background image

 

- 4 - 

Maximal Expandable Power Systems

MaximalE Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local 

codes and authorities having jurisdiction . Product is intended for indoor use only . 

1 . Mount unit in the desired location . Mark and predrill holes in the wall to line up with the top three keyholes 

  in the enclosure . Install three upper fasteners and screws in the wall with the screw heads protruding . Place 

  the enclosure’s upper keyholes over the three upper screws, level and secure . Mark the position of the lower 

  three holes . Remove the enclosure . Drill the lower holes and install the three fasteners . Place the enclosure’s 

  upper keyholes over the three upper screws . Install the three lower screws and make sure to tighten all 

 screws 

(Enclosure Dimensions, pg. 12) .

2 . The power supply is pre-wired to the ground (chassis) . Connect main incoming ground to the provided green 

  grounding conductor lead . Connect unswitched AC power (115VAC, 60Hz) to the terminals marked [L, N] 

  on both  power supply boards . Use 14 AWG or larger for all power connections . (Fig. 2, pg. 6) . 

  Green “AC” LED on power supply board will turn on . 

  This light can be seen through the LED lens on the door of the enclosure . 

 

Keep power-limited wiring separate from non power-limited wiring. 

  Minimum 0.25” spacing must be provided.

  CAUTION: Do not touch exposed metal parts. 

  Shut branch circuit power before installing or servicing equipment. 

  There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

3 . Select desired DC output voltage by setting SW1 to the appropriate position, (Maximal11E, Maximal13E,

  Maximal33E, Maximal35E and Maximal37E) (Fig. 1, pg. 5). 

  Maximal55E power supplies are factory set at 12VDC . Maximal77E power supplies are factory set at 24VDC . 

  Maximal75E power supplies are factory set at 12VDC and 24VDC (Power Supply Board Stand-by Battery 

  Specifications, pg. 5).

4 . Measure the output voltage of the unit before connecting any devices to ensure proper operation .

  Improper or high voltage will damage these devices .

5 . Connect devices to be powered to the terminals marked [+ DC –] (Fig. 2, pg. 6) .

6 . For Access Control applications batteries are optional . When batteries are not used, a loss of AC will result 

  in the loss of output voltage . When the use of stand-by batteries is desired, they must be lead acid or gel type . 

  Connect battery to the terminals marked [+ BAT –] (Figs. 2-7, pgs. 6-11) .

  Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included) .

7 .  Battery and AC Supervision outputs: It is required to connect supervisory trouble reporting devices to outputs 

  marked [AC FAIL, BAT FAIL] supervisory relay outputs marked [NC, C, NO] to appropriate visual 

  notification devices . Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting (Fig. 2a, pg. 6) . 

8 . Mount UL Listed tamper switch (not included) (Altronix model TS112 or equivalent) at the top of the 

  enclosure . Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right 

 side 

(Fig. 2b, pg. 6) .

  Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device . 

  To activate alarm signal open the door of the enclosure .

9 . Please ensure that the cover is secured with the provided key lock .

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:  Under normal load conditions the DC output voltage should be checked for proper 

   

 

voltage level (Power Supply Stand-by Battery Specifications, pg. 5).

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

   

 

voltage at the battery terminals and at the board terminals marked [+ BAT –] to ensure 

   

 

that there is no break in the battery connection wires .

Note: AL400ULXB2, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current is 0 .7A . 

       AL1024ULXB2 (Power Supply Board) maximum charge current is 3 .6A .

Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary .

Power Supply Board LED Diagnostics:

LED

Power Supply Status

Red (DC)

Green (AC)

ON

ON

Normal operating condition .

ON

OFF

Loss of AC . Stand-by battery is supplying power .

OFF

ON

No DC output . Short circuit or thermal overload condition .

OFF

OFF

No DC output . Loss of AC . Discharged battery .

Red (Bat)

Battery Status

ON

Normal operating condition .

OFF

Battery fail/low battery .

Summary of Contents for Maximal11E

Page 1: ...C or 24VDC 6A Power Supply 2 12VDC or 24VDC 6A Maximal37E Power Supply 1 24VDC 10A Power Supply 2 12VDC or 24VDC 6A Maximal75E Power Supply 1 12VDC 10A Power Supply 2 24VDC 10A Maximal13E Power Supply...

Page 2: ...ation pg 5 Power Supply Board Stand by Battery Specifications pg 5 Power Supply Board Output Voltage Settings pg 5 NEC Power Limited Wiring Requirements for Maximal11E pg 7 NEC Power Limited Wiring Re...

Page 3: ...6A 12VDC 6A 24VDC 6A 24VDC 6A 24VDC 6A Maximal35E AL1012ULXB AL600ULXB 2 6 1A 5A 250V 15A 32V AL1012ULXB 12VDC 10A 12VDC 6A 12VDC 10A 24VDC 6A Maximal37E AL1024ULXB2 AL600ULXB 2 7 9A 5A 250V 15A 32V A...

Page 4: ...s to be powered to the terminals marked DC Fig 2 pg 6 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When t...

Page 5: ...AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 0 7A AL1024ULXB2 Power Supply Board maximum charge current is 3 6A Power Supply Board Stand by Battery Specifications Altronix Mod...

Page 6: ...ttery Optional 12VDC Rechargeable Battery Optional 12VDC Rechargeable Battery Optional Ground Wire Line Earth Ground Neutral Line Neutral Input 115VAC 60Hz BAT FAIL L G N DC NO C NC NO C NC BAT AC FAI...

Page 7: ...rent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or F...

Page 8: ...erent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or...

Page 9: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Page 10: ...ire different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gaug...

Page 11: ...erent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or...

Page 12: ...0 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5 38 1mm 1...

Reviews: