background image

7

inside of cap. Tighten cap finger-tight and then tighten 

additional 1/6 of a turn (1 wrench flat), or to the following 

specification, to properly seat the sealing surfaces.

1.  3/8” valve to 5 - 10 in-lbs

2.  5/8” valve to 5 - 20 in-lbs

3.  3/4” valve to 5 - 20 in-lbs

4.  7/8” valve to 5 - 20 in-lbs

Do not introduce liquid refrigerant from the cylinder into 

the crankcase of the compressor as this may damage the 

compressor.

CAUTION

POSSIBLE REFRIGERANT LEAK

 

To avoid a possible refrigerant leak, open the service valves 

until the top of the stem is 1/8” from the retainer.

1.  Break vacuum by fully opening liquid and suction 

base valves. 

2.  Set thermostat to call for cooling. Check indoor and 

outdoor fan operation and allow system to stabilize 

for 10 minutes for fixed orifices and 20 minutes for 

expansion valves.

Charge Verification

WARNING

REFRIGERANT UNDER PRESSURE!

• 

Do not overcharge system with refrigerant.

• 

Do not operate unit in a vacuum or at negative pressure.

Failure to follow proper procedures may cause property 

damage, personal injury or death.

CAUTION

Use refrigerant certified to AHRI standards. Used 

refrigerant may cause compressor damage. Most portable 

machines cannot clean used refrigerant to meet AHRI 

standards.

NOTICE

Violation of EPA regulations may result in fines or other 

penalties.

CAUTION

Damage to the unit caused by operating the compressor with 

the suction valve closed is not covered under the warranty 

and may cause serious compressor damage.

Final Charge Adjustment

Airflow and Total Static Pressure for the indoor unit should 

be verified before attempting to charge system.

1.  Total static pressure is .5” WC or less.

2. 

Airflow is correct for installed unit.

3. 

Airflow tables are in the installation manual and Spec 

Sheet for Indoor Unit.

4.  Complete charging information are in Service Manual 

RS6200006.

NOTE: Superheat adjustments should not be made 

until indoor ambient conditions have stabilized. 

This could take up to 24 hours depending on 

indoor temperature and humidity. Before checking 

superheat run the unit in cooling for 10-15 minutes 

or until refrigerant pressures stabilize. Use the 

following guidelines and methods to check unit 

operation and ensure that the refrigerant charge 

is within limits. 

The outdoor temperature must be 60°F or higher. Set the 

room thermostat to COOL, fan switch to AUTO, and set the 

temperature control well below room temperature.

Units matched with indoor coils equipped with a non-

adjustable TXV should be charged by Subcooling only. 

Superheat on indoor coils with adjustable TXV valves are 

factory set and no adjustment is normally required during 

startup. Only in unique applications due to refrigerant 

line length, differences in height between the indoor 

and outdoor unit and refrigerant tubing sizes or poor 

performance should Superheat setting require adjustment. 

These adjustments should only be performed by 

qualified service personnel. For detailed charge and TXV 

adjustments refer to the appropriate Service Manual.

Fixed Orifice

CAUTION

To prevent personal injury, carefully connect and 

disconnect manifold gauge hoses. Escaping liquid 

refrigerant can cause burns. Do not vent refrigerant into 

the atmosphere. Recover all refrigerant during system 

repair and before final unit disposal.

1. 

Purge gauge lines. Connect service gauge manifold 

to base-valve service ports. Run system at least 10 

minutes to allow pressure to stabilize.

2.  Temporarily install a thermometer 4-6” from 

the compressor on the suction line. Ensure the 

thermometer makes adequate contact and is insulated 

for best possible readings. Use vapor temperature to 

determine superheat.

3.  Refer to the superheat table provided for proper 

system superheat. Add charge to lower superheat or 

recover charge to raise superheat.

4.  Disconnect manifold set, installation is complete.

Superheat Formula = Suct. Line Temp. - Sat. Suct. 

Temp.

Summary of Contents for ASXH3 Series

Page 1: ...DO NOT BYPASS SAFETY DEVICES SHIPPING INSPECTION Always keep the unit upright laying the unit on its side or top may cause equipment damage Shipping damage and subsequent investigation is the respons...

Page 2: ...on Ensure the foundation is sufficient to support the unit A concrete slab raised above ground level provides a suitable base ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof st...

Page 3: ...igid wire or straps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line These sizes are recommended for...

Page 4: ...rmation of copper oxide inside the refrigerant lines The POE oils used in R 410A applications will clean any copper oxide present from the inside of the refrigerant lines and spread it throughout the...

Page 5: ...e system mechanical seals 2 Evacuate the system to less than 500 microns 3 Isolate the pump from the system and hold vacuum for 10 minutes minimum Typically pressure will rise slowly during this perio...

Page 6: ...l panel cover THERMOSTAT SINGLE STAGE HEATING WITH SINGLE STAGE COOLING Single Stage Thermostat with Two Low Voltage Wires to Remote SYSTEM START UP CAUTION POSSIBLE REFRIGERANT LEAK To avoid a possib...

Page 7: ...Superheat adjustments should not be made until indoor ambient conditions have stabilized This could take up to 24 hours depending on indoor temperature and humidity Before checking superheat run the...

Page 8: ...0 13 15 19 23 24 25 6 9 11 15 20 21 23 7 12 17 18 20 8 13 15 16 7 10 11 13 7 8 10 7 8 7 105 110 115 75 80 85 90 95 100 System Superheat Targets for Piston Match ups 1 0 F Indoor Wet Bulb Temperature F...

Page 9: ...D SUCTION PRESSURE TEMPERATURE CHART LIQUID PRESSURE SATURATED LIQUID TEMPERATURE F PSIG R 410A 200 70 210 73 220 76 225 78 235 80 245 83 255 85 265 88 275 90 285 92 295 95 305 97 325 101 355 108 375...

Page 10: ...y ADVANCED ADJUSTMENT RECOMMENDATIONS NOTE Units matched with indoor coils equipped with a TXV should be charged by Subcooling only SUPERHEAT FORMULA SUCTION LINE TEMPERATURE SATURATED SUCTION TEMPERA...

Page 11: ...n Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage or Refrigerant Test For Leaks Add Refrigerant Restrict...

Page 12: ...is important to keep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people coul...

Page 13: ...tdoor Unit Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING...

Page 14: ...14 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 15: ...15 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 16: ...ration Amana Brand products http www amana hac com product registration You can also scan the QR code on the right for the product brand you purchased to be directed to the Product Registration page N...

Reviews: