background image

16

16023324  Rev. 0

©2004 Maytag Services

To minimize contamination, exercise extreme care
when servicing HFC134A sealed systems.

No trace of other refrigerants is allowed in HFC134a
systems. Chlorinated molecules in other refrigerants
such as CFC12, etc. will lead to capillary tube
plugging.

Ester oil is used in HFC134a systems. Do not use
mineral oil. HFC134a and mineral oils cannot be
mixed. If mineral oils were used in HFC134a systems,
lubricant would not return to compressor and would
cause early compressor failure. If significant amount of
oil has been lost from compressor, replace oil rather
than adding oil.

• Ester oils used in HFC134a systems are so

hydroscopic that by the time an inadequate system
performance is detected, oil will be saturated with
moisture.

• CFC12 has much higher tolerance to system

processing materials, such as drawing compounds,
rust inhibitors, and cleaning compounds, than
HFC134a. Such materials are not soluble in HFC134a
systems. If materials were to be washed from system
surfaces by ester oils, they could accumulate and
eventually plug capillary tube.

• Care must be taken to minimize moisture entering

HFC134a system. Do not leave compressor or system
open to atmosphere for more than 10 minutes.
Excessive moisture in HFC134a system will react with
compressor oil and generate acid.

• Compressor must be replaced when performing low

side leak repair.

Drier filter must always be replaced with service drier
filter, part #B2150504.

Important: 

Unbrazing drier filter from tubing will drive

moisture from desiccant and into system, causing
acids to form. Do not unbraze filter drier from tubing. If
CFC12 service drier was installed in HFC134A system,
drier could overload due to excessive moisture.

• HFC134a compatible copper tubing, part #R0174075

.635 millimeter x 457.2 millimeter length and part
#R0174076 7.93 millimeter x 609.6 millimeter must be
used when replacing tubing.

• Avoid system contamination by using Towerdraw E610

evaporating oil, part # R0157532, when flaring,
swagging, or cutting refrigeration tubing.

Service Procedures

HFC134a Service Information

HFC134a is alternative refrigerant for CFC12.
HFC134a has an ozone depletion potential (ODP)
factor of 0.0 and a global warming potential (GWP)
factor of 0.27. HFC134a is not flammable and has
acceptable toxicity levels. HFC134a is not
interchangeable with CFC12. There are significant
differences between HFC134a and CFC12 which must
be considered when handling and processing
refrigeration system.

Health, Safety, and Handling

Health, safety and handling considerations for
HFC134A are virtually no different than those for
CFC12.

Comparison of CFC12 and HFC134a Properties

Health, Safety, and
Handling

CFC12

HFC134a

Allowable overall
exposure limit

1,000 ppm

Same

Vapor exposure to skin

No effect

Same

Liquid exposure to skin

Can cause frostbite

Same

Vapor exposure to eye

Very slight eye irritant

Same

Liquid exposure to eye

Can cause frostbite

Same

Above minimum exposure
limit

Can cause Asphyxiation,
Tachycardia, and Cardia
Arrhythmias

Same

Safety and handling

Wear appropriate skin
and eye protection. Use
with adequate
ventilation.

Same

Spill management

Remove or extinguish
ignition or combustion
sources. Evacuate or
ventilate area.

Same

Fire explosion hazards

May decompose if
contact with flames and
heating elements.
Container may explode
if heated due to resulting
pressure rise.
Combustion products
are toxic.

Same

Disposal procedures

Recycle or reclaim.

Same

To avoid risk of electrical shock, personal injury, or death, disconnect electrical power source to unit, unless test
procedures require power to be connected. Discharge capacitor through a resistor before attempting to service.
Ensure all earthing wires are connected before certifying unit as repaired and/or operational.

!

WARNING

CAUTION

!

Properties/Characteristics

CFC12

HFC134a

Ozone Depletion Potential
(ODP)

1.0*

0.0*

Global Warming Potential
(GPW)

3.2*

0.27*

Molecular weight

121

102

Boiling point at 1 atmosphere

-22°F (-30°C)

-15°F (-

126°C)

Vapor pressure at 77°F
(25°C)

80 psig

82 psig

Liquid density at 77°F (25°C)

82 lb/ft

3

75 lb/ft

3

Flammability

No

No

High-side system operating
Pressure at 65°F (18°C)

HFC134a approximately 3 psig
higher than CFC12

Low-side system operating
Pressure at 65°F (18°C)

HFC134a approximately 2 psig
lower than CFC12

Summary of Contents for AB1924PEK Series

Page 1: ...but is not limited to the following Amana AB1924PEK AB2026PEK AB2225PEK AB2226PEK AB2526PEK G32026PEK G32526PEK GB1924PEK GB2225PEK GB2526PEK Service This manual is to be used by qualified appliance t...

