BLOWER PERFORMANCE SPECIFICATIONS
11
Rev. 1
1. CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer. If the
furnace requires two return filters, this chart assumes both filters are installed.
2. All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed.
3. For most jobs, about 400 CFM per ton when cooling is desirable.
4. INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON
THE RATING PLATE.
5. The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown
on rating plate. The shaded area indicates ranges in excess of maximum external static pressure allowed when
heating.
6
The dashed (---) areas indicate a temperature rise not recommended for this model.
7. The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have
approximately the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.
Note: The models listed in the above airflow table use 10x8 blower assembly instead of 10x6 to achieve a full 4 tons of airflow. Listed below are the model
numbers along with the manufacturing numbers of the two units using the 10x8 blower assembly.
GUID070DA40
P1226909F
GUID070DX40
P1227009F
TONS AC
External Static Pressure, Inches Water Column
@ 0.5"
0.1
0.2
0.3
0.4
0.5
0.6
ESP
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
HIGH
4.0
1799
---
1742
---
1694
---
1622
---
1529
---
1444
GUID070**40
MED
3.5
1720
---
1590
---
1542
---
1483
---
1404
36
1330
(Med-Lo)
MED-LO
2.5
1113
46
1096
47
1078
47
1067
48
1018
50
967
LOW
2
967
53
954
54
941
54
913
56
885
58
826
Model
Heating Speed
As Shipped
MOTOR
SPEED
(CFM & Temperature Rise vs. External Static Pressure)
GUID070**40 Blower Performance
)
(