Amana PTH123G25AXXX Installation Instructions & Owner'S Manual Download Page 18

18

DIAGNOSTIC CODES

C1

Indoor Coil is freezing up.

N

Y

Clean filter, Check for fan and blower operation,

Check for Refrigerant loss

or Restricted capillary tube.

C3

Indoor Coil is freezing up.

N

Y

Clean filter, Check for fan and blower operation,

Check for Refrigerant loss

or Restricted capillary tube.

C4

Indoor Coil froze up.

N

Y

Clean filter, Check for fan and blower operation,

Check for Refrigerant loss

or Restricted capillary tube.

C6

Poor Unit Performance.

N

Y

Check for blower motor, compressor,

or electric heat operation.

C7

Indoor Freezing Lockout (ICT - IAT > 20) +10 Min

N

Y

Clean filter, Check for fan and blower operation,

Check for Refrigerant loss

or Restricted capillary tube.

RE

F

R

IG

E

R

AT

IO

N

AL

E

R

T

S

STATUS

DISPLAY

ERROR 

LIGHT

SUGGESTED ACTION

FP

Freeze

 

Protection

 Engaged.  The  room temperature 

measured by the wireless remote thermostat or indoor ambient 
thermistor active sensor falls below 40°F.

Y

N

No Action required. This setting will disengage when the 

room temperature rises above 43°F.

Fd

Front

 

Desk 

switch is closed. All outputs are switched off.

Y

N

Open front desk switch to allow occupant unit operation.

Eo

Un-Configured Service Board - 

All operation held awaiting configuration

Y

Y

Enter Configuration Menu and set "C3" to "C"

for coolers with electric heat or "H" for heat pumps.

EH

Emergency Hydronic 

Engaged.  The EHH switch is closed.  

Compressor is switched off.

Y

N

Open front emergency hydronic switch to allow 

occupant unit operation.

LS

Load Shedding 

Engaged.  The LS switch is closed.  

Compressor and Electric heat is switched off.

Y

N

Open load shedding switch

to allow occupant unit operation.

On

Control is configured to respond to a wired thermostat

Y

N

No action if a wired thermostat is being used.

Otherwise, see Configuration Settings.

oP

Open Door Lockout

(DS1 & DS2 open; wireless)

Y

Y

Close Room Door.

Unit will not condition space with door open.

nP

Window Switch Lockout -

(LS & INN open)

Y

Y

Close Room Door or Window.

Unit will not condition space with door or window open.

HP

Heat Sentinel -

(WIAT > u3)

Y

N

No action required. This setting will disengage when

the room temperature falls.

Ur

Un-Rented Status

(EHH & INN or wireless)

Y

N

Front Desk needs to set to Rented mode (if applicable).

Indoor Ambient Thermistor reads outside the
range -20°F to 200°F 

&

 the wireless thermostat is not 

communicating to the unit control or

Indoor Ambient Thermistor (IAT) without a wireless remote 
thermostat reads outside the range -20°F to 200°F.

F2

Wireless Remote Thermostat failure

N

N

Replace Wireless Thermostat.

F3

Indoor Ambient Thermistor reads
outside the range -20°F to 200°F

Y

N

Replace black Indoor Ambient Thermistor.

F4

Indoor Coil Thermistor either above
or below operating tolerances.

N

Y

Replace Red Indoor Coil Thermistor .

F5

Wireless Thermostat failure.

N

Y

Attempt to rebind Wireless Thermostat

or Replace Wireless Thermostat.

F6

Indoor Discharge Thermistor either above
or below operating tolerances.

N

Y

Replace Yellow Indoor
Discharge Thermistor.

Fb

Low Remote Battery Warning.

N

Y

Replace Batteries in Wireless Devices.

H1

High Voltage Protection engaged. 
Power supply voltage is to high.

Y

N

Check for incoming power at correct voltage.

br

Brown Out Protection engaged.
Power was lost or voltage is low.

N

N

Check for incoming power at correct voltage.

L6

Discharge Air Too Hot.

N

Y

Clean Filter or Remove Air Blockage.

LC

Outdoor Coil Thermistor temperature high.

N

Y

Clean Condenser Coils, Check Fan for

fault. Code will reset after cleaning.

C2

Indoor Air Recirculation.  Large delta between thermostat and 
return.

N

Y

Clean Filter or Remove Air Blockage or Close

Vent Door or Improve indoor to outdoor seal.

C5

Outdoor Coil temperature too high for outdoor ambient 
temperature.

N

Y

Check for Blocked Outdoor Air or Clean Coil.

Replace black Indoor Ambient Thermistor or 

Wireless Remote Thermostat.

Y

Y

F1

CODE

AI

RF

L

O

W

 

AL

E

R

T

S

F

A

IL

URE

S

M

O

D

E

S

Summary of Contents for PTH123G25AXXX

Page 1: ...ruction Manual Pay special attention to all safety warn ings Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking...

Page 2: ...Goodman does not assume any respon sibility for property damage or personal injury for improper service procedures or services performed by an unqualified person IMPORTANT NOTES Your warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty certificate in a safe place so you can find it if necessary Before using this manual check the...

Page 3: ...ion and to indicate unit status The LEDs next to the selections OFF COOL and HEAT indicate which operational mode is active The LED located in the lower left corner is a status LED This LED indicates the status of the unit See Diagnostic Maintenance Status Report sec tion for further details 7 Button Touch Pad With Display Load shedding When input terminals have been config ured for load shedding ...

