- 2 -
ACM4 Series
Overview:
These units convert one (1) 12 to 24 volt AC or DC input into four (4) independently controlled fused or PTC
protected outputs. These power outputs can be converted to dry form “C” contacts (ACM4 only). Outputs are
activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System,
Card Reader, Keypad, Push Button, PIR, etc. The units will route power to a variety of access control hard-
ware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. All interconnecting devices
must be UL Listed. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. Units are designed to be
powered by one common power source which will provide power for both the board operation and locking
devices, or two (2) totally independent power sources, one (1) providing power for board operation and the
other for lock/accessory power. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may
be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any
or all of the four (4) outputs.
Altronix
Model
Number
Number
of
Outputs
Fuse
Protected
Outputs
PTC
Protected
Outputs
Output
Ratings
Class 2 Rated
Power-Limited
Auto-Resettable
Agency Listings
ACM4
4
P
---
2.5A
---
ACM4CB
4
---
P
2A
P
UL Listings and File Numbers: UL File # BP6714. UL Listed for Access Control System Units (UL 294).
“Signal Equipment” Evaluated to CSA Standard C22.2 No.205-M1983
Specifications:
• 12 to 24 volt AC or DC operation (setting not required).
• Input Ratings: 12VDC @ 0.4A or 24VDC @ 0.2A.
• Power supply input options:
a) One (1) common power input (board and lock power).
b) Two (2) isolated power inputs (one (1) for board power and one (1) for lock/hardware power).
• Four (4) Access Control System trigger inputs:
a) Four (4) normally open (NO) inputs.
b) Four (4) open collector sink inputs.
c) Any combination of the above.
• Four (4) independently controlled outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5A rated relay outputs (ACM4 only).
c) Any combination of the above (ACM4 only).
• Four (4) auxiliary power outputs (unswitched).
• Output ratings:
- Fuses are rated 2.5A each.
- PTCs are rated 2A each.
• Main fuse is rated at 10A.
Note: For Models ACM4/ACM4CB refer to the Total Output Chart on Page 2.
Note: Operating temperature range should be 0 to +49oC.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable
for any or all of the four (4) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• FACP output relay (form “C” contact rated @ 1A/28VDC, not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Removable terminal blocks facilitate ease of installation.
Board Dimensions (L x W x H approximate): 5.175”x 3.36”x 1.25” (131.5mm x 85.6mm x 31.8mm)
Sub-Assembly