
5
WARNING:
CODE COMPLIANCE
Use of aluminum Type B gas
vent for solid fuels is unsafe and
prohibited by the National Fire
Protection Association Code.
Use of aluminum Type B gas vent for solid fuels
is unsafe and prohibited by the National Fire
Protection Association Code. The
recommended method for connecting the boiler
to the chimney is to place a T-joint at the top of
the vertical section leading from the breach
(exhaust) flange. The rear opening must be
covered with a cap, which can be removed for
cleaning and inspection. A horizontal run must
be included, with provision for pipe
disassembly, for pipe inspection and removal of
any fly ash that accumulates. If the horizontal
run to the chimney is inclined, it will encourage
any fly ash, which drops in the pipe to fall back
into the ash separator.
If a second change of direction is required
before entering the chimney a cleanout “T”
should be placed at this point also as indicated
in Figure 1. Each joint should be secured with
three sheet metal screws and sealed with high
temperature sealant capable of withstanding
650
°
F. Any horizontal pipe should be pitched
upward toward the chimney at least ¼” for each
foot of horizontal run. Ensure that there is at
least 18” clearance between horizontal piping
and combustible ceiling. Ensure that the
chimney connection pipe extends at least 2” into
the chimney, but does not extend so far into the
chimney that it blocks airflow. A “T” must
always be used where the stovepipe changes
directions (rather than elbow) to allow for
cleanout.
Figure 1: Proper chimney connection
Particular attention should be paid to the point
where a flue passes through a wall or ceiling.
The pass-thru should always be made with
insulated pipe and the proper accessories or use
of a thimble that provides a diameter of not less
than three times the diameter of the stovepipe.
(see Figure 2)
Figure 2: Stove pipe passing through wall
Summary of Contents for COAL GUN S1000
Page 2: ......
Page 4: ......
Page 7: ......
Page 8: ......
Page 29: ...21 the boiler should immediately be taken out of service and thoroughly cleaned ...
Page 30: ...22 APPENDIX A BOILER SPECIFICATION DIAGRAMS ...
Page 31: ...23 ...
Page 32: ...24 ...
Page 33: ...25 ...
Page 35: ...27 APPENDIX B WIRING DIAGRAMS ...
Page 36: ...28 ...
Page 37: ...29 ...
Page 38: ...30 ...
Page 39: ...31 ...
Page 40: ...32 APPENDIX C EXPLODED PARTS DRAWING ...
Page 42: ...34 ...
Page 54: ...46 APPENDIX H DUMP ZONE WIRING APPLICATIONS ...
Page 55: ...47 ...
Page 56: ...48 ...
Page 57: ...49 ...
Page 58: ...50 APPENDIX I BOILER PIPING EXAMPLES ...
Page 62: ...54 IMPORTANT READ AND KEEP IN YOUR POSSESSION ...