Specifications
900-0161-01-01 Rev B
65
Table 17
Radian Menu Items
Field
Item Default
Minimum
Maximum
(Gen Alert)
ON: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(Gen Alert ON)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Gen Alert)
OFF: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Gen Alert OFF)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Vent Fan)
ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Vent Fan)
Off Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert)
ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(DC Divert ON)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert)
OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(DC Divert OFF)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert)
ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(AC Divert ON)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert)
OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(AC Divert OFF)
Delay
0.5 minutes
0.1 minutes
25.0 minutes
Inverter
Stacking
Stack Mode
Master Master,
Slave
Power Save
Ranking
Mode =
Master
:
Master Power Save Level
0 0 31
Mode =
Slave
:
Slave Power Save Level
1 1 31
Grid-Tie Sell
Grid-Tie Enable
Y
Y
or
N
Sell Voltage
52.0 Vdc
44.0 Vdc
64.0 Vdc
Module Control
Module Control
GS8048A
Auto
Auto, Left, Right, Both
GS4048A
Left
Auto, Left, Right, Both
Calibrate
Grid AC Input Voltage
X
0 Vac
–7 Vac
7 Vac
Gen AC Input Voltage
X
0 Vac
–7 Vac
7 Vac
Output Voltage
X
0 Vac
–7 Vac
7 Vac
Battery Voltage
X
0.0 Vdc
–0.8 Vdc
0.8 Vdc
Grid Interface Protection Menu
Operating
Frequency
Operating Frequency
X
60 Hz
50 Hz, 60 Hz
Mains Loss
Clearance Time
X
2.0 seconds
1.0 seconds
25.0 seconds
Sell Current
Limit
Maximum Sell
Current
GS8048A
X
30 Aac
5 Aac
30 Aac
GS4048A
15 Aac
5 Aac
15 Aac
Grid Support
Defaults shown
are for IEEE
1547 setting
Grid Support Functions
X
N/A
Start Ramp
,
Freq/Watt
,
Ramp Rates
,
Volt/Watt
,
Fixed PF
,
Volt/VAr
Regulatory Specification
X
IEEE 1547
IEEE 1547
,
HECO Rule 14
,
AS4777
,
ABNT 16149
,
CA Rule 21
Low/High Voltage
Ride-Through
OV2
Volts
X
144 Vac
120 Vac
144 Vac
Mode
Cont.
Cont.
,
Mand.
,
Perm.
,
Mom.
,
Cease
Trip
0.16 seconds
0.12 seconds
5.00 seconds
OV1
Volts
X
132 Vac
120 Vac
140 Vac
Mode
Cont.
Cont.
,
Mand.
,
Perm.
,
Mom.
,
Cease
Trip
1 second
1 second
50 seconds
UV1
Volts
X
106 Vac
60 Vac
120 Vac
Mode
Cont.
Cont.
,
Mand.
,
Perm.
,
Mom.
,
Cease
Trip
2 seconds
1 second
50 seconds
UV2
Volts
X
60 Vac
60 Vac
106 Vac
Mode
Cont.
Cont.
,
Mand.
,
Perm.
,
Mom.
,
Cease
Trip
11 seconds
1 second
50 seconds
UV3
Volts
X
60 Vac
0 Vac
105 Vac
Mode
Cont.
Cont.
,
Mand.
,
Perm.
,
Mom.
,
Cease
Trip
0.16 seconds
0.12 seconds
21 seconds
Summary of Contents for OutBack Power GS8048A
Page 1: ...Radian Series Inverter Charger GS4048A GS8048A Operator s Manual ...
Page 6: ...Table of Contents 6 900 0161 01 01 Rev B THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...Operation 20 900 0161 01 01 Rev B NOTES ...
Page 56: ...Troubleshooting 56 900 0161 01 01 Rev B NOTES ...
Page 67: ...Specifications 900 0161 01 01 Rev B 67 NOTES ...