SMP3CTX220 Series Installation Guide

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral.

–  DC +

12VDC / 24VDC @ 2.5A continuous output.

*AC FAIL 

NC, C, NO

SMP3PMCTX220 only

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. 

Contact rating 1A @ 120VAC / 28VDC.

*Low Battery 

NC, C, NO

SMP3PMCTX220 only

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally

energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.

Low battery threshold:

12VDC output threshold set @ approximately 10.5VDC, 

24VDC output threshold set @ approximately 21VDC.

–  BAT +

Stand-by battery connections. Maximum charge rate 0.5A.