42ADA220 Application Guide

5. Synchronizing NAC Power Extender Using Built-in Sync Protocol:

AL642/AL842/1042ADA220 have built-in protocols to support Potter/Amseco, Gentex

®

, System Sensor

®

CooperWheelock

®

 two-wire synchronizable devices, therefore an external sync module is not required 

(Output 

Programming Selection Table, pg. 6)

. In these modes, Input 1 is always used to activate visual notification appliances 

(strobes), and Input 2 is used to activate and silence audible notification appliances (strobes).

Note:

 Input 1 has to be activated in all the configurations.

Fig. 5a

  For continuous loop circuit use 2.2K EOL (Altronix Model# AL-EOL22).

NAC Power Extender:

DIP Switches set for desired Sync Protocol (ex. Gentex

®

System Sensor

®

, Amseco, CooperWheelock

®

).

FACP

(Fire Alarm

Control Panel)

2.2K

EOL

2.2K

EOL

2.2K

EOL

+  AUX1  ---- 

+  OUT1  ---- 

+  LOOP1  ---- 

+  LOOP2  ---- 

+  OUT2  ---- 

+  OUT3  ---- 

+  LOOP3  ---- 

+  LOOP4  ---- 

+  OUT4  ---- 

+  RET1  ---- 

+  IN1  ---- 

+  RET2  ---- 

+  IN2  ---- 

C "DRY2" NC

C "DRY1" NC

+  AUX1  ---- 

EOL or

Next Device.

For Class A

configuration

return to FACP

EOL or

Next Device.

For Class A

configuration

return to FACP

NAC Power Extender:

DIP Switches set to Input to Output Follower Mode

2.2K

EOL

2.2K

EOL

2.2K

EOL

+  AUX1  ---- 

+  OUT1  ---- 

+  LOOP1  ---- 

+  LOOP2  ---- 

+  OUT2  ---- 

+  OUT3  ---- 

+  LOOP3  ---- 

+  LOOP4  ---- 

+  OUT4  ---- 

+  RET1  ---- 

+  IN1  ---- 

+  RET2  ---- 

+  IN2  ---- 

C "DRY2" NC

C "DRY1" NC

+  AUX1  ---- 

Control Circuit

No Notification Appliances Allowed

To EOL or next 
NAC Power Extender
For Class A configuration
return to + LOOP4 -

Summary of Contents for AL1042ADA220

Page 1: ...Extenders Application Guide see Installation Guide for additional information Rev 042010 More than just power TM Installing Company ________________ Service Rep Name __________________________________...

Page 2: ...B Hookups Each output 1 through 4 can be used in Class B or Class A configuration For Class A hookups loop starts on OUT 1 through 4 terminates on corresponding RET For Class B hookups loop starts on...

Page 3: ...of NAC Power Extenders Applications that do not employ synchronization module or FACP with synchronization protocol will not provide NAC synchronization between NAC Power Extenders 3 Non synchronizabl...

Page 4: ...5a For continuous loop circuit use 2 2K EOL Altronix Model AL EOL22 NAC Power Extender DIP Switches set for desired Sync Protocol ex Gentex System Sensor Amseco CooperWheelock FACP Fire Alarm Control...

Page 5: ...ect both Input 1 and Input 2 to it Wire RET1 and RET1 to INP2 and INP2 Both Visual and Audible appliances will be activated simultaneously Fig 6a EOL or Next Device For Class A configuration return to...

Page 6: ...le notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time Gentex Sync Mode Gentex is a registered trademark of Gentex Corporation 1 2 3 4...

Page 7: ...42ADA220 Application Guide 7 Notes...

Page 8: ...m 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4m...

Reviews: