FURNACE SPECIFICATIONS

9

1.

These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.

2.

For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.

3.

The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.

4.

Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.

Unit specifications are subject to change without notice. 

ALWAYS

 refer to the unit's serial plate for the most up-to-date general and electrical information.

(1) 

Wire size should be determined in accordance with National Electrical Codes.  Extensive wire runs will require larger wire sizes.

(2)

 Maximum Overcurrent Protection Device: May use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.

(3) 

See Installation Instructions for appropriate vent diameter, length and number of elbows.

AMS8

MODEL

A

M

S

8

0

403

A

X

A

M

S

8

0

603

A

X

A

M

S

8

0

604

B

X

A

M

S

8

0

804

B

X

A

M

S

8

0

805

C

X

A

M

S

8

1

005

C

X

A

M

S

8

1

205

D

X

A

M

S

8

1

405

D

N

Btuh Input (US) High Fire

40,000

60,000

60,000

80,000

80,000

100, 000

120, 000

140, 000

       Output (US) High Fire

32,000

48,000

48,000

64,000

64,000

80,000

96,000

112, 000

       A.F.U.E.

80%

80%

80%

80%

80%

80%

80%

80%

Rated External Static (" w.c.)

.20 - .50

.20 - .50

.20 - .50

.20 - .50

.20 - .50

.20 - .50

.20 - .50

.20 - .50

Temperature Rise (°F)

25 - 55

25 -55

20 - 50

35 - 65

35 - 65

35 - 65

40 - 70

40 - 70

High Stage Pressure Switch
       Trip Point (" w.c.)

-0.70

-0.75

-0.75

-0.70

-0.75

-0.70

-0.80

-0.80

Blower Wheel (D" x W")

10 X 6

10 x 6

10 x 8

10X8

10x10

10X10

11x10

11x10

Blower Horsepower

1/3

1/3

1/2

1/2

1/2

1/2

3/4

3/4

Blower  Speeds 

4

4

4

4

4

4

4

4

       Max CFM @ 0.5 E.S.P.

1298

1157

1883

1725

1960

1974

2131

2131

Power Supply

115-60-1

115-60-1

115-60-1

115-60-1

115-60-1

115-60-1

115-60-1

115-60-1

       Minimum Circuit Ampacity (MCA)

(1)

8.5

8.5

12.9

12.9

12.9

12.9

15.2

15.2

       Maximum Overcurrent  Device

(2)

15

15

15

15

15

15

15

15

Transformer (VA)

40

40

40

40

40

40

40

40

Heat Anticipator (Amps)

0.7

0.7

0.7

0.7

0.7

0. 7

0. 7

0. 7

Primary Limit Setting (°F)

210°

150°

150°

150°

160°

150°

160°

160°

Auxiliary Limit  Setting (°F)

120°

120°

120°

120°

120°

120°

120°

120°

Rollout Limit Setting (°F)

300°

300°

300°

300°

300°

300°

300°

300°

Gas Supply Pressure
         (Natural/Propane) (" w. c.)

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

Manifold Pressure
     (Natural/Propane) High Stage (" w.c.)

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

Orifice Size (Natural/Propane)

#45 / #55

#45 / #55

#45 / #55

#45 / #55

#45 / #55

#45 / #55

#45 /  #55

#43 /  #55

Number  of  Burners

2

3

3

4

4

5

6

6

Vent  Connector Diameter (inches)

(3 )

4

4

4

4

4

4

4

4

Shipping Weight (lbs.)

84

88

98

106

114

118

130

130

Summary of Contents for AMS80403AX

Page 1: ...006 for troubleshooting information Refer to the appropriate Parts Catalog for part number information Model numbers listed on page 3 AMS8 33 3 8 Gas Furnace Units 80 AFUE Single Stage Multi Speed Upf...

Page 2: ...damage personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you...

Page 3: ...Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise contact your local EP...

Page 4: ...cts An interlock switch prevents furnace operation if the inner blower door is not in place Keep the blower access door in place except for inspection and maintenance See illus tration on pages 5 and...

Page 5: ...e Entrance Alternate Induced Draft Blower Gas Line Entrance Gas Valve Rollout Limit Junction Box Wiring Harness Grommet Gas Manifold Inshot Burner Blower Door Interlock Switch Integrated Control Modul...

Page 6: ...as Inlet High Voltage Inlet Low Voltage Alt Gas Inlet Alt High Voltage Alt LowVoltage M ODEL A B AM S80403AX AM S80603AX AM S80604BX AM S80804BX AM S80805CX AM S81005CX AM S81205DX AMS81405DN 24 1 2 2...

Page 7: ...X 0 80 0130F00042 AMS81405DN 0 80 0130F00042 Pressure Switch Trip Points Part Number 20162901 20162904 20162903 Open Setting F 210 150 160 AMS80403AX 1 AMS80603AX 1 AMS80604BX 1 AMS80804BX 1 AMS80805C...

Page 8: ...x 1 400 24 1 2 20 x 25 x 1 500 BOTTOM RETURN SIDE RETURN Refer to Minimum Filter Area tables to determine filter area requirement NOTE Filters can also be installed elsewhere in the duct system such...

Page 9: ...03AX AMS80604BX AMS80804BX AMS80805CX AMS81005CX AMS81205DX AMS81405DN Btuh Input US High Fire 40 000 60 000 60 000 80 000 80 000 100 000 120 000 140 000 Output US High Fire 32 000 48 000 48 000 64 00...

Page 10: ...22 1975 23 1883 24 1786 1700 1601 AMS80604BX MED 3 5 1668 27 1663 27 1656 27 1645 27 1616 28 1549 1492 1391 MEDIUM MED LO 3 0 1419 31 1426 31 1426 31 1432 31 1419 31 1378 1328 1261 LOW 2 5 1134 39 114...

Page 11: ...0 120 100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULA...

Page 12: ...SEE SPEC SHEET FOR AIR FLOW CHART REQUIREMENTS SO AS TO PROVIDE THE CORRECT HEATING TEMPERATURE RISE AND THE 4 BLOWER SPEEDS MUST BE ADJUSTED BY INSTALLER TO MATCH THE INSTALLATION INTEGRATED CONTROL...

Page 13: ...his schematic is for reference only Not all wiring is as shown above Always refer to the appropriate wiring diagram for the unit being serviced 0005 3M K5 K2 HEAT COOL PARK PARK CIR NEU K8 GAS VALVE H...