Page 4: ...age carrier should be notified as soon as possible preferably within 5 days 4 File the claim with the following supporting documents within the 6 month statute of limitations a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Original invoice or certified copy thereof showing trade and other discounts or reductions d Copy of the i...

Page 5: ...anel out diagonally from one side DRAIN KIT INSTALLATION OPTIONAL ACCESSORY During normal reverse cycle heating operation condensate water will drain out of the rear of the wall sleeve If this water is objectionable a drain kit should be installed The drain kit has provisions for draining the water from either the right or left side of the sleeve externally or from the bottom of the sleeve interna...

Page 6: ...etermine if the new chassis should be used with the non standard specialized grille An improper outdoor grille can decrease cooling or heating capacity increase energy usage and shorten compressor life and possibly void the warranty FRONT REMOVAL 1 Grasp the cabinet front Cabinet Front Removal View 1 2 Pull the bottom of the cabinet front away from the chassis until the retaining clips disengage N...

Page 7: ...nstalled with an existing subbase use the subbase cover extension kit 4 Check the indoor and outdoor grilles for obstructions to air flow The unit must be located where curtains furniture trees or other objects do not block the air flow to and from the unit If air is obstructed and or deflected back into the unit the air conditioner compressor may cycle on and off rapidly This could damage the com...

Page 8: ... the COOL thermostat control and the up or down arrows will provide a cooler room temperature Pressing the HEAT thermostat control and the up or down arrow keys will provide a warmer room temperature LCDI OR AFCI POWER CORD 230 208V and 115V units are equipped with LCDI or AFCI power cords and can open the electrical circuit to the unit In the event the unit does not operate check the reset button...

Page 9: ...an be used as a front desk switch The contact resistance of the switch when closed must be less than 200 ohms for the front desk feature to operate properly Table 3 shows the maximum wire length and corresponding gage size for installation of a front desk switch The following figure shows a wiring schematic for connecting the front desk switch to the unit If the unit is configured for wired unrent...

Page 10: ...pel air at either a 16 or 56 angle 16 Discharge Air 56 Discharge Air Discharge Grille Orientation Options Use the following procedure to change the angle of the discharge air flow 1 Remove the front cabinet see Front Removal 2 Position the front so that the backside is accessible Discharge Air Flow 3 Remove the four 4 screws which secure the discharge air grille to the cabinet front Location of 4 ...

Page 11: ...keep up with the heating load and a two stage thermostat is used COOL the selected room temperature is maintained by cycling the air conditioner Table 4 summarizes the thermostat input combinations and the respective unit functions The following wiring schematic illus trations show wiring schematics for heat pump and straight cool units with electric resistance heat respectively Heat Pump Thermost...

Page 12: ... the inlet air filters be cleaned once per month or more often if operated in dusty or dirty locations or conditions The intake air filters are con structed of durable polypropylene The air intake air filters can be easily inserted into the cabinet front using the cabinet filter guides Before cleaning the intake filter turn the unit off by setting the mode switch to the OFF position Filter should ...

Page 13: ...t must be cleaned more often A minimum of four 4 times a year will maintain proper opera tional conditions and protect unit components Wall Sleeve Clean the wall sleeve while cleaning the unit The caulking around the sleeve should be checked to make sure that any potential air and water openings around the sleeve are properly sealed The wall sleeve s level should also be rechecked Proper leveling ...

Page 14: ...perational mode of the fan in the ON position The fan will run continuously whenever power is applied in this mode In the AUTO position the fan will cycle on and off with the compressor or electric heater Starting delay You may notice a few minutes delay in the starting if you try to restart the unit too soon after turning it off or if you adjust the thermostat right after the compressor has shut ...

Page 15: ...es press the COOL key Once you have scrolled to the correct feature then to se lect the option code for your desired configuration press either the up or down key to scroll through the op tions of the selected feature code To exit configuration mode 1 Press the OFF key Configuration feature mode will also exit if no keys are pressed for a period of two 2 minutes ...

Page 16: ...Un rent HtnTemp 45 95 63 45 95 63 0 Not Twinned 5 Twinned F Fahrenheit Scale C Celsius Scale d6 Sensorless Un Occ Time 1 32 18 1 32 18 d7 1st Un Occ Set Back Temp 1 16 2 1 16 2 d8 1st Un Occ Set Back Time 1 5 1 24 1 5 1 24 5 d9 2nd Un Occ Set Back Temp 1 16 3 1 16 3 dA 2nd Un Occ Set Back Time 5 1 24 d8 24 1 db 3rd Un Occ Set Back Temp 1 16 6 1 16 6 dC 3rd Un Occ Set Back Time 1 24 3 dA 24 3 dF Pl...

Page 17: ...agnostic Status Report mode press and hold the up and down arrows and while holding quickly press the COOL key twice ACTIVE FAILURES If there are no active failures or lockouts the display will show a double dash If there is a code listed see the unit Diagnostic Codes chart for a list of defi nitions OPERATING TEMPERATURES If not in Diagnostic Status Report Mode enter as instructed above and press...

Page 18: ...t will not condition space with door open nP Window Switch Lockout LS INN open Y Y Close Room Door or Window Unit will not condition space with door or window open HP Heat Sentinel WIAT u3 Y N No action required This setting will disengage when the room temperature falls Ur Un Rented Status EHH INN or wireless Y N Front Desk needs to set to Rented mode if applicable Indoor Ambient Thermistor reads...

Page 19: ...19 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 20: ...0 Houston TX 77056 www amana ptac com 2014 2015 2017 Goodman Company L P is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company L P Houston TX USA All rights reserved ...

Reviews: