MaximalRDV Rack Access Power Controllers (PTC)
- 5 -
18 .
Fire Alarm Interface connection options:
a . Connect the FACP trigger input to the removable terminals marked FACP1 and FACP2 . When using
the polarity reversal from an FACP signaling circuit, connect the negative [–] to the terminal marked
FACP1 and the positive to the terminal marked FACP2 (polarity is in alarm condition)
(Rack Mechanical Drawing and Dimensions pg. 12) .
b . For a latching fire alarm interface connect a normally [NO] reset switch to the removable terminals
marked [REST] and [GND] (Figs. 6-11, pg. 9) .
19 . Set the power disconnect circuit breaker to the ON position (Fig. 15a, pg. 12) .
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage
level (Output Voltage and Stand-by Specification Charts, pg. 5).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at
the battery terminals and at the board terminals marked [– BAT +] to ensure that there is no break in the battery
connection wires .
Fire Alarm Interface Switch Settings:
Switch Position
FACP Input
SW1
SW2
OFF
OFf
FACP Signal Circuit (Polarity Reversal) .
ON
ON
Normally Closed [NC] Trigger Input .
ON
OFF
Normally Open [NO] Trigger Input .
Output Voltage and Stand-by Specification Charts:
Altronix Model
Power Supply Board
Battery
20 Min. of
Backup
4 Hr. of
Backup
24 Hr. of
Backup
Maximal1RHV
Maximal1RV
OLS120
(Refer to Fig. 1a, pg. 6 for Switch
[SW1] location and position)
12VDC/40AH*
N/A
3 .5A
0 .5A
24VDC/40AH*
N/A
2 .7A
0 .7A
Maximal3RHV
Maximal3RV
Maximal33RV
AL600XB220
(Refer to Fig. 1a, pg. 6 for Switch
[SW1] location and position)
12VDC/40AH*
N/A
5 .5A
5 .5A
24VDC/40AH*
N/A
5 .5A
0 .7A
LED Diagnostics:
Power Supply Board
LED
Power Supply Status
Red (DC)
Green (AC)
ON
ON
Normal operating condition .
ON
OFF
Loss of AC . Stand-by battery supplying power .
OFF
ON
No DC output . Short circuit or thermal overload condition .
OFF
OFF
No DC output . Loss of AC . Discharged battery .
Output LEDs on Front Panel
ON
Output is triggered .
Blinking
FACP disconnect .