Ambirad AMBIRAD VISION VSX Series Installation And Operating Manual Download Page 10

Doc No. 700015  Page 10 of 36 

 

The flue system 

must be terminated vertically 

only 

and in accordance with the British 

 

 

 

 

 

 

Standard Code of Practice BS 5440: Part 1 - 
Installation  and  maintenance  of  flues  and     
ventilation for gas appliances of rated input not 
exceeding 70kW net (1st, 2nd and 3rd   family 
gases), and the flue system manufacturers 

 

 

instructions as supplied with the flue. 
 
 

1.8.2 Installation 
 

Connection to an appliance which is not 

 

 

 

 

 

 

 

connected to the fuel supply may be carried out 
by a competent person. However, connection to 
an appliance that is connected to the fuel supply 

must 

be carried out by a registered installer. 

 
If the flue passes through a wall, ceiling, or roof 
made from combustible material then it has to 
be sleeved so as to provide a minimum of a 
50mm void between the exterior of the flue and 
the  internal wall of the sleeve. A minimum of 
50mm must be maintained as a clearance 

 

 

 

distance to all other combustible materials. 
 
The manifold should be supported by chain, 
stainless steel flexible wire, or other flexible 
means from the roof structure to allow 

 

 

 

 

 

 

 

movement caused by thermal expansion. 
 
The maximum distance between supports is 
1.5m for horizontal runs. 
 
Wall bands are not load bearing and give lateral 
support only. If used, wall bands should be fitted 
every 3m on vertical runs to ensure the system 
is rigidly held. The system should be braced  
immediately below passing through the roof line 
to ensure the flashing does not suffer lateral 
pressures. 
 
The maximum height unsupported above the 
roof line is 1.5m. Where a joint is above the  
roofline it should be determined that in extreme 
wind conditions this joint would not be over      
exerted. If there is any doubt then a guy wire 
should be used. Beyond this guy wires should 
be installed every meter. 
 
The POCED is capable of withstanding its own 
weight when installed in accordance with these 
instructions and the Regulations shown below. 
 
The  exhaust  flue  should  be  adequately          
supported from the building structure and 

 

 

 

 

 

 

installed  in  accordance  with  the  British            
Standard Code of Practice BS 5440: Part 1 – 
Installation  and  maintenance  of  flues  and     
ventilation for gas appliances of rated  input not 

exceeding 70kW net (1st, 2nd and 3rd family 
gases), and the flue system manufacturers 

 

 

 

instructions as supplied with the flue. 
 
See reference BS 6896. Condensate drain 
pipes must be protected against the effects of 
freezing. 
 
 

1.8.3 Condensation 
 

When designing the flue system the prevention 
of 

the 

formation 

and 

entrapment 

of                

condensation must be a key consideration. 
 
Horizontal flue should be fitted ensuring a slight 
gradient approx 5

° 

towards the terminal. 

 
Where condensation is unavoidable traps 
should 

be 

included 

to 

encourage 

the             

condensates to flow freely to a point from which 
they may be released, preferably into a gully.  
The condensate pipe from the flue to the 

 

 

 

 

 

 

 

disposal point must be made from corrosion     
resistant pipe of not less than 25mm internal  
diameter. 

 
 
1.8.4 Method of Jointing Tube 

 
1.8.4.1 Option 1 

All  pipe  lengths  and  flue  gas  carrying            
components are joined together by a twist lock, 
bayonet system. The system should be installed 
with the visible male collar pointing upwards, 
this is reaffirmed by the directional arrow 

 

 

 

 

pointing upwards, indicating the directional flow 
of  flue  gases.  Taping  of  the  joints  is               
unnecessary. 
 

1.8.4.2 Option 3 

The components are joined by pushing the male 
spigot and female socket together until the stop 
is reached. No sealant is required, but can be 
applied if the formation of condensation is 

 

 

 

 

 

anticipated. 
 
To seal use an applicator gun and apply a 4mm 
diameter bead of high temperature silicon 

 

 

 

 

jointing compound externally round the end of 
the male spigot and internally round the end of 
the female socket. 
 
Push the male spigot into the female socket   
using a slight rotating movement to spread the 
jointing compound uniformly until both fittings 
have fully engaged. 
 

