DRAIN BACK UNIT (DBU) INFORMATION - Fig. 6
Positioning
The DBU must be located within 3 metres of the top of the Solar collector, see Fig. 8. The pipework from the collector to
the DBU
must always
fall by a minimum of 40 mm per metre and
must be
insulated with high temperature pipe
insulation.
Dimensions
The dimensions of the DBU and clearances required for servicing are shown in Fig. 6.
Water connections
The connections at the top and bottom of the DBU are shown in Fig. 6.
Alpha SolarSmart 90 - General Information
Fig. 6
DBU Connections
A
Return from collector to DBU 12 mm
B
Flow from DBU to collector
15 mm
C
Flow from cylinder to DBU
15 mm
D
Return from DBU to cylinder 15 mm
Top
Bottom
Front
Side
55
50
68
10
10
365
A
B
C
D
50 55
198
35
460
35
100
270
450
Serial No. inside DBU,
left above pump
100