9
9400016-J0 Rev D
2.3 System Configurations
The following four configurations are currently available for the CXPS-E3 power system. For more ordering informa-
tion, refer to the CXPS-E3 Ordering Guide on the Alpha website.
Table A —
CXPS-E3 Configuration
Rack Size
Controller
Expanded
I/O
Current
Rating
Rectifier
Capacity
Load
Breakers
Battery
Breakers
Shunt
LVD
(Optional)
Height
19"
CXC HP
L-ADIO
400A
8x 2.4kW
(2 shelves)
21
0
Load
No
5 RU
16
5
Battery
LVBD
5 RU
23"
CXC HP
L-ADIO
400A
10x 2.4kW
(2 shelves)
26
0
Load
No
5 RU
21
5
Battery
LVBD
5 RU
19"
CXC HP
L-ADIO
400A
5x 4kW
(1 Shelf)
21
0
Load
No
7 RU
16
5
Battery
LVBD
7 RU
23"
CXC HP
L-ADIO
400A
6x 4kW
(1 Shelf)
26
0
Load
No
7 RU
21
5
Battery
LVBD
7 RU
2.3.1 CXPS-E3 19" Systems with 48-2.4kW Rectifiers
• Rated for 400A with two 2.4kW shelves
• 5RU with two 2.4kW shelves
• 21 load breakers with load shunt or 16 load and 5 battery breakers with battery shunt
• CXC-HP controller
• L-ADIO module with extensive I/O capability
• Option for LVBD for battery breaker configuration
2.3.2 CXPS-E3 23" Systems with 48-2.4kW Rectifiers
• Rated for 400A with two 2.4kW shelves
• 5RU with two 2.4kW shelves
• 26 load breakers with load shunt or 21 load and 5 battery breakers with battery shunt
• CXC-HP controller
• L-ADIO module with extensive I/O capability
• Option for LVBD for battery breaker configuration
Figure 3 — 23" CXPS-E3 with 48-2.4kW Rectifiers