Page 2: ...REPAIRS WARNING To avoid risk of severe personal injury or death disconnect power before working servicing on appliance to avoid electrical shock To locate an authorized servicer please consult your t...

Page 3: ...Freezer Drawer 29 Refrigerator Compartment Light Bulb 29 Light Bulb Assembly 29 Light Bulb Sockets 30 PC Control Board 30 Light Switch 30 Temp Assure Damper control 30 Fresh Food Thermistor 30 Water...

Page 4: ...rom 25 C to 32 C Saturated gas is drawn off through suction line where superheated gas enters compressor To raise temperature of gas suction line is placed in heat exchange with capillary Temperature...

Page 5: ...est 1 Disconnect power to refrigerator 2 Discharge capacitor if present by shorting terminals through a resistor 3 Remove compressor leads and use an ohmmeter set on highest scale 4 Touch one lead to...

Page 6: ...enser It is very important that adequate air flow over condenser is maintained Condenser is air cooled by condenser fan motor If efficiency of heat transfer from condenser to surrounding air is impair...

Page 7: ...terminal 2 1 Disconnect power to the refrigerator 2 Remove relay cover and disconnect leads 3 Check resistance across terminals 2 and 3 with an ohmmeter Normal 3 to 12 ohms Shorted 0 ohms Open infini...

Page 8: ...NO terminals Closed Drier Drier is placed at post condenser loop outlet and passes liquefied refrigerant to capillary Desiccant 20 8 x 12 4AXH 7 M S Grams Drier must be changed every time the system...

Page 9: ...ttmeter 2 Turn into defrost mode Wattmeter should read specified watts according to Technical Data Sheet 3 When defrost thermostat reaches specified temperature 15 C see Technical Data Sheet thermosta...

Page 10: ...HFC134a and ester oil system Equipment must be exclusively used for HFC134a Exclusive use of equipment only applies to italic items Evacuation pump Check with vacuum pump supplier to verify equipment...

Page 11: ...mpressor Run lead on test cord attaches to M terminal on compressor Service Procedures C R S Fuses Capacitor Compressor Switch To AC supply Attaching Capacitor for Compressor Test 5 Connect a known go...

Page 12: ...Refrigerant leaks are best detected with halide or electronic leak detectors Testing Systems Containing a Refrigerant Charge 1 Stop unit operation turn refrigerator off 2 Holding leak detector explor...

Page 13: ...n normal head pressure and wattage while low side is being pumped out Testing for Restrictions To determine if a restriction exists 1 Attach gauge and manifold between suction and discharge sides of s...

Page 14: ...and F closed open all other valves and start vacuum pump Vacuum Pump 6 cm Copper Tubing Compressor Compressor Process Tube Charging Hose Thermistor Vacuum Gauge Low Side Gauge E Valve B D Valve High...

Page 15: ...ess tube 5 Start compressor and draw remaining refrigerant from charging hoses and manifold into compressor through compressor process tube 6 To check high side pinch off drier process tube Close valv...

Page 16: ...e Procedures HFC134a Service Information HFC134a is alternative refrigerant for CFC12 HFC134a has an ozone depletion potential ODP factor of 0 0 and a global warming potential GWP factor of 0 27 HFC13...

Page 17: ...rate minimum of 20 minutes after thermocouples are installed Turn control to colder to obtain required on time Wattage reading must be recorded in conjunction with temperature test to confirm proper o...

Page 18: ...efrigerant Flow Bottom Mount Refrigerant Flow Diagram EVAPORATOR COMPRESSOR DISCHARGE TUBE CONDENSER CAPILLARY TUBE SUCTION TUBE DRYER PRO CESS TUBE POST CONDENSER TUBE Note Capillary Tube and Suction...

Page 19: ...Flow Diagram CRISPER AIR SUPPLY PORT EVAPORATOR FAN ASSEMBLY EVAPORATOR EVAPORATOR COVER FREEZER RETURN AIR THOUGH LOUVERS AT BOTTOM OF EVAPORATOR COVER FREEZER AIR SUPPLY GRILLE REFRIGERATOR RETURN A...

Page 20: ...20 16023324 Rev 0 2004 Maytag Services Two Way Bottom Mount Machine Compartment Air Flow Diagram Machine Compartment Air Flow Condenser Condenser Fan Assembly Compressor...

Page 21: ...2004 Maytag Services 16023324 Rev 0 21 One Way Bottom Mount Machine Compartment Air Flow Diagram Machine Compartment Air Flow...

Page 22: ...ezer door top Freezer door bottom CLASSIFICATION OF CONDENSATION 1 Haze or fog 2 Beading 3 Beads or small drops 4 Drops running together No sweat on side when compressor is running Conditions after 4...

Page 23: ...tion Overloading of shelves Consumer education Warm or hot foods placed in cabinet Consumer education Cold control set too warm Set control to colder setting Poor door seal Level cabinet Adjust hinges...

Page 24: ...ystem Refrigerant overcharge Check for overcharge Evacuate and recharge system Unit runs continuously Air in system Check for low side leak Repair evacuate and recharge system Unit runs continuously T...

Page 25: ...r for continuity If open replace overload NOTE Ensure overload compressor are below trip temperature before testing Faulty compressor motor capacitor some compressors do not require motor capacitor Ch...

Page 26: ...st system the refrigerant will flood out and cause the suction line to frost or sweat The cause of this problem should be corrected rather than to purge refrigerant from the sytem Running the freezer...

Page 27: ...ge the system replace the drier filter evacuate and recharge with the specified refrigerant charge If the unit performs normally three possibilities exist 1 refrigerant loss 2 partially restricted dri...

Page 28: ...he ambient temperature raises Refrigerators installed in ambient temperatures lower than 60 F will not perform as well because the pressures within the system are generally reduced and unbalanced This...

Page 29: ...ims b Remove toe grille by pulling it directly away from unit and pop plastic cover off bottom door hinge Grille and cover are fragile keep both parts safe from harm c Remove bottom hinge pin and all...

Page 30: ...Mid Level Electronic Model Light Switch 1 After following procedure on removing light bulb assembly 2 Disconnect wires from light switch 3 Squeeze tab to release light switch from light assembly 4 Re...

Page 31: ...eased 5 Remove light bulb 6 Squeeze tab holding light housing in place to release housing and remove 7 Disconnect wires to socket 8 Squeeze tab on back side of housing to release socket Light Switch 1...

Page 32: ...t of plastic clips that hold it to back wall of unit Then roll bottom of evaporator forward and up exposing evaporator heater in its location amid fins at bottom of evaporator 6 Taking care to notice...

Page 33: ...aight away from unit 2 Raise front of refrigerator at least 101 6mm off the deck and block it up 3 Unscrew leveling bolt until wheel is free of leveling bolt 4 Tip wheel assembly down until wheel asse...

Page 34: ...ad screws on bottom of cabinet 5 Carefully lower basepan taking care not to kink tubing to compresser or condenser 6 Remove hex screws holding condenser fan shroud to basepan 7 Lift shroud up and out...

Page 35: ...ram Code the control will not save the new code but will flash the old code and this will be displayed The unit will NOT run with a Program Code of 00 8 Once the Program Code has been saved the Progra...

Page 36: ...the display will return to a normal operating display with set point values 4 Freezer Refrigerator 4 8 Close the Refrigerator door s You are in the defrost mode Note Forced Defrost mode can be exited...

Page 37: ...roper defrost function You can observe defrost heat and voltages while the test is activated 1 Freezer Refrigerator O DEFROST THERMOSTAT OPEN 1 Freezer Refrigerator S DEFROST THERMOSTAT SHORTED CLOSED...

Page 38: ...hort result for a test on the Fresh Food Thermistor circuit as show below The test is activated and de activated via the Refrigerator Up key and must be de activated to move to another test selection...

Page 39: ...Service Test 7 FF Performance Adjustment This test will allow adjustment of the control performance points Each step will incrementally change the Refrigerator performance warmer towards 1 or colder...

Reviews: