background image

MICS 

 

P14DB-MC-EN-7 

 

 

MiCOM 40 Agile P14DB 

(MC) 25 

 

1.5.11 

Common Data Class:  DPC_CTRL_PRV_NS 

Description: 

Controllable Double Point (NAME SPACE) 

CDC Class: 

DPC                              

Attribute 

Type 

FC  Enumeration  Comment 

ctlVal 

BOOLEAN 

   

Control value (Off - FALSE, On - TRUE) 

  

bypass 

ENUMERATED8 

(MMS Type: BSTR16)

 

Bypass 

Bypass 

origin 

Originator 

ST     

Originator of the last change of the 
controllable data 

  

stVal 

CODED_ENUM 

(MMS Type: _BSTR2)

 

ST  Dbpos 

Status value of the data (Intermediate 
state, Off, On or Bad-state) 

  

Quality 

ST     

Quality of the status value 

  

TimeStamp 

ST     

Timestamp of the last change in state of 
status value 

  

ctlModel 

ENUMERATED8 

(MMS Type: INT8)

 

CF  ctlModel 

Control model (Corresponding to the 
behaviour of the data) 

  

sboTimeout  INT32U 

CF     

Select Before Operate timeout period (in 
milliseconds) 

  

cdcNs 

VISIBLE_STRING255  EX     

Common Data Class name space 

  

cdcName 

VISIBLE_STRING255  EX     

Name of the Common Data Class 

  

1.5.12 

Common Data Class:  DPL_STANDARD 

Description: 

Standard Device Name Plate 

CDC Class: 

DPL                              

Attribute  Type 

FC  Enumeration  Comment 

vendor 

VISIBLE_STRING255  D 

   

Name of the vendor 

  

ChwRev 

VISIBLE_STRING255  D 

   

Hardware revision 

  

CswRev 

VISIBLE_STRING255  D 

   

Software revision 

  

CserNum  VISIBLE_STRING255  D 

   

Serial Number 

  

Cmodel 

VISIBLE_STRING255  D 

   

Model Number 

  

Clocation  VISIBLE_STRING255  D 

   

Physical location of device    

1.5.13 

Common Data Class:  INC_CTRL_PRV_NS 

Description: 

Controllable Integer Status NAME SPACE 

CDC Class: 

INC                              

Attribute  Type 

FC  Enumeration  Comment 

ctlVal 

INT32 

   

Control value 

  

bypass 

ENUMERATED8 

(MMS Type: BSTR16)

 

Bypass 

Bypass 

stVal 

INT32 

(MMS Type: INT8)

 

ST  Mod 

Status value of the data 

  

Quality 

ST     

Quality of the status value 

  

TimeStamp 

ST     

Timestamp of the last change in state of 
status value 

  

ctlModel 

ENUMERATED8 

(MMS Type: INT8)

 

CF  ctlModel 

Control model (Corresponding to the 
behaviour of the data) 

  

cdcNs 

VISIBLE_STRING255  EX     

Common Data Class name space 

  

cdcName  VISIBLE_STRING255  EX     

Name of the Common Data Class 

  

dataNs 

VISIBLE_STRING255  EX     

Data name space 

  

 

Summary of Contents for Micom P14DB

Page 1: ...to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or disclosure to thi...

Page 2: ......

Page 3: ...ns a data model built from instances of specific Logical Nodes and must consist of at least an instance of the LPHD Logical Node which is responsible for providing physical device information and an i...

Page 4: ...quency Rate of Change DfpPFRC2 PFRC_NO_SEG df dt 2 Frequency Rate of Change DfpPFRC3 PFRC_NO_SEG df dt 3 Frequency Rate of Change DfpPFRC4 PFRC_NO_SEG df dt 4 Frequency Rate of Change DfpPFRC5 PFRC_NO...

Page 5: ...ive Sequence OcpPTOC1 PTOC_SEG I 1 Overcurrent OcpPTOC2 PTOC_SEG I 2 Overcurrent OcpPTOC3 PTOC_SEG I 3 Overcurrent OcpPTOC4 PTOC_SEG I 4 Overcurrent OcpPTOC5 PTOC_SEG I 5 Overcurrent OcpPTOC6 PTOC_SEG...

Page 6: ...ions for Control operations PloGGIO1 GGIO_IND_64_CTRL Controllable Inputs RlyGGIO1 GGIO_IND_8 Output Contacts 1 4 Logical Node definitions The definition tables for each of the Logical Nodes in the to...

Page 7: ...61850 7 4 2003 PTOC_NO_SEG PTOC Timed Overcurrent w r t No Phase Segregation IEC 61850 7 4 2003 PTOC_SEG PTOC Timed Overcurrent w r t Phase Segregation IEC 61850 7 4 2003 PTOF_NO_SEG PTOF Over frequen...

Page 8: ...single alarm Alm3 SPS_D General single alarm Alm4 SPS_D General single alarm Alm5 SPS_D General single alarm Alm6 SPS_D General single alarm Alm7 SPS_D General single alarm Alm8 SPS_D General single...

Page 9: ...S_D General single alarm Alm46 SPS_D General single alarm Alm47 SPS_D General single alarm Alm48 SPS_D General single alarm Alm49 SPS_D General single alarm Alm50 SPS_D General single alarm Alm51 SPS_...

Page 10: ...m Alm91 SPS_D General single alarm Alm92 SPS_D General single alarm Alm93 SPS_D General single alarm Alm94 SPS_D General single alarm Alm95 SPS_D General single alarm Alm96 SPS_D General single alarm...

Page 11: ...Ind4 SPS_D General indication binary input Ind5 SPS_D General indication binary input Ind6 SPS_D General indication binary input Ind7 SPS_D General indication binary input Ind8 SPS_D General indicati...

Page 12: ..._D General indication binary input Ind7 SPS_D General indication binary input Ind8 SPS_D General indication binary input Ind9 SPS_D General indication binary input Ind10 SPS_D General indication binar...

Page 13: ...binary input Ind48 SPS_D General indication binary input Ind49 SPS_D General indication binary input Ind50 SPS_D General indication binary input Ind51 SPS_D General indication binary input Ind52 SPS_...

Page 14: ...NS Single point controllable status output SPCSO23 SPC_CONTROL_NS Single point controllable status output SPCSO24 SPC_CONTROL_NS Single point controllable status output SPCSO25 SPC_CONTROL_NS Single p...

Page 15: ...Single point controllable status output SPCSO61 SPC_CONTROL_NS Single point controllable status output SPCSO62 SPC_CONTROL_NS Single point controllable status output SPCSO63 SPC_CONTROL_NS Single poi...

Page 16: ...Overvoltage NVD Behaviour X NgvMod INC_CTRL_PRV_NS Negative Sequence Overvoltage Mode X NgvBeh INS_BEH_D_PRIV Negative Sequence Overvoltage Behaviour X ThmMod INC_CTRL_PRV_NS Thermal Overload Mode X...

Page 17: ...supply Energy flow towards bus bar DmdWh BCR_PRIV Real energy demand Energy flow from bus bar DmdVArh BCR_PRIV Reactive energy demand Energy flow from bus bar MTRRs SPC_CTRL_PRV_NS Reset Energy Meters...

Page 18: ..._HEALTH Health NamPlt LPL_LN Name Plate SeqA SEQ_MAG_ANG Positive Negative and Zero sequence current SeqV SEQ_MAG_ANG Positive Negative and Zero sequence voltage ImbNgA MV_FLOAT Imbalance negative seq...

Page 19: ...ering Statistics w r t Average Voltage No Current LN Class MSTA Attribute Attr Type Explanation T X Mod INC_MOD Mode Beh INS_BEH Behaviour Health INS_HEALTH Health NamPlt LPL_LN Name Plate AvVolts1 MV...

Page 20: ...ical Node PTOC_SEG Description Timed Overcurrent w r t Phase Segregation LN Class PTOC Attribute Attr Type Explanation T X Mod INC_MOD Mode Beh INS_BEH Behaviour Health INS_HEALTH Health NamPlt LPL_LN...

Page 21: ...tion LN Class PTOV Attribute Attr Type Explanation T X Mod INC_MOD Mode Beh INS_BEH Behaviour Health INS_HEALTH Health NamPlt LPL_LN Name Plate Str ACD_SEG Start Op ACT_SEG Operate T 1 4 27 Logical No...

Page 22: ...N Name Plate Str ACD_NO_SEG Start Op ACT_NO_SEG Operate T 1 4 30 Logical Node PTUV_NO_SEG Description Undervoltage w r t No Phase Segregation LN Class PTUV Attribute Attr Type Explanation T X Mod INC_...

Page 23: ...rnal equipment health OpCnt INS_BASIC Operation counter Lock SPC_CTRL_PRV_NS Prevention i e Lock Trip Close operations of the Circuit Breaker over IEC 61850 X Pos DPC_CTRL_PRV_NS Switch position BlkOp...

Page 24: ...ith earth current has happened dirNeut ENUMERATED8 MMS Type INT8 ST dir Earth current direction unknown forward or backward q Quality ST Quality of the protection activation information t TimeStamp ST...

Page 25: ...Timestamp of the last change in state of protection activation information 1 5 5 Common Data Class ACT_NO_SEG Description Protection Activation Information w r t No Phase Segregation CDC Class ACT At...

Page 26: ...Measurement range configuration attributes 1 5 9 Common Data Class CMV_MAG_FLOAT Description Complex Measured value w r t Floating Point Magnitude CDC Class CMV Attribute Type FC Enumeration Comment...

Page 27: ...Class 1 5 12 Common Data Class DPL_STANDARD Description Standard Device Name Plate CDC Class DPL Attribute Type FC Enumeration Comment X vendor VISIBLE_STRING255 D Name of the vendor ChwRev VISIBLE_ST...

Page 28: ...Description Integer Status w r t Behaviour CDC Class INS Attribute Type FC Enumeration Comment X stVal INT32 MMS Type INT8 ST Beh The element status q Quality ST The quality of the status value t Tim...

Page 29: ...1 5 21 Common Data Class LPL_LN Description Standard Logical Node Name Plate CDC Class LPL Attribute Type FC Enumeration Comment X vendor VISIBLE_STRING255 D Name of the vendor CswRev VISIBLE_STRING25...

Page 30: ...Attribute Type FC Enumeration Comment X c1 CMV_MAG_ANG_FLOAT Sequence component 1 For semantic meaning see seqT c2 CMV_MAG_ANG_FLOAT Sequence component 2 For semantic meaning see seqT c3 CMV_MAG_ANG_F...

Page 31: ...ta name space 1 5 27 Common Data Class SPC_STATUS Description Controllable Single Point w r t Status Only CDC Class SPC Attribute Type FC Enumeration Comment X stVal BOOLEAN ST Status value of the dat...

Page 32: ...te Type FC Enumeration Comment X phsA CMV_MAG_FLOAT Measurement values for Phase A phsB CMV_MAG_FLOAT Measurement values for Phase B phsC CMV_MAG_FLOAT Measurement values for Phase C 1 5 32 Common Dat...

Page 33: ...c remote maintenance or process 1 6 3 Component RangeConfig_Deadband Comment Measurement range configuration Parent Type RangeConfig Attribute Type Enumeration Comment X min AnalogueValue_Float Minimu...

Page 34: ...The definition of the enumerations are according to IEC 61850 7 3 and IEC 61850 7 4 unless otherwise stated 1 7 1 Enumerated type AddCause Description AddCause Ordinal Semantic 0 Unknown 1 Not suppor...

Page 35: ...Semantic 1 None 2 Open 3 Close Open 4 Open Close Open 5 Close Open Close Open 1 7 5 Enumerated type ctlModel Description Control Model Ordinal Semantic 0 status only 1 direct with normal security 2 sb...

Page 36: ...n Mode Ordinal Semantic 1 on 2 blocked 3 test 4 test blocked 5 off 1 7 10 Enumerated type multiplier Description Exponents of the multiplier value in base 10 Ordinal Semantic 24 y 21 z 18 a 15 f 12 p...

Page 37: ...umerated type seqT Description Sequence Measurement Type Ordinal Semantic 0 pos neg zero 1 dir quad zero 1 7 13 Enumerated type SIUnit Description SI Units derived from ISO IEC 1000 Ordinal Semantic 1...

Page 38: ...5 F 26 C 27 S 28 H 29 V 30 ohm 31 J 32 N 33 Hz 34 lx 35 Lm 36 Wb 37 T 38 W 39 Pa 41 m 42 m 43 m s 44 m s 45 m s 46 m m 47 M 48 kg m 49 m s 50 W m K 51 J K 52 ppm 53 1 s 54 rad s 61 VA 62 Watts 63 VAr...

Page 39: ...FLOAT64 Double 64 bit floating point value INT128 Int64 128 bit signed integer value INT16 Short 16 bit signed integer value INT16U Ushort 16 bit unsigned integer value INT24U Ulong 24 bit unsigned i...

Page 40: ...ct or will apply to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or d...

Reviews: