Altronix AL1042ADA220 Application Manual Download Page 6

 

- 6 - 

42ADA220 Application Guide

Output Programming Selection Table:

Outputs must be programmed independently (OUT1 - OUT4)

Function

Switch Positions

Descriptions

ON

OFF

Input to Output 

Follower Mode

1

2, 3

Output follows signal it receives from the corresponding input (i.e. FACP 

Sync module - maintains synchronization of notification appliance circuit).

Temporal 

Code 3 Mode

3

1, 2

Enables Temporal Code 3 signal generation output. 

This mode will accept a steady or a pulsing input.

Steady Mode

1, 2, 3 A steady output signal will be generated. 

This mode will accept steady or pulsing input.

For the above modes DIP Switch 4 determines which Input controls the corresponding output:

Switch 4 in the ON position causes output(s) to be controlled by Input 1.

Switch 4 in the OFF position causes output(s) to be controlled by Input 2.

Note: It is required to control visual notification appliances (strobes) via

Input 1 (IN1) and audible notification appliances (horns) via Input 2 (IN2).

This allows audible notification appliances (horns) and visual notification

appliances (strobes) to be silenced/ deactivated at same time.

The FACP must be capable of a visual annunciation to the silencing status of 

the output or zone(s) to which the NAC Power Extender is connected.

Sync Mode Selection Table:

Function

Switch Positions

Descriptions

ON

OFF

Amseco

Sync Mode*

1, 3,

4

2

This mode is designed to work with the Amseco series of horns, strobes, 

and horn/strobes to provide a means of synchronizing the Temporal-

coded horns, synchronizing the flash timing of the strobe, allowing 

audible notification appliances (horns) and visual notification appliances 

(strobes) to be silenced/deactivated at the same time.

Gentex

®

Sync Mode*

Gentex is a registered 

trademark of 

Gentex Corporation.

1, 2,

3, 4

This mode is designed to work with the Gentex

®

 series of horns, strobes, 

and horn/strobes to provide a means of synchronizing the Temporal-

coded horns, synchronizing the flash timing of the strobe, allowing 

audible notification appliances (horns) and visual notification appliances 

(strobes) to be silenced/deactivated at the same time.

System Sensor

®

Sync Mode*

System Sensor is a 

registered trademark 

of Honeywell.

1, 2, 4

3

This mode is designed to work with the System Sensor

®

 series of horns, 

strobes, and horn/strobes to provide a means of synchronizing the 

Temporal-coded horns, synchronizing the one-second flash timing of the 

strobe, allowing audible notification appliances (horns) and visual notifica-

tion appliances (strobes) to be silenced/deactivated at the same time.

CooperWheelock

®

Sync Mode*

CooperWheelock is a 

registered trademark 

of Cooper Wheelock.

2, 3, 4

1

This mode is designed to work with the CooperWheelock

®

 series of 

horns, strobes, and horn/strobes to provide a means of synchronizing the 

Temporal-coded horns, synchronizing the one-second flash timing of the 

strobe, allowing audible notification appliances (horns) and visual notifica-

tion appliances (strobes) to be silenced/deactivated at the same time.

*Note:

 AL642ADA220, AL842ADA220, and AL1042ADA220 will only synchronize horns, horn/strobes, and 

strobes that contain synchronization capability. Contact signal manufacturer for more detailed info. 

The same synchronization mode must be selected for all outputs.

AL842LGK Board

Output DIP Switches

INPUT SELECT

TEMPORAL

STROBE SYNC

IN>OUT SYNC

Summary of Contents for AL1042ADA220

Page 1: ...Extenders Application Guide see Installation Guide for additional information Rev 042010 More than just power TM Installing Company ________________ Service Rep Name __________________________________...

Page 2: ...B Hookups Each output 1 through 4 can be used in Class B or Class A configuration For Class A hookups loop starts on OUT 1 through 4 terminates on corresponding RET For Class B hookups loop starts on...

Page 3: ...of NAC Power Extenders Applications that do not employ synchronization module or FACP with synchronization protocol will not provide NAC synchronization between NAC Power Extenders 3 Non synchronizabl...

Page 4: ...5a For continuous loop circuit use 2 2K EOL Altronix Model AL EOL22 NAC Power Extender DIP Switches set for desired Sync Protocol ex Gentex System Sensor Amseco CooperWheelock FACP Fire Alarm Control...

Page 5: ...ect both Input 1 and Input 2 to it Wire RET1 and RET1 to INP2 and INP2 Both Visual and Audible appliances will be activated simultaneously Fig 6a EOL or Next Device For Class A configuration return to...

Page 6: ...le notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time Gentex Sync Mode Gentex is a registered trademark of Gentex Corporation 1 2 3 4...

Page 7: ...42ADA220 Application Guide 7 Notes...

Page 8: ...m 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4m...

Reviews: