page 6
of 29
File: SM1150_r5eng - February 2007 - Technical note: SM1150
SM 1150
File: SM1150_r5eng - February 2007 - Technical note: SM 1150
page 7
of 29
SM 1150
Equipment maintenance
Cleaning
Cleaning of air filter: verify once a month. In case you need to
remove dust then proceed as follow:
- remove main line from the unit
- remove the cover
- use pressurized air from inside to outside for short time: do
not exceed or you may damage the fan
- install the cover and then power-on again.
Fuses replacement
To replace the fuses on rear panel proceed as follow:
- switch-off the main breaker on front panel or whatever device
is provided to remove main line from the equipment;
- unscrew fuseholder cap;
- replace the fuse with a new one with the same electrical
characteristics;
- inspect also the fuseholder: if it’s oxidated or it has burned
point then replace it;
- install the fuseholder cap and screw tight.
For the fuse value look at chapter “Fuses spec”, pg 5.
Equipment installation
The SM1150x cannot operate on a bench: it must be installed
into a proper cabinet like a commercial 19” standard enclo-
sure.
The equipment is intended for industrial use only, not for
laboratory use, and user must respect the wiring norms and
prescriptions as described into next paragraph (“Wiring
instruction”).
The equipment cannot operate cantilevered, it must be safely
fixed inside a cabinet by means of screws on the front panel
(which is provided with 4 holes) and supported by means of a
proper frame on the bottom for, at least, 3/4 of the total depth.
Usually two “L” shaped supports on each side of the equip-
ment, having a dimension of mm 10(h) x 30(l) x 2 (thick) are
suitable for that purpose.
The rear side of the equipment must be protected by a fixed
panel which can be removed only by means of tools or by a
door with security micro-switch: when the door is opened the
micro-switch must shut-off the main line. This safety precau-
tions must be taken to avoid operations on rear fuses or on
connectors while the unit is still powered.
Special attention must be taken on designing the cooling air
flow in case of stacking several units into the same cabinet.
Note that each equipment has its own fan which intake approx
120 m³/h: the outlet of the exhaust air is on rear panel, the
inlets on the right side (looking at front).
When designing a board to house several units we recommend
to adopt the following design criteria:
1. use a standard 19” wide enclosure with a depth of 800 mm
(32”);
2. allow free intake of the cooling air from the side of the cabi-
net and exhaust air from back panel throu the top of the cabinet
or the back side;
3. in case of ambient air with high degree of dust and moisture,
install a proper air conditioner; if you cannot do this, then you
have to use suitable air filters and instruct the user about their
cleaning;
4. provide a separation between the air intake duct and the air
outlets, in order to avoid air-recyrculating;
Handling instructions
The equipment weight is 17.3 kg (38 lbs). Always lift from the
bottom and use an adeguate rugged support to avoid personal
injury and damage to equipment itself.
In case of shipping, package with the original package or use
a wooden case and a proper filler: movement of the equipment
inside the package must be avoided.
Warning for handling:
use handles only for help during
installation.
Never use handles to lift the rack: the handles
don’t withstand the off-center weight of the rack!
To lift always lean the rack over a proper supporting base.
Wiring instructions
The SM1150 must be installed and serviced only by quali-
fied personnel acquainted with the regulations covering the
application. For safety operations the following rules must be
adopted:
I) The equipment must be grounded through the connector #1
using pin 4 (see the wiring diagram at page 20).
II) Connect the ground screw on panel rear (indicated by
“ground” symbol) directly to the remote microwave generator
head by a separate yellow/green wire gauge 2.5 mm².
Summary of Contents for SM1150
Page 19: ...page 18 of 29 File SM1150_r5eng February 2007 Technical note SM1150 SM 1150 ...
Page 21: ...page 20 of 29 File SM1150_r5eng February 2007 Technical note SM1150 SM 1150 Pin out of conn 1 ...
Page 23: ...page 22 of 29 File SM1150_r5eng February 2007 Technical note SM1150 SM 1150 Pin out of conn 5 ...