Note The silicon jointing compound remains 
workable after application for only 5 minutes

 

Summary of Contents for AMBIRAD VISION VSX Series

Page 1: ...tallation must be carried out in accordance with the current IEE wiring regulations BS 7671 BS 6896 Industrial Commercial and any other relevant British Standards and Codes of Practice by a quali ed i...

Page 2: ...ion Natural Ventilation 1 7 2 Flued Radiant Heater Mechanical Ventilation Natural Ventilation 1 8 Flue Combustion Air Inlet 1 8 1 Important Information 1 8 2 Flue Installation 1 8 3 Condensation Consi...

Page 3: ...See fig 1b Attachment to the heater support lugs should be made by a speed link D shackle or in the case of drop rods a closed formed hook The hanging attachments to overhead steelwork etc must be pur...

Page 4: ...ned maximum recommended angle of inclination is 15 Shackle method of attachment Pin must be tightened by pliers Drop rod with formed hook note hook or eyebolt must be closed tight 15 max THE HEATER SH...

Page 5: ...ances MUST be adhered to at all times VSXUT 20 25 30 35 40 45 50 Above Reflector A 100 100 100 Above Burner Heater Outlet B 500 500 500 To the Sides C 1300 1300 1300 Below Tubes D 2300 2500 2500 Horiz...

Page 6: ...her position in between these angles is acceptable A clearance distance x of min 200mm must be observed to allow side door access Care must be taken to observe the minimum pipe bend diameter minimum 2...

Page 7: ...Green Yellow Earth Blue Neutral Brown Live It is recommended the heater or group of heaters are controlled by thermostats a time switch and if required manual control switches and a frost thermostat...

Page 8: ...GREY WHITE FLAME SENSOR IGNITER 8 7 9 11 10 12 1 3 2 4 BLACK PINK WHITE LAMPS ON BURNER GREY YELLOW BLACK GRN YEL BROWN SOLENOID VALVE SWITCH N C N O C GREY EMC FILTER MAINS INPUT L N FAN N L ON MAIN...

Page 9: ...natural ventilation is required For detailed information please see BS6896 section 5 2 2 2 1 Mechanical Ventilation Mechanical ventilation must be installed to meet a minimum of 0 5 air changes per h...

Page 10: ...Regulations shown below The exhaust flue should be adequately supported from the building structure and installed in accordance with the British Standard Code of Practice BS 5440 Part 1 Installation...

Page 11: ...n K 127mm 5ins to 100mm 4ins Reducer L 127mm 5ins Twin Wall Flue Pipe Ducted air must be used in locations where there is airborne dust or where there is a polluted atmosphere e g Chlorinated Vapours...

Page 12: ...used in locations where there is airborne dust or where there is a polluted atmosphere e g Chlorinated Vapours Maximum length 9m Minimum diameter 100mm Maximum no of bends 2 Products of combustion to...

Page 13: ...ere is a polluted atmosphere e g Chlorinated Vapours Maximum length 9m Minimum diameter 100mm Maximum no of bends 2 Maximum flue length 9 0m 125mm Maximum no of bends 2 All flues must terminate vertic...

Page 14: ...44 0 39 6 4 2 11 6 2 9 450x5927x746 158 0 5 2560 VSX50UT4M 49 5 44 6 4 7 12 8 2 5L 450x7692x746 205 0 5 2560 VSX30UT3M 30 0 27 0 2 9 10 5 2 0 450x5927x746 158 1 0 2507 VSX45UT4M 44 0 39 6 4 2 11 6 2...

Page 15: ...o complete the tasks laid out in this manual Pozidrive Screwdriver Trestles Leather Faced Gloves Tape Measure Spanner Set 4 5mm Allen keys 2 2 4 Reflectors All reflectors AND canopies must be position...

Page 16: ...6x 2 3 Identification check list 2x 1x 1x 1x 4x 4x 5x 2x 2x 4x 3x 4x 10x M8 Full Nut 16x 22x 28x No 5 Torque Screw 13x 14x 15x Turbulators 2 2 6 Burner and Heat Exchanger Assembly Slide the burner ass...

Page 17: ...ide of End Caps if saw horses cannot be located ensure any alternative is sound and can carry the heater weight Methodology To cater for the expansion of the firing leg all U bolts on the firing leg e...

Page 18: ...n for location length 3 CAUTION SHARP EDGES 2x 3x 3x 5x Working at the opposite ends of the tubes to the burner locate position two couplers so that the socket heads are facing outwards the pre fitted...

