VertiLine33DV / 63DV Series Installation Guide 

- 3 -

Installation Instructions:

1.  Attach mounting brackets to VertiLine unit for rack or wall mount installation 

(Figs. 4-5, pg. 7)

.

 

Affix rubber pads to VertiLine for shelf installation 

(Fig. 6, pg. 7)

.

2.  Secure the unit into rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at 

 

least 3” from any video monitors). When installing the unit in a rack allow for one half U spacing above 

 

the unit for ventilation.

3.  Insert and secure removable terminal blocks to unit 

(Fig. 1e, pg. 4)

.

4.  Plug the grounded AC line cord (included) into the IEC 320 connector of the VertiLine unit 

(Fig. 1d, pg. 4)

 

Insert the plug end of the line cord into a grounded AC receptacle.

5.  Set illuminated master power disconnect circuit breaker to the (ON) position 

(Fig. 1c, pg. 4)

.

6.  Measure output voltage before connecting cameras/devices. This helps avoiding potential damage.

7.  Set illuminated master power disconnect circuit breaker to the (OFF) position 

(Fig. 1c, pg. 4)

8.  Connect the power output of terminals marked [+ 1 –] to the power input of device 

(Fig. 1b, pg. 4)

.

 

Repeat this step for each additional device (Outputs 2-16).

9.  Upon completion of wiring, set illuminated master power disconnect circuit breaker to the 

 

ON (RESET) position 

(Fig. 1c, pg. 4)

.

10.  The power LEDs on the faceplate for Outputs 1-8 will illuminate when AC power is present 

 

(Fig. 1a, pg. 4).

 

Note:

 If any of the power LEDs are not illuminated, the cause may be due to the following:

 

a.  AC mains fail.

 

b.  Illuminated master power disconnect circuit breaker is OFF or tripped.

 

c.  One (1) or more power output PTCs are tripped due to a short circuit or overload condition.

 

 

To reset the PTC:

 

 

1. Set illuminated master power disconnect circuit breaker to the (OFF) position 

(Fig. 1c, pg. 4)

.

 

 

2. Eliminate the trouble condition (short circuit or overload).

 

 

3. Allow 1 minute for PTC to cool off (reset).

 

 

4. Set illuminated master power disconnect circuit breaker to the (ON) position 

(Fig. 1c, pg. 4)

.

 

 

5. All power LEDs will illuminate indicating power has been restored to all outputs 

(Fig. 1a, pg. 4)

.

Summary of Contents for VertiLine 33DV Series

Page 1: ...ed outputs VertiLine63TDV 24VDC 16A Sixteen 16 PTC protected outputs VertiLine 33DV 63DV Series Rack Mount Power Supplies Models Include Rev 090810 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ Installation Guide ...

Page 2: ...ircuit breaker with manual reset IEC 320 3 wire grounded line cord detachable Removable terminal blocks with locking screw flange Mechanical Units can be rack wall or shelf mounted Modular 1U standard EIA 19 rack mount chassis Enclosure Dimensions H x W x D approx 1 625 x 19 125 x 8 5 41 3mm x 486mm x 216mm Sixteen 16 Output Rack Mount Configuration Reference Chart Altronix Model Number Output Vol...

Page 3: ...ed master power disconnect circuit breaker to the OFF position Fig 1c pg 4 8 Connect the power output of terminals marked 1 to the power input of device Fig 1b pg 4 Repeat this step for each additional device Outputs 2 16 9 Upon completion of wiring set illuminated master power disconnect circuit breaker to the ON RESET position Fig 1c pg 4 10 The power LEDs on the faceplate for Outputs 1 8 will i...

Page 4: ...wer disconnect circuit breaker switch OFF position Circuit breaker tripped Switch not illuminated RESET ON position Switch illuminated 1d IEC 320 Connector 220VAC 50 60Hz grounded line cord included 1e Removable Terminal Block Fig 1 VertiLine33DV VertiLine33TDV VertiLine63DV and VertiLine63TDV front 1a 1b 1c 1d 1e Removable Terminal Block ...

Page 5: ...n Guide 5 Fig 2 Typical Application Drawing 12VDC VertiLine33DV VertiLine33TDV or 24VDC VertiLine63DV VertiLine63TDV Power Outputs to Devices 12VDC VertiLine33DV VertiLine33TDV or 24VDC VertiLine63DV VertiLine63TDV Power Outputs to Devices ...

Page 6: ...s not powered To reset circuit breaker set power switch to the ON RESET position Fig 3 pg 6 The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product s enclosure that may be of sufficient magnitude to constitute an electric shock The exclamation point within an equilateral triangle is ...

Page 7: ... Left Remove Wall Mount Installation 1 Install mounting brackets A on the left and right side of rack chassis using two 2 flat head screws B included Fig 5a 2 Place unit at desired location and secure with mounting screws not included Fig 5b Caution It is necessary to make sure mounting screws are securely fastened to a beam when installing Fig 5 Fig 5a Fig 5b B A Fig 6 Shelf Installation 1 Positi...

Page 8: ...Notes Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty IIVertiLine33DV 63DV Series K04U MEMBER ...

Reviews: