MN-28648 • Rev 3 (11/14) • AR-6G Rotisserie Operation & Care Manual • 12
I N S T A L L A T I O N
G A S C O N N E C T I O N S
The installation of this appliance must be completed by
a qualified installer familiar with the local codes and
regulations governing the installation of commercial gas
appliances. The installation must be made in accordance
with local codes or, in the absence of local codes, with
the National Fuel Gas Code ANSI Z223.1 (latest edition).
In Canada, the appropriate code is the Natural Gas
Installation Code, CAN/CGA-B149.1 or the Propane
Installation Code, CAN/CGA-B149.2.
❑
Both the appliance and the individual appliance shutoff
valve must be disconnected from the gas supply piping
system during any pressure testing of that system at
test pressures in excess of 1/2 psi (3.45 kPa).
❑
The appliance must be isolated from the gas supply
piping system by closing the individual appliance
manual shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal to or
less than 1/2 psi (3.45 kPa).
Use an approved gas pipe sealant at all external threaded
connections. Gas piping used on gas connections must
avoid sharp bends that may restrict the flow of gas to the
appliance. If the connected pressure exceeds 14.0" W.C.
(3.5 kPa), a step-down regulator is required to be supplied
by the owner/operator.
Close the individual manual shut-off valve to isolate
the appliance from the gas supply piping system during
any pressure testing at test pressures equal to or less
than 1/2 psig. (3,4 kPa). The appliance and individual
shut-off valve must be disconnected from the gas supply
piping system during any pressure testing at pressures
in excess of 1/2" psig. (3,4 kPa).
In the U.S.A., installation must conform to local codes
or, in the absence of local codes, with the current
edition of the National Fuel Gas Code, NFPA-54 and
ANSI Z83.11a CSA 1.8a 2004 (or latest edition). In
Canada, installation must be in accordance with local
codes, CAN/CGA-B149.1, Installation for Natural Gas
Burning Appliances and Equipment (latest edition)
or CAN/CGAB149.2 Installation for Propane Burning
Appliances and Equipment (latest edition).
The inlet supply line must be properly sized to
accommodate all individual appliances simultaneously
used on the same line but must never be smaller than
3/4" NPT.
INCORRECT
CORRECT
A
B
C
D
E
F
G
H
GAS INTAKE
A-G Installation elbow
B Wall Valve
C-D Three-piece union fitting
(minimum 1 per installation)
E-F End connector for the
flexible tube
H Marking line
D A N G E R
Installation, air adjustment and/or
service work must be in accordance
with all local codes and must be
performed by a certifi ed service
technician qualifi ed to work on
gas appliances.
D A N G E R
DO NOT store or use gasoline or other
fl ammable vapors or liquids in the
vicinity of this or any other appliance.
D A N G E R
NE PAS entreposer ni utiliser
d'essence ou d'autres vapeurs ou
liquides infl ammables à proximité de
cet appareil ou de tout autre appareil.