Page 19: ...nd bracket 2 5 3 Reflectors 2x 3x 7 CAUTION SHARP EDGES Slide end reflector so that the innermost slotted holes line up with 1st bracket fixing holes then fix in place using M6 x 35mm pins washers nut...

Page 20: ...ng outwards 3x 3x 3x 3x 1x 2x 1x 2x 12 13 3x 3x 3x 3x 2x 2x 11 3x 3x 3x 3x 3x 2x 3x 3x 2 5 5 Canopies Remove protective film before starting Slide the outer canopies over the reflectors from the U ben...

Page 21: ...rofile at the U bend end fix with screws Repeat procedure for cut out canopy end cap again ensuring the flange faces inwards 2 5 6 Canopy End Caps 16 2x 2x 12x 12x CAUTION SHARP EDGES 17 1x 1x 1x 1x 2...

Page 22: ...700015 Page 22 of 36 2600mm 20kW ONLY 3400mm 25 30KW TURBULATORS 976mm TURBULATOR COUPLER 1365mm 1650mm 50 mm O LAP 50mm O LAP 38mm 150 4047mm REFERENCE 3400mm TUBE Y Z X Z Z W Y Y Figure 7 VSX2M 20...

Page 23: ...of 36 Figure 8 VSX3M 30 35 40 45 5927mm REFERENCE 50mm O LAP 50mm O LAP 50mm O LAP 50mm O LAP COUPLER 138mm 5200mm TUBE 1365mm 976mm TURBULATOR 2600mm TURBULATOR 150 2600mm TURBULATOR 1880mm 1650mm Y...

Page 24: ...90mm REFERENCE 50mm O LAP COUPLER 976mm TURBULATOR 1200mm 50mm O LAP 50mm O LAP 50mm O LAP 50mm O LAP 50mm O LAP 293mm 1880mm 1880mm 1650mm 150 COUPLER 3400mm TURBULATOR 3400mm TURBULATOR 50kW ONLY 52...

Page 25: ...Doc No 700015 Page 25 of 36 Figure 10 VSX Heater Breakdown 3 module shown...

Page 26: ...operation of air pressure switch Leave the instructions with a responsible person These appliances should be commissioned by a qualified engineer 3 1 Tools Required The following tools and equipment...

Page 27: ...1 Tools Required The following tools and equipment are advisable to complete the tasks laid out in this manual Suitable alternative tools may be used Large Adjustable Spanners or 22 26 27mm Spanners f...

Page 28: ...he heat exchanger and remove the flexible hose from the burner Step 6 Slacken the set screw on the burner support casting to enable the burner to be removed from the radiant tube Step 7 Remove the bur...

Page 29: ...pper pot burner head can be replaced ensuring the 5 holes on the outer ring are aligned alongside the probes Step 3 The condition of the igniter assembly can be checked for deterioration However we ad...

Page 30: ...nd remove any dust with a soft brush Step 6 Remove any dust from fan scroll and from around the motor Step 7 Ensure the impeller rotates freely Step 8 Refit components 4 7 Radiant Tube Servicing Step...

Page 31: ...the heat exchanger refit 4 9 Reflector Servicing The condition of the reflectors should be noted If necessary the reflectors can be cleaned with a mild detergent This can significantly improve the ef...

Page 32: ...section 1 10 Injector Item 201284 Ignitor Assembly Part No Description 200988 Pepperpot Head Item 2175 Amber Neon Burner On 2180 Red Neon Mains On 200420 Jet Carrier all except See Section 1 10 Combu...

Page 33: ...partment NO NO Does the vacuum switch pull in Check 1 Wiring harness plugs 2 Vacuum switch operation 3 Replace fan Is the burner sparking Does the gas valve open Check 1 Burner controller 2 Replace ga...

Page 34: ...ove Step 5 Fit new burner controller Step 6 Refit HT leads and refit burner controller to wiring harness Step 7 Test product and close access doors 7 2 Air Pressure Switch Replacement Step 1 Disconnec...

Page 35: ...5 From within the combustion chamber remove the two screws holding the front of the gas valve Step 6 Turning the housing over remove the four screws holding the rear burner plate in position Step 7 O...

Page 36: ...the heater is cold and mains electric isolated cleaning of the reflectors with a soft cloth and a mild detergent non solvent based cleaners only in water can be undertaken Additional removal of dust f...

Reviews: