DOOR RELEASE DIAGRAMS
Set jumpers as shown in the chart below. This supplies 16VAC to the door strike through the K & D
terminals when the inside station
DOOR
Button is pressed.
The length of activation time is determined by the dipswitch settings (approx. 2, 10, or 25 seconds).
Set jumpers as shown in the chart below. This example shows the wiring for a Multi-Tap Transformer
(8/16/24 VAC) to supply 24VAC to a door strike when the inside station
DOOR
Button is pressed, while also
supplying 16VAC for system power. Pay special attention to the transformer wiring and terminal markings.
The length of activation time is determined by the dipswitch settings (approx. 2, 10, or 25 seconds).
Set jumpers as shown in the chart below. This configuration supplies continuous 24VDC to a magnetic lock
through the L+ & L- terminals which is shut off when the inside station
DOOR
Button is pressed allowing the
door to be opened. Insure that proper polarity is observed.
16VAC
DOOR
STRIKE
24VAC
DOOR
STRIKE
24VAC
DOOR
STRIKE
24VDC
MAG
LOCK