background image

 

- 2 -  

SMP10C24X220 Series

Overview:

SMP10C24X220 Series units convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input into a regulated 
24VDC @ 10A continuous supply current (see specifications). 

SMP1024X220 Series Power Supply Configuration Reference Chart:

Altronix 

Model Number

Accessory 

Power 

Distribution 

Module(s)

Number 

of 

Output(s)

Fused 

Outputs

PTC 

Outputs

Individual 

Output 

Rating

(A)

Supervised

220VAC 

50/60Hz 

Input

Current

(A)

24VDC

Total 

Output 

Current

(A)

SMP10C24X220

----

1

----

----

10A

----

1.8A

10A

SMP10PMC24X220

P

SMP10PM24P4220

PD4

4

P

----

3.5A

SMP10PM24P4C220

PD4CB

----

P

2.5A

SMP10PM24P8220

PD8

8

P

----

3.5A

SMP10PM24P8C220

PD8CB

----

P

2.5A

SMP10PM24P16220

PD16W

16

P

----

3.5A

SMP10PM24P16C22 PD16WCB

----

P

2.5A

Specifications: 

Installation Instructions:

Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI and with all local 
codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s 

 

upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the 

 

enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two

 

upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 6).

 

Secure enclosure to earth ground. 

2.  Connect ground wire to the ground lug. Connect AC power to the terminals marked [L & N] (Fig. 1, pg. 4 or Fig. 4, 
 

pg. 5). Use 18 AWG or larger for all power connections (Battery, DC output).

 

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).    

 

Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

3.  Measure output voltage before connecting devices. This helps avoiding potential damage.
4.  Connect devices to be powered:
 

a.  For Power Supply Board connect to the terminals marked [---  DC +]. 

 

b.  For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked  

 

 

[1P & 1N] through [4P & 4N] (Fig. 2, pg. 4), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 4), 

 

 

or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 5, pg. 5)

 carefully observing correct polarity.

Input:

•  Input 220VAC (working range 198VAC - 256VAC), 
  50/60Hz, 1.8A.

Output:

•  24VDC output. 
•  10A supply current. 
•  Filtered and electronically regulated outputs.
•  Short circuit and thermal overload protection.

Battery Backup:

•  Built-in charger for sealed lead acid or gel type batteries.
•  Maximum charge current 0.7A. 

Battery Backup 

(cont’d)

:

•  Zero voltage drop when switching over to battery backup.

Supervision 

(supervised models)

:

•  AC fail supervision (form “C” contacts). 
•  Battery presence and low battery supervision 
  (form “C” contacts). 

Visual Indicators:

•  AC input and DC output LED indicators.

Enclosure Dimensions 

(H x W x D)

:

  13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
  -  Accommodates up to two (2)12VDC/7AH batteries.

Summary of Contents for SMP10C24X220

Page 1: ...upervision with supervision Four 4 fuse protected outputs Four 4 PTC protected outputs SMP10PM24P8220 SMP10PM24P8C220 24VDC 10A total supply current 24VDC 10A total supply current with supervision with supervision Eight 8 fuse protected outputs Eight 8 PTC protected outputs SMP10PM24P16220 SMP10PM24P16C220 24VDC 10A total supply current 24VDC 10A total supply current with supervision with supervis...

Page 2: ...cure enclosure to earth ground 2 Connect ground wire to the ground lug Connect AC power to the terminals marked L N Fig 1 pg 4 or Fig 4 pg 5 Use 18 AWG or larger for all power connections Battery DC output Keep power limited wiring separate from non power limited wiring 115VAC 60Hz Input Battery Wires Minimum 0 25 spacing must be provided CAUTION Do not touch exposed metal parts Shut branch circui...

Page 3: ...e Status ON Normal operating condition Terminal Identification OLS250220 OLS257220 Power Supply Board Terminal Legend Function Description L G N Connect 220VAC to these terminals L to Hot N to Neutral DC 24VDC 10A total supply current AC FAIL N C C N O Used to notify loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 12...

Page 4: ...d Lug INPUT LED 1P 2P 3P 4P FUSED OUTPUTS 1N 2N 3N 4N COMMON OUTPUTS F1 F1 F2 F3 F4 COMMON POWER OUTPUTS 1P 1N 2P 2N 3P 3N 4P 4N DC Output to devices From Power Supply Board Factory Installed Used on PTC Models N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 1 D1 INPUT R1 LED DC Output to devices From Power Supply Board Factory Installed Used on PTC Models Fig 1 Fig 2 Fig 3 Fig 1a Pow...

Page 5: ...geable Stand by Battery Ground Lug Fig 4 Fig 4a LOW BAT NC C NO NC C NO OFF ON 5A 250V AC FAIL BAT DC 15 AC DC 220VAC power mains Divider Optional R Stand b Optional Rechargeable Stand by Battery Ground Lug 3 5A 250V For continuous protection against risk of fire replace fuses with same type and rating common outputs protected outputs P N N P S XFMR Input 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 N P...

Page 6: ...2 12VDC 7AH batteries 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm ...

Page 7: ...SMP10C24X220 Series 7 Notes ...

Page 8: ...cal errors Product specifications are subject to change without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime warranty Made in U S A IISMP10C24X220 Rev 012610 H19P MEMBER Notes ...

Reviews: