Amana AMAP084AW Use And Care Manual Download Page 10

10

The power supply cord is unplugged. Plug into a grounded

3-prong outlet. See “Electrical Requirements. ”

The power supply cord has tripped (Reset button has popped

out). Press and release RESET to resume operation.

A household fuse has blown, or circuit breaker has tripped.

Replace the fuse or reset the circuit breaker. If the problem

continues, call an electrician. See “Electrical Requirements. ”

The Power button has not been pressed. Press POWER.

The local power has failed. Wait for power to be restored.

The internal water tank is full. If the “Bucket Full” indicator is

lit, empty the internal tank. See “Draining the Internal Tank”.

Air conditioner blows fuses or trips 

circuit breakers

Too many appliances are being used on the same circuit.

Unplug or relocate appliances that share the same circuit.

Time-delay fuse or circuit breaker of the wrong capacity is

being used. Replace with a time-delay fuse or circuit breaker

of the correct capacity. See “Electrical Requirements.”

You are trying to restart the air conditioner too soon after

turning off the air conditioner. Wait at least 3 minutes after

turning off the air conditioner before trying to restart the air

conditioner.

Air conditioner power supply cord trips 

(Reset button pops out)

Disturbances in your electrical current can trip (Reset button

will pop out) the power supply cord. Press and release RESET

to resume operation.

Electrical overload, overheating, a pinched cord, or aging can

trip the power supply cord (Reset button will pop out). After

correcting the problem, press and release RESET to resume

operation.

NOTE:

 A damaged power supply cord must be replaced with a 

new power supply cord obtained from the product manufacturer 

and must not be repaired.

Air conditioner will not operate

TROUBLESHOOTING

Before calling for service, try the suggestions below to see whether you can solve your problem without outside help.

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, 
fire, or electrical shock.

WARNING

Air conditioner seems to run too much

The current air conditioner replaced an older model. The use

of more efficient components may cause the air conditioner

to run longer than an older model, but the total energy

consumption will be less. Newer air conditioners do not emit

the “blast” of cold air you may be accustomed to from older

air conditioners, but this is not an indication of lesser cooling

capacity or efficiency. Refer to the efficiency rating (EER) and

capacity rating (in BTU/h) marked on the air conditioner.

The air conditioner is in a heavily occupied room, or heat-

producing appliances are in use in the room. Use exhaust

vent fans while cooking or bathing and try not to use heat-

producing appliances during the hottest part of the day. A

higher capacity air conditioner may be required, depending

on the size of the room being cooled .

Air conditioner cycles on and off too 

much or does not cool room in  

cooling mode

The air conditioner is not properly sized for your room. Check

the cooling capabilities of your room air conditioner. Room air

conditioners are not designed to cool multiple rooms.

The filter is dirty or obstructed by debris. Clean the filter.

There is excessive heat or moisture (open container cooking,

showers, etc.) in the room. Use a fan to exhaust heat or

moisture from the room. Try not to use heat-producing

appliances during the hottest part of the day.

The air intakes are blocked. Install the air conditioner in a

location where the louvers are free from curtains, blinds,

furniture, etc.

The temperature of the room you are trying to cool is

extremely hot. Allow extra time for the air conditioner

to cool off a very hot room.

Windows or doors to the outside are open. Close all windows

and doors.

The temperature setting is not set to a cool enough setting.

Adjust the temperature to a cooler setting by pressing the

minus button to reduce the temperature. Set the Fan Speed

control to the highest setting.

Error codes in display

If E1 or or E2 appears in the display, call for service.

95116_AMAP081AW_Amana_portable.indd   10

12/1/2016   1:48:42 PM

Summary of Contents for AMAP084AW

Page 1: ...TIONERS 12 Models Mod les Modelos AMAP084AW 2018 Amana All rights reserved Manufactured under license by XLS Products Pennsylvania 2018 Amana Tous droits r serv s Fabriqu sous licence par XLS Products...

