MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems

MaxFitFE Series Overview:

Altronix MaxFit Expandable Power Systems provide system designers and installers with optimum    power 
choices and the highest levels of versatility. They provide 12VDC or 24VDC via single output power supply/
charger. Includes AC fail, low battery, and battery presence monitoring. Enclosure accommodates up to four (4) 
12VDC/12AH batteries. All interconnecting equipment must be UL Listed.

MaxFitFE Series Configuration Chart:

Altronix
Model 
Number

120VAC

60Hz

Input

Current

Input

Fuse

Rating

Battery

Fuse

Rating

Nominal DC Output Voltage Options

Maximum 

Supply

Current

for Main

and Aux. 

Outputs

Ripple 

Voltage 

(mV)

Under

low

battery 

condition

[DC]

[AUX]

12VDC 
Output

Range (V)

24VDC 
Output

Range (V)

12VDC 
Output

Range (V)

24VDC 
Output

Range (V)

MaxFit3FE

3.5A

5A/250V

10A/32V

10.0-13.2 20.19-26.4 10.03-13.2 20.19-26.4

6A

910

MaxFit5FE

3.5A

5A/250V

15A/32V

10.03-13.2

10.03-13.2

10A

760

MaxFit7FE

4.5A

6.3A/250V 15A/32V

20.17-26.4

20.17-26.4

10A

700

DC outputs for these power supplies are not power-limited. If a power-limited output is required in the end-product ap-
plication, DC output from the power supply must be connected to a separately Listed control unit or accessory board that 
provides power-limited outputs. The product(s) providing the power-limited output(s) must be listed as appropriate 
for the particular end-productapplication and wired in accordance with the products installation instructions. Class 1 
wiring methods, separation of circuits, and proper fire-rated enclosures all must be considered when connecting the 
DC output of the power supply to the end-product devices. The auxiliary outputs of these units are power-limited.

MaxFitFE Series Features:

•  Input: 120VAC, 60Hz.
•  For output voltage and supply current refer to MaxFitFE series Configuration Chart, pg. 2.
•  Auxiliary Power-Limited output rated @ 1A (unswitched).
•  Overvoltage protection.
•  Built-in charger for sealed lead acid or gel type batteries.
•  Maximum charge current 1.54A.
•  Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous
  with no interruption.
•  Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open 
  (NO) or normally closed (NC) trigger.
•  AC fail supervision (form “C” contacts).
•  Battery fail & presence supervision (form “C” contacts).
•  Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units 
  and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
•  For fuse ratings refer to MaxFitFE series Configuration Chart, pg. 2.
•  Green AC Power LED indicates 120VAC present.
•  AC input and DC output LED indicators.
•  Short circuit and overload protection.
•  Enclosure accommodates up to four (4) 12VDC/12AH batteries.
Enclosure dimensions (H x W x D): 20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm).

Summary of Contents for Maximal Fit Series

Page 1: ...24VDC 6A MaxFit5FE 12VDC 10A MaxFit7FE 24VDC 10A Rev MFEPS080119 More than just power TM Installing Company _________________ Service Rep Name _______________________________________ Address ________...

Page 2: ...appropriate for the particular end productapplication and wired in accordance with the products installation instructions Class 1 wiring methods separation of circuits and proper fire rated enclosure...

Page 3: ...d a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect battery to the terminals marked BAT Fig 1g pg 4 Use tw...

Page 4: ...is supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Red Bat Battery Status ON Normal operating condition OFF Battery fail low battery L G N NC C N...

Page 5: ...4 AC FAIL NC C NO Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 30VDC power limited Fig 1b pg 4 BAT FAIL N...

Page 6: ...8 CB VR6 C PD16W CB D NetWaySP3B NetWay4EB NetWaySP4B NetWaySP8B Fig 3a Tamper Switch To Access Control Panel or UL Listed Reporting Device Edge of Enclosure Enclosure External Jacketed Shield Incorre...

Page 7: ...7 MaxiFit3FE MaxFit5FE MaxFit7FE Expandable Power Systems Notes...

Page 8: ...81 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIMaxFit3FE 5FE 7FE Series H21S MEMBER MaxFit Enclosure Dimensions approximate 20 5 x 16 5 x 6 25...

Reviews: