Operation
P846/EN OP/D
MiCOM P846
(OP) 5-7
P4088ENa
OP
Figure 4: Frequency response of the Kalman-filter used in the DLO
The fundamental positive and negative sequence voltage and current phasors and the DC
components are the signals that are transferred from the Kalman filter to the next stage of
the algorithm, the preprocessor.
1.3.3
Preprocessing stage
A significant amount of the algorithm engineering is contained in this stage. The main
variables computed by the pre-processor MW, MVar, KA and KV are simply the classical
positive sequence active power, reactive power, line current and bus voltage, acquired using
a single cycle response Kalman Filter. The other variables, derived from the main ones, are
computed with various FIR (finite impulse response) filters, peak detectors, averaging
functions, slope detection and delta detection algorithms. The output of the
preprocessor is a
set of ten variables to be processed by the fuzzy-logic engine.
For convenience, all variables are converted to per unit quantities using the two following
base parameters specified in the relay settings:
Vbase: Base voltage equal to the rated line to line voltage
Pbase: Base power equal to the line surge impedance loading (SIL)
a
nditions, the positive sequence quantities used
in the pre-processor are not consistent, due to hard signal distortion as in faulty conditions or
severe switching transients (open-line energization). These two special conditions can be
recognized and the corresponding signals modified to ensure their physical continuity and
consistency.
The fault detector provides the fault signal which is a pulse of duration equal to that of the
actual fault. It is used to improve the reliability and security of the relay. Indeed, the
prolonged fault signal allows the blocking to zero of some decisional variables during the
fault. The overall behaviour of the detector is to provide a pulse of duration equal to that of
the actual fault or magnitude discontinuity superimposed on the positive sequence voltage.
For the time period that this indicator is active, three pre-processor variables are inhibited
and blocked to their default values.
Besides these ten variables, the pre-processor generates two additional signals to handle
f ult and start-up conditions. Under these co
Summary of Contents for MiCOM P846
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Page 6: ...P846 EN SS H11 Safety Section SS...
Page 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Page 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Page 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Page 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Page 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Page 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Page 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Page 78: ...P846 EN OP D Operation MiCOM P846 OP...
Page 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Page 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Page 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Page 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Page 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Page 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Page 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Page 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Page 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Page 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Page 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Page 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Page 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Page 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Page 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Page 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Page 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Page 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Page 282: ...P846 EN IN D Installation MiCOM P846 IN...
Page 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Page 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Page 297: ......