background image

Using

 

the

 

On/Off

 

Button

 

(Continued) 

Shut

 

off:

 

Press the on/off button for more than 3 seconds.

Self

 

test:

 

When the unit is connected to line power, press the on/off button.

Buzzer

 

off:

 

Except for the low battery and overload alarms, turn off the buzzer by pressing the on/off button for 1 second.

Alarms

 

and

 

Troubleshooting 

This unit has several audible alarms. To turn off the alarm, press the power button. 

Slow

 

Alarm

 

(1

 

beep

 

every

 

2

 

seconds):

 

Most alarms except for low battery and overload. See the troubleshooting table.

Low

 

Battery

 

Alarm

 

(1

 

beep

 

every

 

1

/

2

 

second):

 

The  unit  is  operating  on  battery  power  and  the  battery  is  almost

discharged. This alarm cannot be shut off. 

Overload

 

(continuous

 

beeping):

 

The unit is overloaded and it automatically turns itself off. Disconnect unnecessary loads

and restart the unit. This alarm cannot be shut off. 

Symptom 

Troubleshooting

 

Table 

Causes 

Action 

Unit

 

does

 

not

 

turn

 

on,

 

the

LED

  is not on.

The power switch is not 
pushed.

 

Push it for more than 1 second

 

Battery voltage less than 20 
VDC.

 

Plug the unit into the line for at 
least 6 hours to recharge the 
battery then restart.

 

Load less than 20W when 
unit is in battery mode.

 

This is normal. The unit's "green 
mode" is active.

 

PCB  failure.

 

Contact AOE.

 

Unit

 

is

 

always

 

in

 

battery

mode.

 

Power cord loose.

 

Plug it in.

 

AC fuse blown or breaker 
tripped.

 

Replace the fuse or reset the 
breaker.

 

PCB  failure.

 

Contact AOE.

 

Backup

 

time

 

less

 

than

predicted

 

Battery is not charged.

 

Plug the unit into the line for at 
least 6 hours to recharge the 
battery then restart.

 

PCB  failure.

 

Contact AOE.

 

The

 

buzzer

 

is

 

continuously

beeping

 

The unit is overloaded.

 

Turn off some of the loads.

 

Page 

3

 to 

7

Summary of Contents for Tetrex 500

Page 1: ...Tetrex 500 USER MANUAL...

Page 2: ...outlined in this manual One at a time turn on the loads lf the buzzer is continuously on the unit is over loaded Turn off unnecessary loads To turn the unit off press the On Off button for more than...

Page 3: ...on the unit Green mode When green mode is on and the line becomes unqualified and less than 20 watts of power is drawn by the loads the unit automatically turns off When the line is requalified the u...

Page 4: ...t automatically turns itself off Disconnect unnecessary loads and restart the unit This alarm cannot be shut off Symptom Troubleshooting Table Causes Action Unit does not turn on the LED is not on The...

Page 5: ...Novell Netware and Linux Contact AOE for more information The software lets you Turn off the unit Set up an alarm when line power is unqualified Shut off power to the loads before the battery is drai...

Page 6: ...al Transfer Time mSec 2 to 4 including detection time Safety UL CSA CE Protection Spike Protection 480 Joules 2 mSec lnput Fuse or circuit breaker Overload Automatic power off if overload exceeds 110...