SMP10C12X Series
Overview:
Altronix SMP10C12X Series power supply/chargers convert a 115VAC, 60Hz input into a regulated 12VDC
output with up to 10A of continuous load current (see specifications).
SMP10C12X Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory
Power
Distribution
Module(s)
Number
of
Outputs
Fused
Outputs
PTC Outputs
(auto-resettable)
Individual Output
Rating (A)
Supervised
115VAC
50/60Hz
Input
Current
(A)
12VDC
Total
Output
Current
(A)
SMP10C12X
-
1
–
–
10A
–
1.45A
10A
SMP10C12XX*
–
–
SMP10PMC12X
–
–
P
SMP10PMC12XX*
–
–
SMP10PM12P4
PD4
4
P
–
3.5A
SMP10PM12P4CB
PD4CB
–
P
2.5A
SMP10PM12P8
PD8
8
P
–
3.5A
SMP10PM12P8CB
PD8CB
–
P
2.5A
SMP10PM12P16
PD16W
16
P
–
3.5A
SMP10PM12P16CB
PD16WCB
–
P
2.5A
*Refer to Fig. 2, pg. 5 and Enclosure Dimensions on pg. 8 for enclosure size.
Specifications:
Input:
• Input 115VAC, 60Hz, 1.45A.
Output:
• 12VDC output.
• 10A supply current.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 0.7A.
• Zero voltage drop when switching over to
battery backup.
Features:
• Power ON/OFF switch.
Supervision
(select models)
:
• AC fail supervision (form “C” contacts).
• Battery presence and low battery supervision
(form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0ºC to 49ºC ambient.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
SMP10C12X, SMP10PMC12X,
SMP10PM12P4, SMP10PM12P4CB,
SMP10PM12P8, SMP10PM12P8CB,
SMP10PM12P16, SMP10PM12P16CB:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
SMP10C12XX, SMP10PMC12XX:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pgs. 7, 8). Secure enclosure to earth ground.
2. Slide [Power ON/OFF] switch t o OFF position (Fig. 1a, pg. 4).
3. Connect AC power to the terminals marked [L & N], connect ground to the green flying lead (Fig. 1, pg. 4).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).