Trove2/Mercury Fused Kits Installation Guide
Overview:
Altronix Trove Mercury kits are pre-assembled and consist of Trove2M2 enclosure/backplane with factory installed Altronix power supply/charger(s) and sub-
assemblies. These kits also accommodate various combinations of Mercury boards for up to sixteen (16) doors in a single enclosure.
Configuration Chart:
Altronix
Model Number
Networkable
120VAC 60Hz Input Current (A)
Power Supply Board Input Fuse Rating
Power Supply Board Battery Fuse Rating
Nominal DC Output Voltage
Maximum Supply
Current for Main and
Aux. Outputs on Power
Supply board and
ACM4/ACM8 Access
Power Controller’s
outputs
Fail-Safe/Fail-Secure or Dry Form “C” Outputs
Current Per ACM4/ACM8 Output
(A)
ACM4/ACM8 Board Input Fuse Rating
ACM4/ACM8 Board Output Fuse Rating
PDS8 Board Input Fuse Rating
PDS8 Board Output Fuse Rating
PD8UL/PD16W Board Output Fuse Rating
Power Supply
1
Power Supply
2
[DC] [Aux] [DC] [Aux]
Output Range (VDC)
Output Range (VDC)
Output Range (VDC)
Output Range (VDC)
T2MK3F4
–
3.5
5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4
–
–
24VDC @ 5.8A
4
2.5
10A/
250V
3A/
250V
10A/
250V
3A/
250V
–
T2MK3F4Q
P
3.5
5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4
–
–
24VDC @ 5.8A
4
2.5
10A/
250V
3A/
250V
10A/
250V
3A/
250V
–
T2MK3F8
–
3.5
5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4
–
–
24VDC @ 5.8A
8
2.5
10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
–
T2MK3F8Q
P
3.5
5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4
–
–
24VDC @ 5.8A
8
2.5
10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
–
T2MK7F8
–
4.5 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
–
–
24VDC @ 9.2A
8
2.5
10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
–
T2MK7F8Q
P
4.5 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
–
–
24VDC @ 9.2A
8
2.5
10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
–
T2MK75F16
–
8
6.3A/
250V 15A/
32V
20.17-
26.4
20.28-
26.4
9.7-
13.2
10.03-
13.2
12VDC @ 9.3A
24VDC @ 9.2A
16
2.5
10A/
250V
2.5A/
250V
–
–
3.5A/
250V
5A/
250V
T2MK75F16Q
P
8
6.3A/
250V 15A/
32V
20.17-
26.4
20.28-
26.4
9.7-
13.2
10.03-
13.2
12VDC @ 9.3A
24VDC @ 9.2A
16
2.5
10A/
250V
2.5A/
250V
–
–
3.5A/
250V
5A/
250V
T2MK77F16
–
9
6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4
24VDC @ 9.2A
16
2.5
10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
–
T2MK77F16Q
P
9
6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4
24VDC @ 9.2A
16
2.5
10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
–
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners
and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper
screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes
and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three
lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite
hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 1, pg. 2)
. Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed
reporting device. To activate alarm signal open the door of the enclosure.
4. Refer to the
eFlow Power Supply/Charger Installation Guide
for eFlow6NB, eFlow102NB, eFlow104NB and
Sub-Assembly Installation Guide
for the following models: ACM4, ACM8, LINQ2, PDS8, VR6 for further
installation instructions.
5. Fasten snap on spacers onto metal pems configuration of backplane depending on the Mercury access controller
(Fig. 2-5, pg. 3-6)
.
6. Position Mercury access controller module over corresponding spacers and depress onto snap on spacers
(Fig. 2-5, pg. 3-6)
.
7. Mount backplane to enclosure with hardware.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure