R2432UL Series 

- 3 - 

9.  Green power LEDs on faceplate will illuminate when AC power is present. When an output is in a trouble condition

 

(blown fuse or tripped PTC) the corresponding LED will not be illuminated (Fig. 1, pg. 3):  

 

a.  Blown fuse (R2432300UL and R2432600UL) - Set power switch on the back of the unit to the OFF position

  (Fig. 1c, pg. 3). Remove faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA (Altronix model # Fuse1).

 

b.  Tripped PTC (R2432300ULCB and R2432600ULCB) - To reset PTC, set power switch on the back of the unit 

 

 

to the OFF position. After approximately 30 sec. set power switch to the ON (RESET) position (Fig. 1c, pg. 3).

10.  Power switch with built-in circuit breaker:

 

OFF position - Switch not illuminated. Outputs not powered.

 

RESET (ON) position - Switch illuminated. Outputs powered.

 

Circuit breaker tripped - Switch not illuminated. Power LEDs on faceplate are not illuminated. Outputs not powered.

 

To reset circuit breaker set power switch to the ON (RESET) position (Fig. 1c, pg. 3).

Note:  Do not exceed unit’s electrical load ratings as indicated in reference chart (Pg. 2).

  Do not place mechanical load on the unit.

 

 

Unit is designed optimally for normal data room office installations. Data racks should always be properly ventilated.

CAUTION:  Equipment to be installed/serviced by authorized personnel only.
 

Shut brunch circuit power before servicing/installing equipment.

WARNING:  To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
 

This installation should be made by qualified service personnel and should conform

 

to the National Electrical Code and all local codes.

AC Power

LED's

AC Power

LED's

AC Power

LED's

AC Power

LED's

AC Power

LED's

AC Power

LED's

Divider

AC Power

LED's

AC Power

LED's

Removable Terminal 

Block 

(Green Wire

Earth GND)

 PTC1

Used 

on PTC 

Models

RESET

XFMR*

XFMR*

P

N

N
P

Divider

S

S

P

N

N
P
S

S

Illuminated  

Power Disconnect  

Circuit Breaker with  

manual reset 

S

P

N

S

P

N

24VAC Output

(Factory Set)

28V

AC

28V

AC

24V

AC

24V

AC

28VAC Output

Strain Relief 

Line Cord 

Fig. 1

Fig. 1a

Fig. 1d

Fig. 1e

Fig. 1b

Fig. 1c

Reviews: