background image

20

We reserve the right to modify technical specifications without prior notice.
UK830500/190402 

© Alpha-InnoTec GmbH

Installation of the control 

element

  DANGER!

 

Danger  of  fatal  injury  due  to  electric 
current!

 

Electrical  connections  may  be  installed 
only by qualified electricians.

 

Before  opening  the  unit,  disconnect  the 
system from the power supply and secure 
it from being switched back on!

Situated  at  different  heights  in  the  front  facade  of  the 
unit are recesses (each with 4 recesses) for fastening the 
control element:

1  four upper recesses
2  four lower recesses

4  hooks  are  located  on  the  back  side  of  the  control 
element and can be used to hang the control element on 
the front facade of the unit:

Proceed as follows:

  Hang  the  control  element’s  hooks  on  the  recesses 

of  the  front  facade  (either  in  the  upper  or  lower 
recesses)…

Example:
Control element in upper recesses

  Push  the  control  element  down  until  it  locks  into 

position…

  Stick the heating and heat pump regulator’s control 

cable into the 

right

 bushing on the bottom of the 

control element…

  NOTICE.

 

A connection to a computer or a network 
can  be  installed  via  the  left  bushing  on 
the  bottom  of  the  control  element,  thus 
allowing  the  heating  and  heat  pump 
regulator  to  be  controlled  remotely.  One 
pre-condition  is  that  a  screened  network 
cable (category 6) be installed through the 
unit when installing the unit.

  Operating manual for the heating and heat pump 

regulator,  version  “Qualified  technician”,  “Web 
server” section.

Summary of Contents for SWC 100H

Page 1: ...We reserve the right to modify technical specifications without prior notice UK830500 190402 Alpha InnoTec GmbH COMPACT Operating Manual Heat Pumps BRINE WATER UK SWC Series...

Page 2: ...s for the respective model This operating manual is intended only for persons as signed to work on or operate the unit Treat all con stituent parts confidentially The information contained herein is p...

Page 3: ...h cooling function 18 INSULATING THE HYDRAULIC CONNECTIONS 19 OVERFLOW VALVE 19 Inspecting and setting up the overflow valve 19 INSTALLATION OF THE CONTROL ELEMENT 20 INSTALLATION AND REMOVAL OF THE S...

Page 4: ...gned or removed without the express writ ten permission of the manufacturer EC conformity The unit bears the CE mark of conformity EC declaration of conformity Safety The unit is operational safe when...

Page 5: ...ap plicable laws directives and standards for the recovery recycling and disposal of materials and components of cooling units Dismantling Operating principle of heat pumps Heat pumps operate on the...

Page 6: ...pump system op erates efficiently and ecologically the following are espe cially important ENERGY SAVING TIP Avoid unnecessarily high flow tempera tures A lower flow temperature on the hot wa ter sid...

Page 7: ...at pump regulator Variant 2 Automatic switching from heating to cooling op eration and vice versa This variant can operate using a cooling curve NOTICE Variant 2 is possible only if a Comfort board av...

Page 8: ...ng manual of the heat pump and heating regulator DANGER Service and repair work on the compo nents of the unit may be performed only by customer service personnel authorized by the manufacturer Overvi...

Page 9: ...bserve the following when performing all work NOTICE Always comply with applicable accident prevention regulations with applicable statutory regulations ordinances and di rectives WARNING The heat pum...

Page 10: ...oden pallet and during transport This can result in personal injury and damage to the unit Take suitable precautionary measures to eliminate the danger of tipping DANGER Make sure to secure unit again...

Page 11: ...y sound insulated surface Make sure that the founda tion is designed for the weight of the heat pump Overview Technical data scope of delivery General unit data section Compensate for minor unevenness...

Page 12: ...very Heat source and Heating circuit sections CAUTION When installing the connections always secure the connections on the unit from twisting in order to prevent damage to the copper pipes in the inte...

Page 13: ...source is integrated in the unit The expansion vessel for the heating circuit and the cor responding cap valve are included in the scope of deliv ery They must be integrated in the heating circuit on...

Page 14: ...nt Electrical connections may be installed only by qualified electricians Before opening the unit disconnect the system from the power supply and secure it from being switched back on DANGER Observe t...

Page 15: ...upply of the heat pump with a 3 pole automatic cut out with at least 3 mm contact gap Note the level of the release current Overview Technical data scope of delivery Electric section CAUTION The senso...

Page 16: ...circuit RINSING AND FILLING THE HEAT SOURCE Contamination and deposits in the heat source can cause malfunctions Proceed as follows Rinse heat source system thoroughly Thoroughly mix the anti freeze a...

Page 17: ...UT COOLING FUNCTION Bleeding is conducted automatically by means of the in tegrated bleeding function in the safety component Add only anti freeze mixed with water to the heat source CAUTION The conce...

