Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
 

in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

 

the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower 

 

two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 14-16). Secure enclosure to earth ground.

2.  Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL or    
 ALTV248ULCB 

(Figs. 1a, 2a, pgs. 4, 5). Set power disconnect circuit breaker to OFF position for all 

 

other models (Figs. 3a - 10a, pgs. 6-13).

3.  All units are factory set for 24VAC operation. 
 

For 28VAC operation adjust unit prior to mounting and applying power as follows: 

 

Change the wire position so that the wire marked [28V] is connected to the terminal marked [P] and 

 

the wire marked [24V] is connected to the terminal marked [S]

 

Note: ALTV248ULCB set for 28VAC operation is not Class 2 Rated, not power-limited.

4.  Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1-10, pgs. 4-13)
 

secure green lead to earth ground. Use 18 AWG or larger for all power connections.

 

Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided. Use separate knockouts.

5.  Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL or    
 ALTV248ULCB 

(Figs. 1a, 2a, pgs. 4, 5). Set power disconnect circuit breaker to RESET (ON) position 

 

for all other models (Figs. 3a-10a, pgs. 6-13).

6.  Measure output voltage before connecting devices. This helps avoiding potential damage.
 

Terminals marked [1P] - [8P] are of the same polarity.

 

CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting 

 

the output voltage.

7.  Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL or    
 ALTV248ULCB 

(Figs. 1a, 2a, pgs. 4, 5). Set power disconnect circuit breaker to OFF position for all 

 

other models (Figs. 3a-10a, pgs. 6-13).

8.  Connect devices to terminals marked [1P] - [1N] through [4P] - [4N] on PD4/PD4CB board (Figs. 9, 10, 
 

pgs. 12, 13) or terminals marked [1P] - [1N] through [8P] - [8N] on PD8/PD8CB board (Figs. 1-8, 

 

pgs. 4-12), carefully observing polarity.

9.  Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL or    
 ALTV248ULCB 

(Figs. 1a, 2a, pgs. 4, 5). Set power disconnect circuit breaker to RESET (ON) position 

 

for all other models (Figs. 3a-10a, pgs. 6-13).

10.  Green LED will illuminate when power is present.
11.  Upon completion of wiring, secure enclosure door with screws (supplied). 
 

Installation of cam lock is optional.

 

Caution: Equipment to be installed/serviced by authorized/trained personnel only. 

 

Shut branch circuit power before installing/servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This 
installation should be made by qualified service personnel and should conform to the National Electrical 
Code and all local codes. Use 75˚C or higher rated UL insulated wiring for connecting the unit to the mains. 
Replace fuses with the same type and rating (refer to Eight (8) Output ALTV248UL Reference Chart, pg. 2).

Terminal Identification:

PD4/PD4CB - Distribution Module

1P - 4P

AC output.

1N - 4N

AC output.

PD8/PD8CB - Distribution Module

1P - 8P

AC output.

1N - 8N

AC output.

Summary of Contents for ALTV248175UL

Page 1: ...0ULM 24VAC 12 5A 300VA or 28VAC 10A 280VA Eight 8 Fuse Protected Outputs ALTV248600UL 24VAC 25A 600VA or 28VAC 20A 560VA Eight 8 Fuse Protected Outputs ALTV248ULCB 24VAC 3 5A 85VA or 28VAC 3A 85VA Eight 8 PTC Protected Outputs ALTV248175ULCB 24VAC 7A 175VA or 28VAC 6 25A 175VA Eight 8 PTC Protected Outputs ALTV248300ULCB 24VAC 12 5A 300VA or 28VAC 10A 280VA Eight 8 PTC Protected Outputs ALTV248300...

Page 2: ... 28VAC 10A ALTV248300ULM 24VAC 12 5A 8 P 3 5A 3 5A 15A 32V 2 7A 28VAC 10A ALTV248300ULCBM 24VAC 12 5A 8 P 2 5A 15A 32V 2 7A 28VAC 10A ALTV248600UL 24VAC 25A 8 P 3 5A 3 5A 15A 32V 5 4A 28VAC 20A ALTV248600ULCB 24VAC 25A 8 P 2 5A 15A 32V 5 4A 28VAC 20A Specifications Agency Listings UL Listed for Commercial CCTV Equipment UL 2044 CUL Listed CSA Standard C22 2 No 1 98 Audio Video and Similar Equipmen...

Page 3: ... power distribution board marked PD to ON position for models ALTV248UL or ALTV248ULCB Figs 1a 2a pgs 4 5 Set power disconnect circuit breaker to RESET ON position for all other models Figs 3a 10a pgs 6 13 6 Measure output voltage before connecting devices This helps avoiding potential damage Terminals marked 1P 8P are of the same polarity CAUTION Determine the maximum operating voltage of the equ...

Page 4: ...in the literature accompanying the appliance CAUTION To reduce the risk of electric shock do not open enclosure There are no user serviceable parts inside Refer servicing to qualified service personnel N P S N P S 24VAC Output 28VAC Output 28V 24V 24V 28V Voltage Selection Configuration Primary In line Fuse LED INPUT ON OFF MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P...

Page 5: ... Follow same procedure using terminals 2P N through 8P N for outputs 2 through 8 LED INPUT ON OFF MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N PD8 24VAC configuration Class 2 Not Wet Class 3 Wet 28VAC configuration Class 1 Green Lead ground Black Lead White Lead Input 115VAC 50 60Hz non power limited Fig 2 ALTV248ULCB Fig 2a ...

Page 6: ...edure using terminals 2P N through 8P N for outputs 2 through 8 LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N Green Lead ground Black Lead White Lead Input 115VAC 50 60Hz non power limited Fig 3 ALTV248175UL Fig 3a N P S N P S 24VAC Output 28VAC Output 28V 24V 24V 28V Voltage Selection Configuration ...

Page 7: ... N through 8P N for outputs 2 through 8 LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N Class 2 Not Wet Class 3 Wet Green Lead ground Black Lead White Lead Input 115VAC 50 60Hz non power limited Fig 4 ALTV248175ULCB Fig 4a N P S N P S 24VAC Output 28VAC Output 28V 24V 24V 28V Voltage Selection Configuration ...

Page 8: ...n Illuminated Power Disconnect Circuit Breaker with manual reset 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 8P N for outputs 2 through 8 LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N Class 1 Outputs Green Lead ground White Lead Black Lead Input 115VAC 50 60Hz ...

Page 9: ...minated Power Disconnect Circuit Breaker with manual reset 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 8P N for outputs 2 through 8 LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N Class 2 Not Wet Class 3 Wet Green Lead ground White Lead Black Lead Input 115VAC 50 60Hz ...

Page 10: ...nfiguration Illuminated Power Disconnect Circuit Breaker with manual reset Black Lead White Lead Green Lead ground LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N Transformer underneath power distribution board Input 115VAC 50 60Hz Fig 7 ALTV248300ULM Fig 7a ...

Page 11: ...iguration Illuminated Power Disconnect Circuit Breaker with manual reset Black Lead White Lead Green Lead ground Transformer underneath power distribution board Input 115VAC 50 60Hz LED INPUT MAIN FUSE COMMON POWER OUTPUTS FUSED POWER OUTPUTS N P S 1 2 3 4 5 6 7 8 P N Fig 8 ALTV248300ULCBM Fig 8a ...

Page 12: ...e Lead Input 115VAC 50 60Hz 1P 1N 2P 2N 3P 3N 4P 4N LED 3 5A 250V 3 5A 250V 3 5A 250V N P S MAIN FUSE 1P 1N 2P 2N 3P 3N 4P 4N LED 3 5A 250V 3 5A 250V 3 5A 250V N P S MAIN FUSE Class 1 Outputs Class 1 Outputs Fig 9 ALTV248600UL Fig 9a N P S N P S 24VAC Output 28VAC Output 28V 24V 24V 28V Voltage Selection Configuration ...

Page 13: ... 2P 2N 3P 3N 4P 4N LED N P S MAIN FUSE 24VAC configuration Class 2 Not Wet Class 3 Wet 28VAC configuration Class 1 1P 1N 2P 2N 3P 3N 4P 4N LED N P S MAIN FUSE 24VAC configuration Class 2 Not Wet Class 3 Wet 28VAC configuration Class 1 Fig 10 ALTV248600ULCB Fig 10a N P S N P S 24VAC Output 28VAC Output 28V 24V 24V 28V Voltage Selection Configuration ...

Page 14: ...5mm Enclosure Dimensions H x W x D ALTV248UL ALTV248ULCB 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm Enclosure Dimensions H x W x D ALTV248300ULM ALTV248300ULCBM 8 5 x 7 5 x 3 875 215 9mm x 191mm x 98 4mm 3 63 92 2mm 7 25 184 15mm 7 25 184 15mm 1 25 4mm 1 25 4mm 1 25 4mm 1 75 44 45mm 8 13 206 5mm 8 13 206 5mm 3 85 97 79mm 1 25 4mm 1 25 4mm 1 25 4mm 3 85 97 79mm 1 25 4mm 1 25 31 75mm 1 25 31 75mm 1 ...

Page 15: ...4mm 5 75 146 05mm 1 25 4mm 1 13 28 7mm 5 88 149 35mm 0 88 22 35mm 0 88 22 35mm 1 11 28 19mm 1 11 28 19mm 4 5 114 3mm 4 5 114 3mm 4 5 114 3mm 4 5 114 3mm 7 5 190 5mm 7 5 190 5mm 2 5 63 5mm 12 304 8mm 12 304 8mm Enclosure Dimensions H x W x D ALTV248175UL ALTV248175ULCB ALTV248300UL ALTV248300ULCB 12 x 7 5 x 4 5 304 8mm x 190 5mm x 114 3mm ...

Page 16: ... IIALTV248UL Series D03R MEMBER Enclosure Dimensions H x W x D for ALTV248600UL ALTV248600ULCB 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 937...