Great user manuals database on
BLOWER PERFORMANCE SPECIFICATIONS
13
NOTES:
1.
CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer.
2.
All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed.
3.
For most jobs, about 400 CFM per ton when cooling is desirable.
4.
INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
5.
The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded area indicates
ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for air conditioning purposes only.
6
The dashed (---) areas indicate a temperature rise not recommended for this model.
7.
The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise at a
particular CFM, while the ESP at that CFM will be lower.
Tons AC
at 0.5"
0.6
0.7
0.8
ESP
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
HIGH
3.0
1521
22
1466
23
1414
24
1373
24
1298
26
1243 1164 1075
*M(H/S)80453A***
MED
2.5
1160
29
1160
29
1132
29
1121
30
1082
31
1042
997
925
(MEDIUM)
MED-LO
2.0
961
35
955
35
948
35
932
36
913
37
882
821
803
LOW
1.5
781
43
785
42
781
43
773
43
761
44
745
716
668
HIGH
3.0
1422
36
1352
38
1307
40
1197
43
1157
45
1092 1075
983
*M(H/S)80703A***
MED
2.5
1098
47
1081
48
1051
49
1039
50
1021
51
983
924
868
(MEDIUM)
MED-LO
2.0
919
56
913
57
892
58
847
----
829
----
818
792
728
LOW
1.5
758
----
741
----
741
----
733
----
699
----
677
649
626
HIGH
4.0
2134
----
2100
25
2042
25
1975
26
1883
28
1786 1700 1601
*M(H/S)80704B***
MED
3.5
1668
31
1663
31
1656
31
1645
32
1616
32
1549 1492 1391
(MEDIUM)
MED-LO
3.0
1419
37
1426
36
1426
36
1432
36
1419
37
1378 1328 1261
LOW
2.5
1134
46
1145
45
1166
44
1171
44
1160
45
1144 1111 1071
HIGH
3.0
1607
41
1572
42
1547
43
1498
45
1448
46
1390 1302 1222
*M(H/S)80903B***
MED
2.5
1159
58
1156
58
1145
58
1127
59
1108
60
1075 1033
957
(MEDIUM)
MED-LO
2.0
938
----
916
----
916
----
900
----
889
----
865
829
785
LOW
1.5
785
----
766
----
743
----
730
----
709
----
683
666
604
HIGH
4.0
2051
----
1983
----
1895
35
1812
37
1725
39
1627 1530 1439
*M(H/S)80904B***
MED
3.5
1736
38
1708
39
1652
40
1611
41
1540
43
1475 1394 1307
(MEDIUM)
MED-LO
3.0
1493
45
1668
40
1459
46
1429
47
1389
48
1339 1274 1204
LOW
2.5
1200
56
1185
56
1180
56
1173
57
1158
58
1125 1125 1080
HIGH
5.0
2290
----
2229
----
2155
----
2047
----
1960
----
1837 1712 1584
*M(H/S)80905C***
MED
4.0
1852
36
1820
37
1777
38
1719
39
1641
41
1567 1469 1382
(MEDIUM)
MED-LO
3.5
1615
41
1592
42
1556
43
1516
44
1470
45
1405 1346 1235
LOW
3.0
1290
52
1285
52
1265
53
1235
54
1214
55
1174 1044
904
HIGH
5.0
2323
37
2225
38
2120
40
2040
42
1974
43
1801 1688 1577
*M(H/S)81155C***
MED
4.0
1858
46
1847
46
1799
47
1744
49
1674
51
1577 1493 1399
(MEDIUM)
MED-LO
3.5
1596
53
1587
54
1571
54
1552
55
1493
57
1397 1326 1217
LOW
3.0
1291
----
1272
----
1261
----
1257
----
1205
----
1168 1118 1060
HIGH
5.0
2469
42
2389
43
2300
45
2223
47
2131
49
2027 1902 1786
*M(H/S)81405D***
MED
4.0
1575
66
1558
67
1545
67
1513
69
1500
69
1419 1354 1271
(MEDIUM)
MED-LO
3.5
1402
----
1380
----
1343
----
1319
----
1296
----
1245 1183 1106
LOW
3.0
1200
----
1186
----
1161
----
1127
----
1082
----
1042
995
926
(CFM & Temperature Rise vs. External Static Pressure)
0.1
0.2
0.3
0.4
0.5
Model
Heating Speed
As Shipped
Motor
Speed
EXTERNAL STATIC PRESSURE (Inches Water Column)
(
)