Page 2: ...ll air conditioner Plug into a grounded 3 prong outlet Do not remove ground prong Do not use an adapter Do not use an extension cord INSTALLATION REQUIREMENTS Location Requirements IMPORTANT Observe a...

Page 3: ...ble vent hose 1 C Vent hose round connector 1 D Vent hose window connector 1 A B C D PARTS AND FEATURES Front View Casters Control Panel Handle Air Outlet Back View Internal tank drain Air outlet heat...

Page 4: ...e cord is crushed the electronics detect leakage current and power will be disconnected in a fraction of a second To test your power supply cord 1 Plug power supply cord into a grounded 3 prong outlet...

Page 5: ...re the vent opening in the slider panel is not covered Tighten the wing nut securely If the window is too narrow to fit the slider panel without blocking the vent opening 1 Loosen the wing nut and rem...

Page 6: ...nough to reach from the air conditoner to the window Be sure there are no sharp bends or kinks in the hose Press the window connector end of the vent hose into the opening on the slider panel as shown...

Page 7: ...to the outdoors when using Cooling mode Dehumidify DEHUM Mode Air is dehumidified as it passes through the unit without being in full cooling mode For temperatueres above 77 F 25 C the fan speed is ad...

Page 8: ...dicator will be lit and the air conditioner will turn off until the internal tank is emptied See Care and Cleaning Using the Remote Control The functions on the remote control operate the same way as...

Page 9: ...acing to ensure maximum efficiency Draining the Internal Tank If the air conditioner turns off and the Bucket Full indicator is lit it is necessary to drain the internal tank before using the air cond...

Page 10: ...t use an extension cord Failure to follow these instructions can result in death fire or electrical shock WARNING Air conditioner seems to run too much The current air conditioner replaced an older mo...

Page 11: ...rther assistance If you need further assistance you can write to XLS Products with any questions or concerns at XLS Products Inc Customer Service P O Box 16262 Philadelphia PA 19114 0262 Please includ...

Page 12: ...IN IMPLIED WARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED TO ONE YEAR OR THE SHORTEST PERIOD ALLOWED BY LAW XLS PRODUCTS SHALL NOT BE LIABLE FOR INC...

Page 13: ...ecte L emplacement d installation doit disposer de Une prise lectrique avec liaison la terre situ e moins de 6 pi 183 cm du point de sortie du cordon d alimentation du climatiseur REMARQUE Ne pas util...

Page 14: ...ecteur rond pour conduit 1 D Connecteur de conduit pour fen tre 1 A B C D PI CES ET CARACT RISTIQUES Vue de face Roulettes Tableau de commande Poign e Sortie d air Vue arri re R servoir interne Sortie...

Page 15: ...en une fraction de seconde Pour tester le cordon d alimentation 1 Brancher le cordon d alimentation lectrique dans une prise trois alv oles reli e la terre 2 Appuyer sur RESET r initialisation un t m...

Page 16: ...471 4 po 1 2 m Hauteur d ouverture minimum de 43 4 po 12 cm Mesures de l ouverture dans la fen tre guillotine normale Largeur d ouverture minimum de 43 4 po 12 cm Hauteur d ouverture minimum de 245 8...

Page 17: ...flexible pour relier le climatiseur et la fen tre S assurer qu il n y a aucun coude serr ou pli dans le tuyau Placer le c t fen tre du conduit flexible dans l ouverture du panneau coulissant comme in...

Page 18: ...ature peut tre r gl e entre 61 F 90 F 16 C 32 C IMPORTANT Le conduit flexible doit expulser l air chaud l ext rieur pendant l utilisation du mode refroidissement Mode d shumidificateur L appareil d sh...

Page 19: ...mplir Si cela se produit l indicateur de r servoir plein s allume et le climatiseur s arr te jusqu ce qu il soit vid Voir la section Entretien et nettoyage Bruits de fonctionnement normaux Lorsque le...