Page 18: ...ixing valve from A and B to AB Reset servo motor of the mixing valve to automatic as soon as bleeding is completed NOTICE Push switch on servo motor up BLEEDING THE HEAT SOURCE FOR A UNIT WITH COOL IN...

Page 19: ...nd heat pump regulator Operating manual of the heating and heat pump regulator Turn the adjusting knob of the overflow valve until the temperature difference spread between the forward and return flow...

Page 20: ...used to hang the control element on the front facade of the unit Proceed as follows Hang the control element s hooks on the recesses of the front facade either in the upper or lower recesses Example...

Page 21: ...facade you must first remove the screen s temporary cover and then reinsert it above the logo Screen at time of delivery 1 recess for control element 2 logo 3 temporary cover First insert the screen...

Page 22: ...pted to the heating capacity of the heat pump We offer a variety of hot water tanks for you to choose from They are optimized for use with your heat pump NOTICE Integrate the hot water tank in the hea...

Page 23: ...ng element 2 Reset button Dismantling DANGER Danger of fatal injury due to electric current Electrical connections may be installed only by qualified electricians Before opening the unit disconnect th...

Page 24: ...ctions Heating circuit Heat source Refrigerant Refrigerant type Quantity kg Electric Voltage code all pole circuit breaker heat pump A Voltage code circuit breaker control voltage A Voltage code circu...

Page 25: ...0 34 0 33 1300 1 206 221 G1 AG G1 AG R407c 2 3 3 PE 400V 50Hz C10 1 N PE 230V 50Hz B10 3 N PE 400V 50Hz C10 2 22 4 1 0 78 6 9 20 20 6 4 2 0 08 n n 0 2 n n 9 2 12 0 5 25 1 5 813171 d SWC 120H K 11 7 4...

Page 26: ...ctions Heating circuit Heat source Refrigerant Refrigerant type Quantity kg Electric Voltage code all pole circuit breaker heat pump A Voltage code circuit breaker control voltage A Voltage code circu...

Page 27: ...0 20 9 6 3 0 2 n n 0 25 n n 13 0 18 0 5 35 1 5 813174 d SWC 230 K 22 1 4 3 20 0 3 2 22 5 4 5 20 55 5 25 47 60 3700 4900 5900 0 74 0 68 3700 25 13 1900 3900 4500 0 41 0 38 2700 2 345 360 R1 IG R1 IG R4...

Page 28: ...0 1 0 2 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacity Pe Power consumption COP Coef ci...

Page 29: ...6 0 7 0 8 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacity Pe Power consumption COP Coef cien...

Page 30: ...0 9 1 0 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacity Pe Power consumptio...

Page 31: ...0 9 1 0 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacity Pe Power consumptio...

Page 32: ...8 0 9 1 0 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacity Pe Power consumpt...

Page 33: ...0 6 0 7 0 8 0 9 1 0 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacity Pe Powe...

Page 34: ...4 0 5 0 6 0 7 0 8 0 9 1 0 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacity P...

Page 35: ...3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Temperature heat source Qh Heating capacit...

Page 36: ...0 m3 h p p p bar 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 m3 h p p Legend UK823000L 170408 Volume ow heating water Volume ow heat source Temp Tempera...

Page 37: ...1 SWC 120H bis SWC 170H AG 1 1 4 5 Durchf hrungen f r Elektro F hlerkabel 6 Sicherheitsbaugruppe im Beipack 1 2 4 3 B A Legend UK819248b All dimensions in mm A Front view B Top view C Rear view D Cont...

Page 38: ...lation on sylomer strips C Top edge of nished oor D Distance to next lateral object 20 E Shaded area free space for service purposes We reserve the right to modify technical specifications without pri...

Page 39: ...heitsbaugruppe im Beipack Achtung Im Lieferumfang enthalten 4x Kompensator DN 40 Rp 1 1 2 IG DIN 2999 Legend UK819253b All dimensions in mm A Front view B Top view C Rear view D Control element 1 Heat...

Page 40: ...lateral object 20 E Shaded area free space for service purposes F In the event of offset mounting of the compensators the dimension 400 can be reduced to 250 The bracket must be provided by the custom...

Page 41: ...I 9I 5 I 7I I I 3 I I I I I I IA I I I D I I I I I I I I 19 2 2 2 I I I I I 5 C 0 0 0 0 I 5 I I I I I I I I I I I 0 9I I I I I E 0 5 C 9I I I I I I I I I I I I I I I I I 9I I B C E I I I I I I 47 7 H...

Page 42: ...I I I I I I I I I I 5 7I I I I 9I 5 I 7I I I 3 I I I I I I I I 0 I I 9I I I I I I 9I I I I I I I I I I I I I I I I I I I I 9I I I I I I B E 09I HI 09I EI 09I EI 0 5 0 0 0 C 5 0 I C 0 5 47 7 H I 0 I 5...

