background image

2

What Is An Amana Media Air Cleaner?

Your Amana Media Air Cleaner is a high efficiency air
filtration device designed to remove dirt, dust, pollen, and
other microscopic particles from the air passing through it.
Considering the messy dirt collecting job it performs, you
will be surprised at the simplicity of its operation and care.

How The Air Cleaner Works

Dirty air enters the air cleaner by way of the return air duct
system in your home.  Particles are collected by the special
pleated filter media.  The pleats provide an exceptionally
large filtering face area in a very compact space which
allows maximum dirt holding capacities with minimum air
flow resistance.

Application

The air cleaner is used with Amana’s gas furnaces and
blower coils.  The air cleaner should be installed in the
system so that all the system air is circulated through the air
cleaner.  The air cleaner will only remove the airborne
contaminants delivered to it.  Maximum performance is
obtained when the system blower is set for continuous
operation.

INSTALLATION REQUIREMENTS

The best location for the air cleaner is in the return air duct
next to the blower compartment.  In this location, the blower
motor and cooling coils will be kept clean.  

Do not install

the air cleaner in the discharge air duct.

  Before installing

the air cleaner, consider the application.  If a transition is
required, refer to section entitled “

Transitions

”. The unit

must be readily accessible for periodic inspection and
replacement of the media cartridge to maintain maximum
efficiency and trouble-free operation.

AIR CONDITIONING

The air cleaner should be installed upstream of the cooling
coil.  This will keep the coil clean and reduce air conditioning
coil maintenance.  Improved cooling efficiency directly
affects energy costs.  A clean coil will reduce utility costs.
Failure to replace the media cartridge can cause damage
to the cooling system.

HUMIDIFIERS

Location of the system humidifier is important to the opera-
tion of the air cleaner.

When an evaporative type humidifier is used, it may be
installed between the furnace warm air duct and the return
air duct without affecting the air cleaner.  Atomizing and
spray type humidifiers should be installed downstream of
the air cleaner.  If it must be installed upstream allow at least
6’ between air cleaner and humidifier.

TRANSITIONS

If the air duct does not fit the air cleaner cabinet opening,
gradual transitions are recommended to reduce air turbu-
lence through the air cleaner and maximize efficiency.  Not
more than 20° (about 4” per lineal foot) of expansion should
be used on each side of the transition fitting (Figure 1).

AIR FLOW

AIR FLOW

FURNACE
OPENING

AIR CLEANER

AIR CLEANER
OPENING

MAXIMUM 4" DROP
PER LINEAL FOOT

TRANSITION SECTION

FURNACE

Figure 1

TURNING VANES

If the air cleaner is installed adjacent to a 90° duct elbow,
add turning vanes inside the duct to improve the air distri-
bution across the face of the air cleaner (Figure 2).

Summary of Contents for MEDIA

Page 1: ...autions listed here take precedence Comfort Quality Trust Heating Air Conditioning May 2002 20182003 Dear Owner Congratulations on your choice of an Amana Media Air cleaner You can now look forward to year after year of clean air living As you become better acquainted with your Amana Media Air Cleaner we believe you will agree that it is one of the best investments you have ever made Thefollowingi...

Page 2: ...efer to section entitled Transitions The unit must be readily accessible for periodic inspection and replacement of the media cartridge to maintain maximum efficiency and trouble free operation AIR CONDITIONING The air cleaner should be installed upstream of the cooling coil Thiswillkeepthecoilcleanandreduceairconditioning coil maintenance Improved cooling efficiency directly affects energy costs ...

Page 3: ...accordingtostateand local codes 5 The air cleaner cannot remove existing dirt from the blower and ducts Clean the area thoroughly before you begin 6 Remove unit access panel and media filter from the cabinet NOTE The following is a typical installation of the air cleaner on an upflow furnace Figure 6 You may have to alter the installation to fit your application 7 Locate the cabinet in the cold ai...

Page 4: ...ionAirBear filtercartridge Thefrequencyoffilter replacement is best determined by visual examination Steps For Replacing Filter 1 Disconnect furnace blower cabinet power 2 Open access door by pulling the handle Remove door completely 3 Pull used filter straight out of cabinet 4 Slide new filter cartridge into cabinet with AIR FLOW arrow pointing in the direction of air flow 5 Replace door Note You...

Page 5: ...If there is less than 7 in for mounting the air cleaner between the duct and the unit move the return air drop UPFLOW HORIZONTAL INSTALLATION Mounted vertically in return duct as close to the unit as possible Figure 5 Installation beneath unit Cleaner mounts horizontally where return air enters from below Raise unit by installing a suitable wood structure and install air cleaner SHEET METAL TRANSI...

Page 6: ...ons Product is operated in a corrosive environment containing concentrations of corrosive agents causing deterioration of metal components OWNER S RESPONSIBILITIES Provide proof of purchase sales receipt Provide normal care and maintenance Make product reasonably accessible for service Pay for freight labor and travel Pay for service costs for service outside servicer s normal business hours Pay f...

Reviews: