44
To aid in the trouble shooting process
the UT controller has a LED flash code
diagnostic sequence:
Steady Off
No control Power
Steady On
Power Applied, Control OK
1 Flash
Combustion Pressure Switch Open With Blower On
2 Flashes
Combustion Pressure Switch Closed With Blower Off
3 Flashes
Lockout From The Three Ignition Trials
4 Flashes
Lockout From Five Flame Losses
5 Flashes
Control Hardware Fault Detected
6 Flashes
Lockout From Five Pressure Switch Losses