Amana PTAC DS02G-H Installation Instructions Manual Download Page 4

4

CONFIGURATION TABLE 

* Default Value

Configuration 

Code

Configuration Feature Description

Option

Option Code 

- -

Menu Start

press Fan button for 1st code

none

Ob

Wired T-stat reversing valve signal (“B” or “O”)

“B” T-stat Terminal

b

“O” T-stat Terminal * 

o *

HE

Unit Type

Heat Pump

HP

Cooler with Electric Heat *

EL * 

CL

Low Temperature Limited Set Point

60-91°F (but not more than CH); 64°F *

60-90; 64 *

CH

High Temperature Limited Set Point

60-92°F (but not less than CL); 82°F *

60-90; 82 *

db

Auto-Changeover Deadband °C

1.0-2.5, 2.2* °C (1.8-4.5, 4.0* °F)

1.0-2..5, 2.2*

CF

Display °F or °C Temperatures

Fahrenheit Scale *

F *

Celsius Scale 

C

LC

Compressor Lockout

Minimum 3-minute Compressor Lockout *

01 *

No Compressor Lockout

00

OC

Occupancy Enable

Enable Occupancy Detection

E

Disable Occupancy Detection *

d *

UC

Un-Occupied Cooling Setpoint

59-92 °F; 82°F *

59-92; 82 *

UH

Un-Occupied Heating Setpoint

58-91 °F; 64°F *

58-91; 64 *

nA

Network Address - Zibee Short Address

Read Only Points

(Press Up Button for) 1st two Hexidedimal Digits

00-FF

(Press Down Button for) 2nd two Hexidedimal Digits

00-FF

Fr

Factory Reset 

Reset to Factory Defaults

05

Hold Existing Defaults

00