ALUTERM B 350 - 600
|
Installation, User and Service Manual
|
instructions for user
Heating
Alutherm B 350 - 600
Note : Maximum allowed draught is 120 Pa, this means that in case of vertical flue the maximum length is limited to 30 mtrs
Boiler type
1
2
3
4
5
6
7
8
Component
350
425
510
600
Pressure drop [Pa]
Flue gas
[Pa]
Air
[Pa]
Flue gas
[Pa]
Air
[Pa]
Flue gas
[Pa]
Air
[Pa]
Flue gas
[Pa]
Air
[Pa]
Pipe length 1 m
Ø 250mm
0,6
0,9
1,3
1,8
Pipe length 1 m
Ø 150mm
4,2
6,5
9,4
12,7
Bend 90°
Ø 250mm
5,3
8,3
12,0
16,3
Bend 90°
Ø 150mm
16,2
25,3
36,5
49,7
Bend 45°
Ø 250mm
3,4
5,2
7,5
10,3
Bend 45°
Ø 150mm
6,9
10,7
15,4
21,0
Terminal C33
Ø250mm,Ø250mm
20,8
32,5
46,8
63,7
Terminal B23
Ø250mm
6,2
9,8
14,0
19,1