Altronic 6715 D Manual Download Page 14

 

6715D/Rev. Jul.2020 

Page 14 

Altronic Research Inc. 

3-8. Ducting.

  In many installations it will be necessary to duct the discharge air from the 

Model 6715D to the exterior of the building.  In some installations it will also be necessary 
to supply inlet air from outside of the climate-controlled portion of the building. 

 
 

The discharge air flow is approximately 325 SCFM at a maximum temperature of 250

°

F.  

Due to the high temperatures involved, non-metallic duct materials should not be used for 
the discharge duct, but may be suitable for inlet duct.  Attaching a discharge duct to the 
unit is easily accomplished: 

 
1. 

Remove the 10 torx head screws attaching the discharge grill. 

2. 

Then, replace the discharge grill with a discharge air duct adapter. 

 

Suitable ducting can then be attached to the adapter.  This duct should be as short as possible to 

minimize back pressure.  Design of the ducting and wall or ceiling penetrations should be 
referred to a competent heating and air conditioning firm. 

 
 

"Make-up air" is a ventilation term used to indicate the supply of outdoor replacement air 
to a building in a controlled manner.  It may be provided for the Model 6715D by ducting 
into the room or by extending a supply duct to either intake grill of the blower enclosure 
and installing a blanking plate on the other grill. 

 
 

Make-up air will enter the building to equal the volume actually exhausted, whether or not 
provision is made for this replacement.  However, the actual exhausted volume may not 
equal the design volume unless an adequate supply is provided. 

 

3-9.  Adjustments.

  No field adjustments are necessary or possible. 

 

3

-10. 

Preparation for Reshipment.

  No special measures are required to prepare the Model 

6715D for reshipment.  Care must be taken to protect the RF connector and to immobilize 
the swivel flange.  Packaging should provide protection against abrasion and impact.   

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for 6715 D

Page 1: ...ALTRONIC RESEARCH INC P O BOX 249 YELLVILLE ARKANSAS U S A 72687 0249 PHONE 870 449 4093 FAX 870 449 6000 1 800 482 LOAD 5623 in US altronic com MODEL 6715 D COAXIAL LOAD RESISTOR...

Page 2: ...6715D Rev Jul 2020 Page 2 Altronic Research Inc MODEL 6715D 15 KW DIGITAL UHF AIR COOLED COAXIAL RESISTOR...

Page 3: ...ement fails to be a satisfactory solution our limit of obligation shall be no more than full refund of the purchase price This warranty is limited to products of our own manufacture Equipment and comp...

Page 4: ...echanical Description 9 1 7 General Principle of Operation 9 1 8 Operating and Adjustment Controls 9 1 9 Operator Training 10 II Test Equipment and Special Tools 2 1 Test Equipment Required 11 2 2 Spe...

Page 5: ...0 Page 5 Altronic Research Inc SECTION PAGE V Maintenance 5 1 Cleaning 16 5 2 Lubrication 16 5 3 RF Circuit 16 VI Diagrams 6 1 Outline and Dimensions 17 6 2 Schematic Diagram 18 6 3 Parts List 19 VII...

Page 6: ...AL PROTECTION TO SHUT OFF FAN WHICH WILL CAUSE DAMAGE TO UNIT PROVISIONS ARE MADE TO TRIP THE INTERLOCK IN THE EVENT OF OVERHEAT BUT THE INTERLOCK MUST BE PROPERLY CONNECTED TO THE RF SOURCE FOR THIS...

Page 7: ...and or cause the unit to fail CAUTION Do not connect the unit to an RF power source without first ensuring that the load is connected to the proper line voltage and that the interlock circuit is prope...

Page 8: ...le phase 50 60 Hz 230 208 230VAC single phase 50 60 Hz 1 3 Equipment Required But Not Supplied The Model 6715D Coaxial Load is complete as supplied but the user must furnish AC Mains input RF input in...

Page 9: ...rill This places the RF input connector at the coolest point in the air stream and affords exceptionally quiet operation 1 7 General Principle of Operation After ascertaining that the Model 6715D is c...

Page 10: ...ent An understanding of the normal and abnormal indications which may be presented at the control point The proper procedures for starting using and stopping the equipment under normal conditions The...

Page 11: ...ial outlet air minus inlet air and ambient air temperature which the equipment is experiencing We recommend the John B Fluke Mfg Co Model 52 or equivalent instrument for this function 2 2 Special Tool...

Page 12: ...pecification sheet at the end of this manual Reading should be 1 ohm If not consult factory 3 3 Pre installation Tests Prior to installation connect the load to AC Mains power for the following tests...

Page 13: ...TTACHED TO THE PROPER AC POWER SUPPLY WITH INTERLOCK CONNECTED WHENEVER THE RF CONNECTOR IS ATTACHED TO THE SOURCE INADVERTENT APPLICATION OF RF POWER TO THE UNIT WITHOUT AC POWER MAY DAMAGE OR DESTRO...

Page 14: ...ible to minimize back pressure Design of the ducting and wall or ceiling penetrations should be referred to a competent heating and air conditioning firm Make up air is a ventilation term used to indi...

Page 15: ...ck Circuit Two thermal switches are connected in series from Control Line 1 to Interlock Relay RY2 terminal 13 These thermal switches are Single Pole Normally Closed and open at a specified temperatur...

Page 16: ...fan and motor by vacuuming Do not use solvents or an air jet as these can damage the motor Remove dirt and dust accumulations from the grills and resistor assembly with an air jet and a soft brush 5 2...

Page 17: ...6715D Rev Jul 2020 Page 17 Altronic Research Inc SECTION VI 6 1 OUTLINE AND DIMENSIONS...

Page 18: ...6715D Rev Jul 2020 Page 18 Altronic Research Inc 6 2 SCHEMATIC DIAGRAM...

Page 19: ...6715D Rev Jul 2020 Page 19 Altronic Research Inc 6 3 REPLACEMENT PARTS LIST MODEL 6715D CONSULT FACTORY...

Page 20: ...ating Sea Level 15 KW Frequency Range UHF Cooling Method Forced Air Ductable Ambient Temperature 30 C to 43 C Fan Assembly 3 4 hp direct drive centrifugal AC Power Requirements 115 VAC 60 Hz 9 Amp 1 P...

Reviews: