may scaled differently to the 7 segment display. For example the bargraph scale may be indicating
percentage fill of a tank whilst the 7 segment display is indicating actual process units. To set
bargraph low level go to the
bAr_
function and use the
^
or
v
push buttons to set the value
required then press
F
to accept this value.
5.10
Bargraph high value
Display:
bAr~
Range:
Any display value
Default Value:
1000
Seen only in bargraph display instruments. Displays and sets the bar graph high value i.e. the value
on the 7 segment display at which the bargraph will reach its maximum indication (e.g. all LEDs
illuminated). May be independently set anywhere within the display range of the instrument. To
set bargraph high level go to the
bAr~
function and use the
^
or
v
push buttons to set the
value required then press
F
to accept this value.
5.11
Analog output option low value
Display:
REC_
Range:
Any display value
Default Value:
0
Seen only when analog retransmission option fitted. Refer to the separate “PM4 Panel Meter
Optional Output Addendum” booklet supplied when this option is fitted for wiring details and link
settings. Displays and sets the analog retransmission (4–20mA, 0–1V or 0–10V, link selectable)
output low value (4mA or 0V) in displayed engineering units. To set the analog output low value
go to the
REC_
function and use the
^
or
v
push buttons to set the required value then press
F
to accept this selection.
Example:
If it is required to retransmit 4mA when the display indicates
0
then select
0
in this
function using the
^
or
v
button.
5.12
Analog output option high value
Display:
REC~
Range:
Any display value
Default Value:
1000
Seen only when analog retransmission option fitted. Refer to the separate “PM4 Panel Meter
Optional Output Addendum” booklet supplied when this option is fitted for wiring details and link
settings. Displays and sets the analog retransmission (4–20mA, 0–1V or 0–10V, link selectable)
output high display value (20mA, 1V or 10V) in displayed engineering units. To set the analog
output high value go to the
REC~
function and use the
^
or
v
push buttons to set the required
value then press
F
to accept this selection.
Example:
If it is required to retransmit 20mA when the display indicates
50
then select
50
in
this function using the
^
or
v
button.
PM4BCMAN-2.0-0
25 of
Summary of Contents for PM4-BC
Page 7: ...3 5 Parallel BCD input PM4BCMAN 2 0 0 7 of 40...
Page 8: ...3 6 Strobed BCD input 8 of 40 PM4BCMAN 2 0 0...
Page 9: ...3 7 Addressed BCD input PM4BCMAN 2 0 0 9 of 40...
Page 10: ...3 8 Parallel binary input also used for Gray code 10 of 40 PM4BCMAN 2 0 0...
Page 11: ...3 9 Strobed binary input also used for Gray code PM4BCMAN 2 0 0 11 of 40...
Page 12: ...3 10 Addressed binary input also used for Gray code 12 of 40 PM4BCMAN 2 0 0...