Altronix TROVE T1RHW3F4 Installation Manual Download Page 3

 

T1RHW3F4 Installation Guide 

- 3 -

Installation Instructions for T1RHW3F4:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local

codes and authorities having jurisdiction. These products are for indoor use only and must be installed within 

the protected premises.

Note:

 First assemble and Install Z Bracket Wire Management Accesory

(refer to Z Bracket Installation pg. 4)

1.  Remove backplane from enclosure prior to installing into rack cabinet 

 

(do not discard hardware).

2.  In order to mount included UL Listed tamper switch (Altronix Model TS112 or

 

 equivalent) turn the enclosure upside down. Punch out the knockout in 

 

designated location, on the back of the unit, from outside of the drawer 

 

(Fig. 1, pg. 3)

. Insert the tamper switch into the knockout from outside of the 

 

drawer with the button facing outwards and spaded connectors inside the drawer.

 

Connect tamper switch wiring to the Access Control Panel input or the 

 

appropriate UL Listed reporting device. 

 

To activate alarm signal open the rack drawer.

3.  Slide the rack enclosure into an open 2U location in the four post rack cabinet.

4.  Utilizing proper fasteners attach front ears to the rack rails.

5.  Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.

6.  Secure the rack cover 

(Fig. 2a, pg. 3)

 and rack drawer to earth ground 

(Fig. 2b, pg. 3).

7.  Ensure that all internal cofigurations (voltage selection, switch settings, etc.) are completed before 

 

mounting backplane back into Trove rack enclosure.

8.  After all components are mounted on the backplane, attach it to the enclosure using included hardware. 

9.  Mount Honeywell modules to THW1R backplane, refer to

 page 5

.

10.  Refer to the 

eFlow Power Supply/Charger Installation Guide

 for eFlow6NB and corresponding sub-assembly

 

 

Installation Guides

 for the following models: ACM4(CB), PDS8(CB), VR6 for further instructions.

Fig. 1

Back of the drawer,

viewed from outside.

Tamper Switch

mounting location

Fig. 2

Fig. 2a

Fig. 2b

Reviews: