Cordex Integrated System Controller (CXCI) Option
The CXCI option is mounted in the converter system shelf and brings advanced monitoring technology to the
Cordex series of converters. This compact system controller is designed for seamless operation and set up of
Alpha power systems and is equipped with the complete range of Cordex software (
version 1.97 minimum
)
features, including the following:
•
Designed to communicate directly with Cordex converters
•
Provides local and remote communications
•
User definable alarms
•
Daily logging of system events and statistics.
Behind the CXCI’s front panel lies the main controller motherboard, which contains a microprocessor, memory, as
well as numerous other electronic components.
The CXCI includes a web server providing easy set up and monitoring using an Internet connection with the
standard Windows® Internet Explorer browser.
The data logging feature allows the user to capture data from multiple inputs, for AC/DC voltages, load/battery
current, cell voltages & temperatures (automatically for up to 16 user defined logs). Typical applications of the
CXCI logging include power system details, thermal performance of outdoor enclosures, battery cell specifics, or
mains variations captured by an AC voltage watchdog.
A built-in audio speaker sounds an intermittent tone during active alarms.
The input/output (I/O) board houses a series of terminal connections; located at the rear of the system shelf via a
D-sub connector.
NOTE:
Customer settings for the CXCI will be provided separately in the system documentation package.
2.3
System Controller Front Panel
Figure 2–Cordex CXCI model system controller front panel
(Photo is for reference only – subject to installation requirements)
2.3.1
Display
The CXCI has a 4-digit display for monitoring system voltage (V) and current (A). A pushbutton toggle switch
allows the user to alternate the display reading.
Hard reset
(push once)
Soft reset
(push once)
[Hold for 3 seconds
to reset IP address]
Ethernet port
LCD screen (V/A)
Display pushbutton
toggle switch (V/A)
Port for Alpha DC
modem (e/w cable)
only
System status
LEDs
Details of controller operation
are provided in the current
version software manual
(
version 1.97 minimum
).