16
CONFIGURATION SETTINGS CHART
*Indicates factory default
See manufacturer for additional configuration options.
Configuration
Code
Configuration Feature
Option Code
Option
0 *
Chassis Membrane *
L5
Wired Thermostat
rE
Wireless Stat & 7-Button
L0
Locked Membrane
Au
do not use
On
do not use
bP
Button present
bA*
Revert to Cyclic
A
Always run fan (even if Off)
C
do not use
bC
Revert to Continuous
C
Cooler Only PTC
H*
Heat Pump PTH *
0
Sevice No Operation "Eo"
dC
Dry Cooler DRY
dH
do not use
uC
MTC Cooler
uH
MTH Heat Pump
C4
Room I.D. Digit 1 & 2
00* - 99
00* - 99
C5
Room I.D. Digit 3 & 4
00* - 99
00* - 99
0*
Off*
1
On
18
18 Hour Automatic Entry
C8
Temp. Limiting Cool
60* - 80
60* - 80
C9
Temp. Limiting Heat
68 - 90, 80*
68 - 90, 80*
c3
Un-rent ClnTemp.
45 - 95, 79*
45 - 95, 79*
c4
Un-rent HtnTemp.
45 - 95, 63*
45 - 95, 63*
0*
Not Twinned*
5
Twinned
F*
Fahrenheit Scale*
C
Celsius Scale
d6
Sensorless Un-Occ. Time
1 - 32, 18*
1 - 32, 18*
d7
1st Un-Occ. Set Back Temp.
1 - 16, 2*
1 - 16, 2*
d8
1st Un-Occ. Set Back Time
.1, .5*, 1 - 24
.1 ,.5 ,1 - 24, .5*
d9
2nd Un-Occ. Set Back Temp.
1 - 16, 3*
1 - 16, 3*
dA
2nd Un-Occ. Set Back Time
.5, 1* - 24
(d8) - 24, 1*
db
3rd Un-Occ. Set Back Temp.
1 - 16, 6*
1 - 16, 6*
dC
3rd Un-Occ. Set Back Time
1 - 24, 3*
(dA) - 24, 3*
dF
Platform Group Code
00* - 99
00* - 99
r4
Room Prefix
00* - 99
00* - 99
r5
Room Suffix
00* - 99
00* - 99
0*
Door Switch
1
Motion Sensor
2
Front Desk
3
Wired Un-rented Set Back
4
Emergency Hydronic
5
Load Shedding
6
Alarm Sensor
0*
Door Switch
1
Motion Sensor
2
Front Desk
3
Wired Un-rented Set Back
4
Emergency Hydronic
5
Load Shedding
6
Alarm Sensor
uL
Config. Security Code
00* - 99
00* - 99
CA
Wireless Twin Unit
C1
Interface
C2
ID Fan Operation
C3
Reverse Cycle Operation
C6
Wired Occupancy
u9
Input Pins UN2 & COM
Cd
English / Metric Temp
u8
Input Pins UN1 & COM