Page 43: ...3 A B C B F F 7F 1 5 F D F F F F F F0 F F F0 F 5 F F F F F F F F F F F F F F F F 0 F F F F F 0 F F F F 1 0 F F F F F F F F F F F FEF BF F 9F F F F F 2 A B C A C F F0 F 9F 5 F FD F 5 F 5 A C A B C 1 F...

Page 44: ...F B C 4 F 1 B 5 5 5 5 5 1 F F F 5 C F F 1 F F F F F F F F 1 1 F F F 5 D 1 D 5 B B 2 F 6 9F F F F0 F 9F 5 F FD D F F F F 9F F F0 F F F 1 F F 9F F F0 F F F 1 FD 54 4 2 6 F B7 7 4 5 F 2 4 B C D 2 4 B C D...

Page 45: ...1 C A B C 9F F F F F F F F F F 1 2 F F B F A B C 5 5 F F A C F F F F F F F F F F C F0 F 9F 5 F FD F F F F F F F F F F FEF BF F F F F 5 F 7F F F 3 5 5 F A B C F F 7F 0 A C F F F F F F0 F F F0 F 1 5 2 4...

Page 46: ...4 1 D 1 F F F 5 F F F F F F F F F F 1 F F F F F F F F 9F F F F F 1 F F 9F F F0 F F F D F F F F F F F 9F F 2 1 C F F F F F B F F F F 1 F5F4BCF 6 1 5 2 4 2 6 F B7 7 4 5 F 2 4 B C D 2 4 6 B C D B C D 2...

Page 47: ...F F F A C F F F B 1 F F F F 5 F 7F F F 3 F F A C F F F F F F0 F F F0 F F0 F 9F 5 F FD 0 5 F 5 5 F F F A B C 0 A B C 9F F F F F F F F F F F F F F F C 1 4 2 6C F B7 7 4 5 F 2 4 B C D 2 4 6 B C D B C D...

Page 48: ...5 1 4 F0 F 9F 5 F FD F F 1 F F F F F F F F F F F F 5 1 F F 6 1 F B 9F F D C 1 F F 9F F F0 F F F F F F 9F F F0 F F F 2 F F F 1 5 1 F F F 1 F5F4BCF 9F F F F F 1 4 2 6C F B7 7 4 5 F 2 4 B C D 2 4 6 B C D...

Page 49: ...B F F F F F F F F F F F F F 0 F F F F F F F F F F A C F F F F F 1 F F F 0 F F F F F F D 5 F 5 A B C F0 F 9F 5 F FD F F F A B C 5 F A C F F F 5 F 7F F F 3 F F F F F F0 F F F0 F F F F F F F F F F F F F...

Page 50: ...F F 9F F F0 F F F 9F F F F B D C F F F 1 F5F D F F F F F F F F F F F F F F F F 5 B 5 D 5 F B F F F 9F F F0 F F F 6 F F F F F F F F F F F F F F F F C F F 1 F 27 C7 666 5 F 2 4 B C D 2 4 6 B C D B C D...

Page 51: ...SWC 100H K 100 393 SWC 120H 100 384 SWC 120H K 100 394 SWC 140H 100 385 SWC 140H K 100 395 SWC 170H 100 386 SWC 170H K 100 396 SWC 230 100 387 SWC 230 K 100 397 SWC 70H 100 381 SWC 70H K 100 391 EC D...

Page 52: ...0 362 SWP 500H 100 367 SWP 820 100 363 SWP 700H 100 375 SWP 1100 100 372 SWP 850H 100 376 SWP 1250 100 373 SWP 1000H 100 377 EC DIRECTIVES STANDARDIZED EN 98 37 EG EN 378 EN 349 2006 95 EG EN 60529 EN...

Page 53: ...otection screen installed q Yes Rotary field of fan q O K Heat source brine heat source water Heat source volume flow q O K Motor protection setting A Rotary field of heat source circulating pump q O...

Page 54: ......

Page 55: ...the date you will be contacted by phone I hereby confirm that all preliminary work required for commissioning has been carried out and completed The system is ready for operation Requested commissioni...

Page 56: ......

Page 57: ...57 We reserve the right to modify technical specifications without prior notice UK830500 190402 Alpha InnoTec GmbH...

Page 58: ...fr DE Alpha InnoTec GmbH Industriestrasse 3 95359 Kasendorf Tel 49 0 9228 99 06 190 Fax 49 0 9228 99 06 199 Hotline 49 0 171 26 63 326 info alpha innotec com www alpha innotec com AT Peter Rie Mannhe...

Page 59: ...act 73 6921 RZ Duiven Tel 31 0 26 445 98 45 Fax 31 0 26 445 93 73 info nathan nl www nathan nl NO Alpha InnoTec Norge AS Langgaten 59 4306 Sandnes Tel 47 0 51 6605 95 Fax 47 0 51 6605 94 info alpha in...

Page 60: ......

Reviews: