FireSwitch108
- 5 -
3 . Connect two (2) 12VDC batteries wired in series to terminals marked [– BAT +] (Fig. 2, pg. 5) .
Note: If batteries being used in your installation do not fit into the FireSwitch unit, it is required to install
a separate enclosure UL Listed for appropriate application . Separate battery enclosure is required to have
50 cubic inches of additional open space . All wiring methods shall be in accordance with the National
Electrical Code NFPA 70/NFPA 72/ANSI/Canadian Electrical Code/CAN/ULC-S524/ULC-S527/
ULC-S537 and with all local codes and authorities having jurisdiction . Battery circuits are not Power-
Limited provide 0 .25” spacing from Power-Limited circuits use separate knockout . If additional battery
enclosure is required it must be UL Listed for the application and mounted within 5’ of the FireSwitch
enclosure in the same room, minimum 12 AWG wire in appropriate conduit is required for connection .
When using conduit, make sure it is installed in a matter where it can not turn .
4 . To trigger NAC outputs via the FACP signaling circuit(s) (polarity reversed) set INP1 and INP2 DIP
switches to the OFF position . To trigger NAC outputs via the FACP dry relay contact (normally closed NC)
set INP1and INP2 DIP switches to the ON position (Fig. 2a, pg. 5).
5 . Determine the functionality of outputs [OUT1] through [OUT8] . Outputs can be programmed as Class “A”
NACs, Class “B” NACs, Aux . power output(s) with battery backup or Aux . power output(s) without
battery backup .
Note: Not all devices can use the sync feature .
Be sure to check Appendix A to ensure the device you havechosen will work with this feature .
Note: When programming outputs for Aux . power it will not be affected by the FACP trigger input .
(Refer to Fig. 4, pg. 8 for Wiring, for Programming refer to pg. 9) .
Battery 1
Battery 2
Green
Lead
Battery connections are Non Power-Limited:
Use two (2) 12V batteries connected in series
Door
Wire Strap from
Enclosure to Door
Unswitched
120VAC 60Hz
Supervised
INP1
RET1
INP2
RET2
OUT1 OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
Non
Power-
Limited
Non
Power-
Limited
Power-Limited
Regulated
Non Supervized,
Class E
Inputs
Power-Limited
Supervised
+ SYNC
---
GF1
GF2
NC
NO
C
EA
RT
H
NEGA
TIV
E
POSITIV
E
ETHERNET
RIGHT
LEFT
UP
DOWN
PRESS DOWN
FOR ENTER
Power-
Limited
Non
Supervised
Class E
+
24V
--
+
AUX
--
BA
T F
AIL
AC
FA
IL
---
BA
T
++
DC
--
DC
AC
NC
C
NO
NC C
NO
Class 1
AC LOCA
L
NC
C NO
L
N
Battery and AC Supervision
Circuit (power-limited).
Non supervised Class E
Use separate knockout.
Keep 0.25" spacing between Power-Limited wiring and Non Power-Limited wiring
6.3A 250V
INP2
INP1
INP2
INP1
ON
INP2
INP1
INP2
INP1
ON
DIP Switch
Non Power-Limited
Input
Fuse
Non Power-Limited
Supervised
15
15
A
32
V
ON
AC DELAY
OFF 2 Hour
s
ON 1 minute
Power-Limited Supervised Outputs - Regulated 2.5A per output in alarm
When programmed for AUX - Non Supervised Class E Special Application only
Fig. 2
Fig. 2a