background image

29

PACKAGE UNITS 

  - DUAL FUEL  & GAS                                                                                                                           

HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed

by a 

qualified service agency

 before the heating and cooling seasons begin.

WARNING

High Voltage!

Disconnect ALL power before servicing or 

installing thus unit. Multiple power sources may 

be present. Failure to do so may cause property 

damage, personal injury, or death.

Replace or Clean Filter

IMPORTANT NOTE: 

Never operate unit without a filter in

-

stalled as dust and lint will build up on internal parts resulting 

in loss of efficiency, equipment damage and possible fire. 
A return air filter is not supplied with this unit; however, there 

must be a means of filtering the return air. An indoor air filter 

must be used with your comfort system. A properly main-

tained filter will keep the indoor coil of your comfort system 

clean. A dirty coil could cause poor operation and/or severe 

equipment damage.

The installer of your unit can tell you where your filter(s) are 

and how to clean or replace them.

Check your return filter(s) at least once every two months. 

When they are dirty, replace or clean as required. Dispos-

able type filters should be replaced. Reusable type filters 

may be cleaned.

NOTE:

 Reusable type filters should be washed with warm 

water, dried completely and sprayed with an adhesive ac-

cording to the manufacturers recommendations. 

                                

You may want to ask your dealer about high efficiency filters. 

High  efficiency  filters  are  available  in  both  electronic  and 

non-electronic  types. These  filters  can  do  a  better  job  of 

catching small airborne particles.

Improper filter maintenance is the most common cause of 

inadequate heating or cooling performance. Filters should 

be cleaned (permanent) or replaced (disposable) every two 

months or as required. When replacing a filter, it must be 

replaced with a filter of the same type and size and always 

make  certain  the  air  flow  arrows  on  the  filter  point  in  the 

proper direction.

Condenser, Evaporator and Induced Draft Motors

The bearings on the air circulating blower motor, condenser 

motor and the combustion fan motor are permanently lubri-

cated and  require no further lubrication.

Compressor

The compressor motor is hermetically sealed and does not 

require additional oiling.

Annual Inspection (Qualified Servicer Only)

Your package unit should be inspected by a qualified install

-

er, or service agency at least twice every year. This check 

should be performed before the heating and cooling sea-

sons begin. This will ensure that adequate combustion air is 

being drawn and the vent system is working properly. Partic-

ular attention should be paid to the following items. Repair 

as necessary.

•      Check physical support of the unit. Ensure it is sound 

without any sagging, cracks, or gaps, around the 

base.

•       Check for obvious signs of deterioration of the unit.

•        Flue  Hood  and  Combustion Air  Inlet.  Check  for 

blockage (wasp nest, etc.) and corrosion.

Flue Hood (Qualified Servicer Only)

•   Return  Air Connection. Check for physical soundness 

and ensure that the connection is firmly sealed to the 

package unit casing.

•  

Heat  exchanger

. Check for corrosion and/or 

obstructions within the heat exchanger passageways.

•   Burners.

 Check for proper ignition, burner flame, and 

flame sense.

•   Wiring. Check wires for damage. Check electrical 

connections for tightness and/or corrosion.

•   Filters

. Check that filters are clean and in the proper 

placement in the unit or duct system.

•   Louvers. Inspect air inlet louvers inside the heat 

exchanger compartments. Ensure the area is clean 

and free of dirt and debris.

Clean Outside Coil (Qualified Servicer Only)

The outdoor coil should be inspected annually. It is important 

to keep the outdoor coil clean. Dirt, leaves, or debris could 

restrict the airflow. If cleaning of the outdoor coil becomes 

necessary,  hire  a  qualified  servicer.  Inexperienced  people 

could easily puncture the

 

tubing in the coil. 

 

Before Calling Your Servicer

• 

Check the thermostat

 to confirm that it is properly 

set.

• 

Check  the disconnect switch

 near the unit to confirm 

that it is closed.

• 

Check the electrical panel  for tripped circuit breakers  

or failed  fuses . Reset the circuit breakers or replace 

fuses as necessary. 

• 

Check  for blockage of the indoor air inlets and 

outlets

.  Confirm  that  they  are  open  and  have  not 

been blocked by objects (rugs, curtains or furniture).

• 

Check  for obstructions on the unit

 . Confirm that it has 

not been covered on the sides or the top. Remove 

any obstruction that can be safely  removed. If  the 

unit  is  covered  with  dirt  or  debris,  call  a  qualified 

servicer to clean it. 

• 

Check the filter

. If it is dirty, clean or replace it.

Summary of Contents for APG 16 M Series

Page 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Page 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Page 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Page 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Page 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Page 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Page 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Page 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Page 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Page 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Page 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Page 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Page 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Page 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Page 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Page 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Page 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Page 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Page 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Page 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Page 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Page 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Page 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Page 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Page 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Page 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Page 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Page 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Page 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Page 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Reviews: