SS-AMVM96
www.amana-hac.com
9
8 www.amana-hac.com
SS-AMVM96
P
roduCt
s
PeCiFiCAtions
P
roduCt
s
PeCiFiCAtions
ACVM96 A
irFlow
d
AtA
— H
eAting
s
Peeds
ACVM960604CX
Rise Range: 20 - 50°F)
ACVM960805DX
Rise Range: 20 - 50°F)
Adjust
Tap
CFM *
Rise (°F)
Adjust
Tap
CFM *
Rise (°F)
Minus(-)
1,098
48
Minus(-)
1,440
49
Normal
1,220
44
Normal
1,600
44
Plus (+)
1,342
40
Plus (+)
1,760
40
Minus(-)
1,206
44
Minus(-)
1,539
46
Normal
1,340
40
Normal
1,710
41
Plus (+)
1,474
36
Plus (+)
1,881
38
Minus(-)
1,314
40
Minus(-)
1,620
44
Normal
1,460
36
Normal
1,800
39
Plus (+)
1,606
33
Plus (+)
1,980
36
Minus(-)
1,431
37
Minus(-)
1,719
41
Normal
1,590
33
Normal
1,910
37
Plus (+)
1,749
30
Plus (+)
2,101
34
* @ .1" - .5" w.c. ESP
* @ .1" - .5" w.c. ESP
Notes
• All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• Operation is recommended below .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for
cooling purposes only.
• 100% CFM shown. CFM will vary proportionally with the gas valve BTU/H input.