Vertiline33D/VertiLine33TD/Vertiline63D/VertiLine63TD
- 3 -
10. The power LEDs on the faceplate for Outputs 1-8 will illuminate when AC power is present (Fig. 1a, pg. 4).
Note: If any of the power LEDs are not illuminated, the cause may be due to the following:
a. AC mains fail.
b. Illuminated master power disconnect circuit breaker is OFF or tripped.
c. One (1) or more power output PTCs are tripped due to a short circuit or overload condition.
To reset the PTC:
1. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1c, pg. 4).
2. Eliminate the trouble condition (short circuit or overload).
3. Allow 1 minute for PTC to cool off (reset).
4. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 1c, pg. 4).
5. All power LEDs will illuminate indicating power has been restored to all outputs (Fig. 1a, pg. 4).