re commissioning after Service 4 Spare Parts 5 Fault Finding Guide 6 Replacing Parts 6 1 Bu...

Page 3: ...2 8 2 4 450x5927x746 158 0 5 2560 VSX45UT 44 0 39 6 4 2 11 6 2 9 450x5927x746 158 0 5 2560 VSX50UT 49 5 44 6 4 7 12 8 2 5L 450x7692x746 205 0 5 2560 1 3 Table 1 Technical Details All heaters to run on...

Page 4: ...nd inspect burner head See servicing instructions Check operation of air pressure switch Leave the instructions with a responsible person Injector pressure test point Adjustment screw under cap to set...

Page 5: ...Wrench with 13mm Socket 12mm Spanner 3 1 Tools Required The following tools and equipment are advisable to complete the tasks laid out in this manual Suitable alternative tools may be used Large Adjus...

Page 6: ...nger and remove the flexible hose from the burner Step 6 Slacken the set screw on the burner support casting to enable the burner to be removed from the radiant tube Step 7 Remove the burner and posit...

Page 7: ...replaced ensuring the 5 holes on the outer ring are aligned alongside the probes Step 3 The condition of the igniter assembly can be checked for deterioration However we advise replacement at each ser...

Page 8: ...dust with a soft brush Step 6 Remove any dust from fan scroll and from around the motor Step 7 Ensure the impeller rotates freely Step 8 Refit components 3 7 Radiant Tube Servicing Step 1 Brush any d...

Page 9: ...hanger refit 3 9 Reflector Servicing The condition of the reflectors should be noted If necessary the reflectors can be cleaned with a mild detergent This can significantly improve the efficiency of t...

Page 10: ...ription See section 1 10 Injector 200358 Extruded Burner Head Item 201284 Ignitor Assembly Part No Description 200988 Pepperpot Head Item 2175 Amber Neon Burner On 2180 Red Neon Mains On 200420 Jet Ca...

Page 11: ...cuum switch pull in Check 1 Wiring harness plugs 2 Vacuum switch operation 3 Replace fan Is the burner sparking Does the gas valve open Check 1 Burner controller 2 Replace gas valve Check 1 Vacuum swi...

Page 12: ...tep 5 Fit new burner controller Step 6 Refit HT leads and refit burner controller to wiring harness Step 7 Test product and close access doors 6 2 Air Pressure Switch Replacement Step 1 Disconnect the...

Page 13: ...impulse tube and the burner head wiring Step 5 From within the combustion chamber remove the two screws holding the front of the gas valve Step 6 Turning the housing over remove the four screws holdin...

Page 14: ...and a mild detergent non solvent based cleaners only in water can be undertaken Additional removal of dust from the radiant tubes burner and heat exchanger can be undertaken 7 4 Frequency of Servicin...