Installation Instructions
4
HOOD EXHAUST
NOTE: Read these next two pages only if you plan to vent your exhaust to the outside. If you plan to
recirculate the air back into the room, proceed to page 11.
OUTSIDE TOP EXHAUST (EXAMPLE ONLY)
The following chart describes an example of one possible ductwork installation.
* IMPORTANT:
If a rectangular-to-round transition adaptor is used, the bottom corners of the damper will have
to be cut to fit, using the tin snips, in order to allow free movement of the damper.
DUCT PIECES
EQUIVALENT
LENGTH
x
NUMBER
USED
=
EQUIVALENT
LENGTH
Roof Cap
24 Ft.
x
(1)
=
24 Ft.
12 Ft. Straight Duct (6"
Round)
12 Ft.
x
(1)
=
12 Ft.
Rectangular-to-Round
Transition Adaptor*
5 Ft.
x
(1)
=
5 Ft.
Equivalent lengths of duct pieces are based on actual
tests and reflect requirements for good venting
performance with any vent hood.
Total Length
=
41 Ft.
OUTSIDE BACK EXHAUST (EXAMPLE ONLY)
The following chart describes an example of one possible ductwork installation.
NOTE:
For back exhaust, care should be taken to align exhaust with space between studs, or wall should be
prepared at the time it is constructed by leaving enough space between the wall studs to accommodate
exhaust.
DUCT PIECES
EQUIVALENT
LENGTH*
x
NUMBER
USED
=
EQUIVALENT
LENGTH
Roof Cap
40 Ft.
x
(1)
=
40 Ft.
3 Ft. Straight Duct
(3¼" x 10"
Rectangular)
3 Ft.
x
(1)
=
3 Ft.
90° Elbow
10 Ft.
x
(2)
=
20 Ft.
Equivalent lengths of duct pieces are based on actual
tests and reflect requirements for good venting
performance with any vent hood.
Total Length
=
63 Ft.
Summary of Contents for MMV1175JZ
Page 23: ...Installation Instructions 23 NOTE ...
Page 24: ...Part No 8101P710 60 Form No Code No DE68 03141B ...
Page 47: ...Instrucciones de instalación 23 NOTA ...
Page 48: ...N º pieza 8101P710 60 Formulario A 08 05 N º de código DE68 03141B ...
Page 71: ...Instructions d installation 23 REMARQUE ...
Page 72: ...Référence 8101P710 60 N formulaire A 08 05 Code n DE68 03141B ...