Page 20: ...ssaire de drainer ce dernier avant d utiliser de nouveau le climatiseur 1 Drainer le r servoir interne 1 Arr ter et d brancher le climatiseur 2 Placer une cuvette ou une petite chaudi re sous le drain...

Page 21: ...iseur semble se mettre en marche trop fr quemment Ce climatiseur remplace un vieux mod le Du fait de l utilisation de composants plus efficaces il est possible que le climatiseur fonctionne pendant de...

Page 22: ...ez besoin de plus d assistance vous pouvez crire XLS Products en soumettant toute question ou tout probl me XLS Products Inc Customer Service P O Box 16262 Philadelphia PA 19114 0262 N oubliez pas d i...

Page 23: ...CI DESSUS LES GARANTIES IMPLICITES Y COMPRIS LES GARANTIES APPLICABLES DE QUALIT MARCHANDE OU D APTITUDE UN USAGE PARTICULIER SONT LIMIT ES UN AN OU LA PLUS COURTE P RIODE AUTORIS E PAR LA LOI XLS PR...

Page 24: ...acondicionador de aire Conecte a un contacto de pared de conexi n a tierra de 3 terminales No quite el terminal de conexi n a tierra No use un adaptador No use un cable el ctrico de extensi n C mo de...

Page 25: ...rdenanzas vigentes Verifique el lugar donde se instalar el acondicionador de aire Aseg rese de tener todo lo necesario para una instalaci n correcta El lugar debe tener Un tomacorriente el ctrico con...

Page 26: ...de segundo ADVERTENCIA Peligro de Choque El ctrico Conecte a un contacto de pared de conexi n a tierra de 3 terminales No quite la terminal de conexi n a tierra No use un adaptador No use un cable el...

Page 27: ...a abertura de la ventilaci n en el panel deslizante Apriete la tuercas mariposa de manera ajustada Si la ventana es demasiado angosta para encajar en el panel deslizante sin bloquear la abertura de la...

Page 28: ...ar la muerte incendio o choque el ctrico Conexi n El ctrica Extienda un poco ambos extremos de la manguera de ventilaci n Inserte un conector redondo en sentido horario en un extremo de la manguera de...

Page 29: ...y C ENCENDIDO o APAGADO del acondicionador de aire Presione POWER Encendido para ENCENDER o APAGAR el acondicionador de aire IMPORTANTE Si apaga el acondicionador de aire espere al menos 3 minutos an...

Page 30: ...humedad alta es posible que el tanque interno se llene Si esto sucede se iluminar la luz indicadora Bucket Full Balde lleno y el acondicionador de aire se apagar hasta que se vac e el tanque interno...

Page 31: ...unas horas para que se seque toda la humedad de los serpentines 2 Apague el acondicionador de aire y desench felo Retire las bater as del control remoto 3 Retire el tap n de desag e del tanque interno...

Page 32: ...A un cable de suministro el ctrico se debe reemplazar con un nuevo cable de suministro el ctrico obtenido del fabricante del producto y no se debe reparar Parece que el acondicionador de aire funciona...

Page 33: ...nidos Para obtener m s asistencia Si necesita asistencia adicional puede escribir a XLS Products con sus preguntas o dudas a XLS Products Inc Customer Service P O Box 16262 Philadelphia PA 19114 0262...

Page 34: ...G N SE ESTIPULA EN LA PRESENTE LAS GARANT AS IMPL CITAS INCLUSO LAS GARANT AS DE COMERCIABILIDAD O DE IDONEIDAD PARA UN PROP SITO PARTICULAR SE LIMITAR N A UN A O O AL PER ODO M S CORTO PERMITIDO POR...

Page 35: ...35 95116_AMAP081AW_Amana_portable indd 35 12 1 2016 1 48 51 PM...

Page 36: ...95116_AMAP081AW_Amana_portable indd 36 12 1 2016 1 48 51 PM...

Reviews: