XBV Power Supply/Chargers 

- 3 -

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:  Under normal load conditions, the DC output voltage should be checked for proper 
   

voltage level.

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

   

voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the 

   

board terminals marked [+ BAT –] to ensure that there is no break in the battery 

   

connection wires.

Replacing Batteries: 

Disconnect existing batteries. Connect battery to the terminals marked [+ BAT –].

   

Use two (2) 12VDC batteries connected in series for 24VDC operation.

LED Diagnostics 

(AL300XB2V, AL400XB2V and AL600XB220)

:

Red (DC)

Green (AC)

Red (BAT)

Power Supply Status

ON

ON

ON 

Normal operating condition.

ON

OFF

ON

Loss of AC. Stand-by battery is supplying power.

OFF

ON

OFF

No DC output. Battery trouble.

OFF

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

ON

ON

OFF

Battery missing / low.

LED Diagnostics 

(AL1012XB220 and AL1024XB2V)

:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend

Function/Description

L, G, N 
(Fig. 1a, pg. 4)

Connect 220VAC to these terminals: L to hot, G to ground, N to neutral.

+ DC – *
(Fig. 1d, pg. 4)

AL300XB2V: 

12VDC or 24VDC @ 2.5A continuous output.

AL400XB2V: 

12VDC @ 4A or 24VDC @ 3A continuous output.

AL600XB220: 

12VDC or 24VDC @ 6A continuous output.

AL1012XB220: 

12VDC @ 10A continuous output.

AL1024XB2220:  24VDC @ 8A continuous, 10A in alarm.

AC FAIL
NO, C, NC
(Fig. 1b, pg. 4)

Used to notify loss of AC power, e.g.connect to audible device or alarm panel. 
Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 
AC or brownout fail is reported within 1 minute of event. 
To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit.

BAT FAIL
NO, C, NC
(Fig. 1b, pg. 4)

Used to indicate low battery condition, e.g. connect to alarm panel. 
Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 
A removed battery is reported within 1 minute. 
Battery reconnection is reported within 1 minute.
Low battery threshold: approximately 21VDC.

+ BAT – **
(Fig. 1c, pg. 4)

Stand-by battery connections.
AL300XB2V, AL400XB2V, AL600XB220, AL1012XB220 maximum charge 
current 0.7A.
AL1024XB2V maximum charge current 3.6A.

AL1012XB220 terminals marked [– DC +]

**  AL1024XB2V terminals marked [– BAT +]