Vertiline33D/VertiLine33TD/Vertiline63D/VertiLine63TD

 

- 3 -

10.  The power LEDs on the faceplate for Outputs 1-8 will illuminate when AC power is present (Fig. 1a, pg. 4).   
 

Note: If any of the power LEDs are not illuminated, the cause may be due to the following:

 

a.  AC mains fail.

 

b.  Illuminated master power disconnect circuit breaker is OFF or tripped.

 

c.  One (1) or more power output PTCs are tripped due to a short circuit or overload condition.

 

 

To reset the PTC:

 

 

1.  Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1c, pg. 4).

 

 

2.  Eliminate the trouble condition (short circuit or overload).

 

 

3.  Allow 1 minute for PTC to cool off (reset).

 

 

4.  Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 1c, pg. 4).

 

 

5.  All power LEDs will illuminate indicating power has been restored to all outputs (Fig. 1a, pg. 4).

Summary of Contents for VertiLine33D

Page 1: ...e VertiLine33D 12VDC 8A Sixteen 16 PTC protected outputs VertiLine33TD 12VDC 16A Sixteen 16 PTC protected outputs VertiLine63D 24VDC 8A Sixteen 16 PTC protected outputs VertiLine63TD 24VDC 16A Sixteen 16 PTC protected outputs Rev 090810 More than just power TM ...

Page 2: ...When installing the unit in a rack allow for one half U spacing above the unit for ventilation 3 Insert and secure removable terminal blocks to unit Fig 1e pg 4 4 Plug the grounded AC line cord included into the IEC 320 connector of the Vertiline unit Fig 1d pg 4 Insert the plug end of the line cord into a grounded AC receptacle 5 Set illuminated master power disconnect circuit breaker to the ON p...

Page 3: ... breaker is OFF or tripped c One 1 or more power output PTCs are tripped due to a short circuit or overload condition To reset the PTC 1 Set illuminated master power disconnect circuit breaker to the OFF position Fig 1c pg 4 2 Eliminate the trouble condition short circuit or overload 3 Allow 1 minute for PTC to cool off reset 4 Set illuminated master power disconnect circuit breaker to the ON posi...

Page 4: ...Vertiline63TD rear 1a 1b 1c 1d 1a LED s 1 8 Power LED indicators 1b Power Outputs 12VDC or 24VDC 1c Illuminated master power disconnect circuit breaker switch OFF position Circuit breaker tripped Switch not illuminated RESET ON position Switch illuminated 1d IEC 320 Connector 115VAC 60Hz grounded line cord included 1e Removable Terminal Block 1e Removable Terminal Block ...

Page 5: ...D VertiLine63TD 5 Fig 2 Typical Application Drawing 12VDC Vertiline33D Vertiline33TD or 24VDC Vertiline63D Vertiline63TD Power Outputs to Devices 12VDC Vertiline33D Vertiline33TD or 24VDC Vertiline63D Vertiline63TD Power Outputs to Devices ...

Page 6: ...d Outputs not powered To reset circuit breaker set power switch to the ON RESET position The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product s enclosure that may be of sufficient magnitude to constitute an electric shock The exclamation point within an equilateral triangle is in...

Page 7: ...d screws from both sides of rack chassis Fig 3a 2 Attach mounting brackets A on the left and right side of rack chassis using the two 2 flat head screws B included Fig 3b 3 Install unit into desired EIA 19 rack position and secure with mounting screws not included Fig 3c Fig 5 Fig 4 Shelf Installation 1 Position and affix rubber pads C included at each corner on the bottom of the unit Fig 5 2 Plac...

Page 8: ...TD Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIVertiline33DSeries F14P Notes MEMBER ...

Reviews: