RPV311
Chapter 15
– Installation
RPV311-TM-EN-6
290
The equipment indicates sync when the data acquisition frequency is according to the equipment's nominal
acquisition frequency and the equipment's internal clock is updated.
The RPV311 internal clock is updated with every hour rollover or when the equipment turns to sync mode.
If the IRIG-B signal is not valid or not connected, the device indicates no sync. If the IRIG-B signal is
connected and valid, the time quality of the time reference reported in the IRIG-B frame is shown by the
RPV311, but the time quality is not considered by the synchronization.
In the absence of the IRIG-B signal, the equipment can be synchronized by an SNTP time server, however,
the acquisition frequency does not have the same stability afforded by the IRIG-B signal (accuracy less than
12 ppm), and the equipment does not indicate sync.
The IRIG-B signal is preferred over the SNTP time server.
If no IRIG-B signal is available and the SNTP server is unreachable, the unit obtains the time of an internal
CMOS clock. Drift is better than 0.1 second in 24 hours.
The RPV311 has an electrical and an optical IRIG-B input, as shown in
Figure 131: Electrical and optical inputs for sync using IRIG-B
To synchronize the equipment using fiber-optic input, use the appropriate fiber-optic type, considering its
minimum curvature radius.
The use of a twisted pair cable is recommended for the electrical input.
For distances greater than 3 m, to minimize EMC effects, the use of fiber-optic cable is recommended.
5.14.1
CONNECTION DIAGRAM OF THE SYNCHRONISM INPUTS
Figure 132: Connection diagram of electrical synchronism inputs
For information about electrical synchronism input specifications, see Section 2.4 of the Specifications
Summary of Contents for Reason RPV311
Page 2: ......
Page 15: ...INTRODUCTION CHAPTER 1...
Page 34: ...SAFETY INFORMATION CHAPTER 2...
Page 45: ...HARDWARE DESIGN CHAPTER 3...
Page 56: ......
Page 57: ...CONFIGURATION CHAPTER 4...
Page 75: ...RPV311 Chapter 4 Configuration RPV311 TM EN 6 75 Figure 21 Email Fax configuration...
Page 77: ...RPV311 Chapter 4 Configuration RPV311 TM EN 6 77 Figure 22 Adding and editing voltage circuits...
Page 117: ...OPERATION CHAPTER 5...
Page 121: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 121 Figure 46 Status monitoring sequence...
Page 123: ...RPV311 Chapter 5 Operation RPV311 TM EN 6 123 Figure 47 Monitoring sequence...
Page 128: ...Chapter 5 Operation RPV311 128 RPV311 TM EN 6 Figure 50 Equipment settings monitoring sequence...
Page 155: ...RECORDS CHAPTER 6...
Page 172: ......
Page 173: ...TW FAULT LOCATOR CHAPTER 7...
Page 183: ...PMU CHAPTER 8...
Page 189: ...MODBUS CHAPTER 9...
Page 193: ...DNP3 CHAPTER 10...
Page 196: ......
Page 197: ...GOOSE MESSAGE DETECTION CHAPTER 11...
Page 200: ......
Page 201: ...SOFTWARE RPV TOOLS CHAPTER 12...
Page 228: ......
Page 229: ...SOFTWARE RPV MANAGER CHAPTER 13...
Page 249: ...COMMUNICATIONS CHAPTER 14...
Page 261: ...INSTALLATION CHAPTER 15...
Page 295: ...Chapter 15 Installation RPV311 RPV311 TM EN 6 295 Figure 138 RA331 RA332 and RA333 dimensions...
Page 299: ...MAINTENANCE AND TROUBLESHOOTING CHAPTER 16...
Page 310: ...TECHNICAL SPECIFICATIONS CHAPTER 17...
Page 331: ...RPV311 Chapter 17 Wiring Diagrams WIRING DIAGRAMS CHAPTER 18...
Page 340: ...APPENDIX A...